 Classroom Self-Contained Unit Ventilator

Model AEQ

MicroTech

 

II™, Electromechanical Controls

©2006 McQuay International

IM 798  (10-06)

Vertical Floor Self-Contained Air Source Heat Pump – Model AEQ

Improper installation can cause equipment damage, personal injury or death. Before beginning
installation, please read this publication in its entirety.
Develop a thorough understanding before starting the installation procedure.
This manual is to be used as a guide. Each installation is unique, so only general topics are covered.
The order in which topics are covered may not be those required for the actual installation.

IMPORTANT!

C

Installation Manual

IM 798

Group:  

Unit Ventilator

Part Number: 106506240

Date: 

 October 2006

Содержание AEQ

Страница 1: ...al injury or death Before beginning installation please read this publication in its entirety Develop a thorough understanding before starting the installation procedure This manual is to be used as a...

Страница 2: ...Details 28 Wall Sleeve Junction Box Electrical Terminals 29 30 Step 5 Installing the Unit Ventilator Pre Installation Checklist 31 Remove Packaging and Inspect the Unit s 31 Before Moving the Unit Up...

Страница 3: ...nance or use can cause fire electrical shock or other conditions which can result in personal injury or property damage This product must be installed only by personnel with the training experience sk...

Страница 4: ...rtage and any damage on all copies of the freight bill If damage or shortages are found the consignee should 1 Note any visible damage to the shipment or container on all copies of the delivery receip...

Страница 5: ...ich does notbecom e appar entuntil themerch andise has been unpac ked The conte ntsmay be dama ged intransi tdue torough handl ingeven thoug hthecarton may not show extern aldama ges Such dama geisthe...

Страница 6: ...are installed before the AE unit is installed On many jobs the louver and wall sleeve are shipped ahead of the unit itself Installation instructions for these components are shipped with the individu...

Страница 7: ...efully locate the area of interior and exterior wall to be removed Determine the appropriate location on the interior wall where the unit ventilator is to be installed Using the rear edge of the wall...

Страница 8: ...ning size The following is a typical procedure for installing in existing masonry walls Follow local codes and safety procedures If the Model AE unit is to be installed in an existing classroom an ope...

Страница 9: ...made watertight See the louver splitter and wall sleeve installation sections Shut off valves for hot water and steam must be flush with the floor to allow unit installation and removal see piping arr...

Страница 10: ...ional Grille Detail 28 711 mm 21 2 63 5 mm Table 4 Wall Louver Dimensions Check Required Size Unit Size Width Height IN MM IN MM 024 030 841 2 2140 281 4 715 036 040 961 2 2444 281 4 715 044 048 054 1...

Страница 11: ...sleeve properly caulk it for a weather tight seal to help prevent moisture from seeping into the wall Sealing is critical in preventing freeze ups cold drafts air infiltration and to prevent moisture...

Страница 12: ...Figure 24 Typical Louver Installation with Sloped Flashing Unit Louver D Seal Wall Sleeve Cross Channel No Caulk between flashing and louver Recess Louver a Minimum of 1 16 Beyond the Building Facade...

Страница 13: ...louver from the building exterior Louver dimensions are 1 16 1 6 mm except as noted Intake and discharge must not be restricted Trees shrubs etc must be a minimum of 30 762 mm away from intake Louver...

Страница 14: ...711 mm A End Panel L L C Louver Louver 1 1 Seals Seals L C Unit Partial or Full Unit Recess Application B C IN MM IN MM Full Recess 165 8 422 113 8 289 Partial 195 8 498 83 8 213 Recess 217 8 556 61 8...

Страница 15: ...he sleeve in this fashion No holes are provided in the louver or in the wall sleeve for this type of mounting the holes must be drilled in the field Mounting hardware must also be provided by the inst...

Страница 16: ...ontal air splitter between louver and wall sleeve must be installed Angle Bracket Mounting to Interior Surface Figure 33 ThisisavariationoftheinstallationshowninFigure32 where the angle brackets are m...

