21
MODGAS-XWR2 Technical Guide
I/O Map
See
Table 2, this page
to reference the inputs and outputs that
are available on the MODGAS-XWR2 Module.
Analog Inputs
Reset Input (RST IN)
This input is only required when the module is in Stand-Alone
Mode. The Supply Air Temperature Setpoint can be reset by
supplying a 0-10 VDC signal to the RST IN low voltage terminal
block. This reset signal is optional and is only used if you require
resetting of the Supply Air Temperature.
Supply Air Temperature Sensor (SAT)
This input is only required when the module is in Stand-Alone
Mode. The Supply Air Temperature Sensor is the control source.
This sensor has to be installed for the unit to operate. The Supply
Air Temperature Sensor is located in the discharge air stream and
monitors temperature to maintain the Supply Air Temperature
Setpoint.
Binary Inputs
Heat Enable Contact (HEAT EN)
This input is only required when the module is in Stand-Alone
Mode; it is not required when used as an expansion board to other
AAON unit controllers. The Heat Enable input is activated by
a 24 VAC signal. The module will not operate without 24 VAC
being applied to this input terminal when used in a Stand-Alone
Mode.
Proof of Ignition 1 (PO-IGN1)
The Proof of Ignition input is activated by a 24 VAC signal
supplied from the ignition module to enable the modulating
Gas Valve 1 (and the modulating Gas Valve 2 in the 2V1IGN1S
configuration). If the flame does not ignite, the ignition module
will turn off this enable and the MODGAS-XWR2 will turn on
the “No Proof of Flame” Alarm.
Proof of Ignition 2 (PO-IGN2)
The Proof of Ignition input is activated by a 24 VAC signal
supplied from the ignition module to enable the modulating Gas
Valve 2. If the flame does not ignite, the ignition module will
turn off this enable and the MODGAS-XWR2 will turn on the
“No Proof of Flame” Alarm.
Communicating Outputs
Gas Valve Output 1
This communicating output will control the modulating gas
valve. It can detect if the valve is connected and can verify the
valve position.
Gas Valve Output 2
This communicating output will control the modulating gas
valve. It can detect if the valve is connected and can verify the
valve position.
Relay Outputs
RLY1 - Fan Enable
This relay works in conjunction with the Low Speed Fan Relay
(RLY2) to control the speed of the blower motor. When the
MODGAS-XWR2 has heat enabled, this relay closes to bring
the blower on at high speed. The module will activate the Low
Speed Fan Relay (RLY2) to reduce the blower speed as the gas
valve modulates closed.
RLY2 - Low Speed Fan
Depending on the gas valve position, this relay will close to
switch the blower to low speed. The module automatically
switches the blower to low speed as the gas valve modulates
closed in order to maintain proper fuel to air ratios.
RLY3 - Heat 1
Once the MODGAS-XWR2 brings on heat, Heat 1 (RLY3) is
the first stage of heat.
NOTE:
In the 2V2IGN1S configuration, Heat 1 (RLY3)
and Heat 2 (RLY4) are one stage.
Analog Inputs
1
(RST IN) Reset Signal
2
(SAT) Supply Temperature
3
(AUX AI) Not Used
Binary Inputs
1
(AUX BI) Not Used
2
(HEAT EN) Heat Enable
3
Proof of Ignition 1 (PO-IGN1)
4
Proof of Ignition 2 (PO-IGN2)
Analog Outputs (0-10 VDC)
1
Fan
2
Low Speed Fan
3
Heat 1
4
Heat 2
5
Heat 3
6
Heat 4
Table 2: MODGAS-XWR2 Inputs and Outputs
INPUTS AND OUTPUTS
Inputs and Outputs