Page 28
HV/HW-CEP Series
+
+
Weighing
mode
Press
To set the LOLO
limit vaue
Press
To set the LO
limit vaue
Press
Press
To set the HI
limit vaue
Press
To set the HIHI
limit vaue
Weighing
mode
Weighing
mode
Press
To set the LO
limit vaue
Press
To set the HI
limit vaue
Weighing
mode
Press
Weighing
mode
Press
To set level 1
lower limit vaue
Press
To set level 2
lower limit vaue
Press
To set level 3
lower limit vaue
Press
To set level 3
upper limit vaue
Press
To set level 4
upper limit vaue
Weighing
mode
Press
To set level 5
upper limit vaue
Press
+
11.2.
Entering the comparator values
1. In the weighing mode, press and hold the
SET
key and press the
COMP
key to enter
the comparator value setting mode.
2. Enter the comparator values using the following keys.
0 to 9 To enter numerical value
C
To cancel settings
SET
To switch b and -
ENTER
To store setting values
* Each time the
SET
key is pressed,
“
-
”
switches between being lit and off at the
first digit.
“
-
”
being lit means a minus setting.
3. When the setting is complete, “
end
”
is displayed and the scale returns to the
weighing mode. (At this time, power-on-zero is not performed.)
Example of five-level
comparator mode
Example of three-level
comparator mode
(upper/lower limit mode)
Example of seven-level
comparator mode (portion
weighing mode)
With the HW-60KCEP, set as
follows.
LOLO 8.500 kg
LO 10.000 kg
HI 10.500 kg
HIHI 12.000 kg
With the HV-200KCEP, set as
follows.
LO 148.85 kg
HI 152.5 kg
With the HV-15KCEP, set as follows.
Level 1 (LOLO) 0.500 kg or more
Level 2 (LO) 1.000 kg or more
Level 3 (OK) 1.500 kg to 2.000 kg
Level 4 (HI)
up to 2.500 kg
Level 5 (HIHI)
up to 3.000 kg
* With the HV-C models, the
scale changes the
minimum display digit
depending on the display
range. Enter 0 for the final
digit.
Содержание HV-15KCEP
Страница 15: ...HV HW CEP Series Page 13 The label on the scale ...
Страница 44: ...MEMO ...
Страница 45: ...MEMO ...
Страница 46: ...MEMO ...
Страница 47: ......