Страница 17: ...ng Collar on Exterior Surface Sealant or gasketing material also on sides Wall Sleeve Wall Intake Louver Maximum Recess 2 Minimum Recess 1 16 Flange is caulked on inside top and two sides to seal to b...

Страница 18: ...e wall sleeve during shipping and is field assembled Figure 39 Wall Sleeve Dimensions for Recessed Applications CAUTION The opening between the wall sleeve and the louver must be completely enclosed b...

Страница 19: ...pth Consult approved AAF HermanNelson submittal drawings for the job to determine the proper amount of recess if any and recommended wall opening size The AE unit chassis attaches to the wall sleeve t...

Страница 20: ...ally recessed into a Masonry Thick Wall Top View Finished Wall Opening Dimension LR Table 8 Wall Sleeve Wall Column for Anchoring Wall Sleeve Wall Sleeve Junction Box Holes for Securing to Floor Wall...

Страница 21: ...Wall Sleeve Finish Top Unit Inside Top 1 2 13mm 195 8 498mm Room Projection 41 2 102mm 81 8 206mm 111 2 292mm Figure 45 165 8 Room Projection or Full Wall Sleeve Recess Shading indicates portion of un...

Страница 22: ...harge air and the outdoor air inlet b Therearenoairleaksaroundtheperimeterofthewallsleeve where it adjoins the wall 10 Install a drain tube by others into the building drain system for the removal of...

Страница 23: ...cation shown By Others Louver must be sealed air and watertight at top and both ends By Others Building must be sealed between Wall Sleeve and under Louver for water run off Pitch toward Louver D Seal...

Страница 24: ...wall sleeve to provide air and water tight seal to interior wall of building 2 Level the wall sleeve horizontally and plumb the wall sleeve vertically 3 Mark top bottom at D seal flange and sides whe...

Страница 25: ...tal Air Splitters By Others Apply sealant by others to bottom edge of unit not shown and to top flange and both end flanges of wall sleeve as shown This must provide a watertight seal to the wall of t...

Страница 26: ...f 7 8 22 2 mm O D Cooper Drain Tube by AAF HermanNelson 7 5 8 194 mm 8 1 2 216 mm Drain tube by others Drain tube must not interfere with the damper linkage or caster Tube must pitch down and must not...

Страница 27: ...59 3 Bring the main power through the waterproof conduit to the junction box on the wall sleeve to the terminal lugs on the upstreamsideofSW1 MainPowernon fused ON OFF switch See Figure 60 for termin...

Страница 28: ...fined in this area SW1 Main Power Nonfused On Off Switch AAF HermanNelson 875 Dia Knockouts 3 Safety Precaution Reverse this cover when unit is removed from wall sleeve to cover opening in the end of...

Страница 29: ...for MicroTech II and Electromechanical 10 pin MicroTech II only 12 pin MicroTech II only 3 Remove the wall sleeve junction box terminal lugs cover plate 4 Insert the unit chassis main power wires 21 2...

Страница 30: ...always be maintained throughout the network Always connect to and to The shield connection must be continuous throughout the entire network and must be connected to earth ground at one and only one po...

Страница 31: ...very important that the unit be lifted only from the end designated on the carton Forks on the forklift should be minimum of 72 inches long Strap type sling of nylon or other material should be used r...

Страница 32: ...the drainage space at the bottom of the outdoor air louver has been cleaned up Adequate access space for maintenance service and unit removal has been provided Wall sleeve is properly sealed air and w...

Страница 33: ...replacement Procedure Wall and floor must be at 90o to one another If not the floor needs to be leveled 90o to wall Be sure that the outdoor section drain pan notches are not blocked see Figure 50 an...

Страница 34: ...ed Place the washers over the threaded studs and tighten the mounting nuts see cautions Turned out bottom flange on wall sleeve cross channel for fastening to floor 7 fasteners AE 024 030 8 fasteners...

