AAF Flanders AstroHood S-I Скачать руководство пользователя страница 1

AstroHood

 

S-lI

AstroHood

 S-l & S-ll  

Ducted HEPA Terminal Hoods

AstroHood S-l

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Содержание Flanders AstroHood S-I

Страница 1: ...AstroHood S lI AstroHood S l S ll Ducted HEPA Terminal Hoods AstroHood S l INSTALLATION OPERATION AND MAINTENANCE MANUAL ...

Страница 2: ... Grid T Bar Ceiling 06 Field Installed Trim for Hard Gypsum Ceilings 06 07 PermaFrame 08 Grille Installation and Removal 09 10 Filter Unpacking Installation Storage and Operation 11 12 Aerosol Injection and Static Pressure Upstream Aerosol Ports 12 13 Damper Options and Operation 14 15 Insulation Options 15 Appendix A Warranty Information 16 Appendix B Manual Revision History 17 Contacting AAF Fla...

Страница 3: ... government codes laws and policies Before proceeding with installation operation or maintenance review this Installation Operation and Maintenance Manual in its entirety and all safety procedures with your company s safety personnel Precautions Units must be properly transported and handled since improper transport and or handling can result in damage blemishes or other imperfections Deliveries a...

Страница 4: ...he lowest operational pressure drop and thus energy savings of any damper configuration available Its pressurized plenum design also leads the industry in airflow uniformity The S ll unit comes standard with Guillotine damper but Spilt Butterfly or ESD damper options are available All standard mounting and trim options are available wire suspension rod suspension grid T bar ceilings and clean ceil...

Страница 5: ... or side and in round or square rectangular configurations For side inlets damper options are limited to ESD and Guillotine Flexible duct connections should be made using stainless steel worm gear type draw bands supplied by others for maximum reliability For square rectangular inlets contractor is responsible for securing and sealing duct work to factory supplied blank flange Examples of inlets s...

Страница 6: ...by others The hardware is adjusted to secure the housing to the ceiling by cinching the field installed trim option to the underside of the hard ceiling There are four 4 clean ceiling flanges with one 1 located on each side of the housing The clean ceiling angles are welded to the housing body and are of the same material as the housing The AstroHood unit should be leveled and secured to the ceili...

Страница 7: ...d unit into the opening and seat the unit onto the grid T bar Apply uniform pressure to ensure the flange is bonded to the grid T bar see Fig 07 4 Remove excess RTV Fig 07 Flange Mount for Grid T Bar Ceiling Flange is the same material as housing Flange is not designed to support ceiling Field Installed Trim for Hard Gypsum Ceilings The AstroHood unit can be installed from either above the ceiling...

Страница 8: ...anroom 4 Remove the trim and apply a continuous small bead diameter of RTV Dow Corning 732 or GE 102 recommended to the ceiling mating surface of the trim 5 Reinsert the trim align the holes and secure in place using blind closed rivets see Fig 10 Fig 11 a It is important to use closed end or blind rivets b Otherwise dirty air may travel along the rivet shaft and into the cleanroom 6 Remove excess...

Страница 9: ...s guarantees a smooth cleanable surface White powder coat paint is supplied as standard finish The PermaFrame is ordered separately from the AstroHood unit Drawing Notes Construction 18 ga cold rolled steel or 304 stainless steel For SS finish use SS suffix unit supplied painted white standard IL Inside Length IW Inside Width Model Number Actual Dimensions inches Weight lbs AstroHood L W IL IW 2 x...

Страница 10: ... people perform this task To replace grille 1 Align the holes in the grille with the four studs 2 Hold the grille in place and reinstall the flat washers and acorn nuts To avoid potential injury it is strongly recommended two people perform this task 3 Hand tighten the acorn nuts Do not use a wrench or socket as overtightening may damage the threaded connection Grille Installation and Removal The ...

Страница 11: ...h both safety cables 3 Rotate the grille upward to the closed position 4 Push the turn fasteners into their receptacles and rotate 90 degrees clockwise to lock in place To remove grille 1 While supporting the underside of the grille with one hand rotate the turn fasteners 90 degrees counterclockwise to disengage the fasteners 2 Carefully pivot the grille downward so that it is hanging freely by th...

Страница 12: ...e careful to keep the filter away from your body and any objects in your path If the bag is not present always handle filter by the frame avoiding contact with the media and or face screen Remove the bag carefully Avoid bringing hands and fingers into contact with the filter media Additional precautions for gel seal filters Care is taken at the factory to prevent the bag from contacting the gel Be...

Страница 13: ...op Aerosol Injection and Static Pressure Upstream Aerosol Ports All S l and S ll units are supplied with room side aerosol injection port and aerosol dispersion system as well as an upstream static pressure upstream aerosol sample port to facilitate validation testing These ports are available as either standard 3 8 female NPT fittings supplied with respective plugs or as 3 8 chrome plated female ...

Страница 14: ...ng normal operating conditions Simply connect the mating male component into the female fitting to introduce aerosol or take measurements as needed The CPC side thumb latch allows for simple one handed disconnection and seating of the check valve Fig 20 Quick Connect Disconnect Aerosol Injection and Static Port Fig 21 Quick Connect Disconnect Aerosol Injection and Static Port ...

Страница 15: ...superior airflow uniformity The ESD is operated and adjusted from the room side with a Phillips head screwdriver via mechanical rod and rack pinion control affording infinite fine tuning adjustment over a minimum of ten 10 full turns and making it inherently self locking see Fig 23 The Guillotine Damper is operated from the room side by a mechanical rod linkage assembly of stainless steel construc...

Страница 16: ...ation Options Insulation options are available to prevent heat loss mitigate potential condensation and or provide sound attenuation Determining the use of these options is the responsibility of the design engineer The 2 foil backed option is an aluminum foil backed fiberglass installed 6 0 R value attached to the housing using adhesive mounted insulation anchors and caps The Armaflex option is a ...

Страница 17: ...removal and re installation of such product s or goods including but not limited to labor service costs and shipping charges The same obligations and conditions shall extend to replacement parts furnished by the Seller hereunder This parts warranty and any optional extended warranties are granted only to the original user Seller s duty to perform under this or any warranty may be delayed at Seller...

Страница 18: ...17 APPENDIX B MANUAL REVISION HISTORY Revision Version Revision Date Description of Change Approval ...

Страница 19: ...Bartow FL Columbia MO Fayetteville AR Hudson NY Momence IL Ontario CA Smithfield NC Tijuana Mexico Votorantim Brazil Washington NC Europe Cramlington UK Gasny France Vitoria Spain Ecoparc France Trencin Slovakia Vadstena Sweden Vantas Finland Asia Middle East Riyadh Saudi Arabia Shah Alam Malaysia Suzhou China Shenzhen China Miaoli Taiwan Bangalore India Noida India Yuki Japan Nippon Muki For Tech...