Страница 35: ...1 4 42 7 45 0 High 6 elem 14 8 42 7 69 4 70 0 Low 3 elem 7 3 18 4 38 9 40 0 High 6 elem 14 6 36 7 61 9 70 0 Low 3 elem 7 3 9 2 19 3 20 0 High 6 elem 14 6 18 4 30 8 35 0 187 229 207 253 33 Elec Heat 46...

Страница 36: ...230 60 1 2 5 6 0 23 7 129 Elec Heat 208 60 1 Volt Hz Ph Voltage Range Room Fan FLA Outdoor Fan FLA Compressor Heating Options Min Max RLA LRA Heater KW Low 3 elem 12 0 57 7 116 6 125 0 High 6 elem 24...

Страница 37: ...Connections DISCONNECT ALL ELECTRICAL POWER BEFORE SERVICING UNIT TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK DANGER USE COPPER CONDUCTORS ONLY UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER...

Страница 38: ...s network wiring between these units needs to be field installed Optional network communication is provided via plug in communication modules that connect directly to the UVC 2 Communication Module op...

Страница 39: ...es on the indoor coil 13 Outdoor Direct Expansion DX Coil Refrigerant Temperature Sensor S5 The S5 sensor is installed on the unit ventilator s outdoor refrigerant coil on the right hand side of the c...

Страница 40: ...operation only Fan Only Fan operation only Auto Unit automatically switches between heating cool ing and economizer operation to satisfy the room load conditions The current unit state is also displa...

Страница 41: ...drill with 8 mm 5 16 in drill bit for surface mounting only WARNING MicroTechII Remote Wall Mounted Sensor WARNING To avoid electrical shock personal injury or death 1 Installer must be qualified exp...

Страница 42: ...ch II Wall Mounted Sensor allows for two mounting methods wall box mounting and surface mounting Note Wall box mounting requires the large mounting base Use either the large or small mounting base for...

Страница 43: ...dial into place on the sensor making sure that the dial points straight up 5 Replace the sensor on the mounting base Repairs and Replacement No repair options available Call your local AAF McQuay repr...

Страница 44: ...nd subject to change without notice See unit for actual wiring diagram DISCONNECT ALL ELECTRICAL POWER BEFORE SERVICING UNIT TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK DANGER USE COPPER CONDUC...

Страница 45: ...d subject to change without notice See unit for actual wiring diagram DISCONNECT ALL ELECTRICAL POWERBEFORESERVICINGUNIT TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK DANGER USE COPPER CONDUCTORS...

Страница 46: ...ED Control Wiring Step 6 Unit Electrical and Control Connections Figure 91 Unit Mounted Manual Changeover Two stage Electric Heat Applies to units produced after Jan 2001 Unit Mounted Manual Changeove...

Страница 47: ...Control Connections Figure 94 20 Outside Air Unit Mounted Auto Changeover One stage Thermostat with Wet Heat or Electric Heat Applies to units produced after Jan 2001 AEQ AED UNIT MOUNTED AUTO CHANGE...

Страница 48: ...trols Applies to units produced after Jan 2001 Step 6 Unit Electrical and Control Connections Note These are typical wiring diagrams and subject to change without notice See unit for actual wiring dia...

Страница 49: ...d with enough hardware to assemble one right hand and one left hand filler having a combined length of 18 or less The minimum length of one Attach Through Guide Channel into Top Top Rear Top Support T...

Страница 50: ...ts Fit Front Alignment Bar Into Welded Notches Permitting Alignment Of Storage Accessories With The Unit Ventilator Adjustable Kick Plate And Leg Levelers Alignment Slot Cabinet Assembly Figure 98 12...

Страница 51: ...t Insert through upper mounting holes inside unit end compartment and thread into tinnerman clips on the end panel Attach the end panel to the unit using four 4 5 32 hex socket head fasteners provided...

Страница 52: ...Matic Wall Louvers Recommended Maximum Number of VentiMatic Wall Openings VentiMatic Shutters Shutter s B C For Wall Louvers Which Can Be Mounted Air Capacity On Standard Louver Maximum Length Height...

Страница 53: ...tails Dimensions As Directed By Architect 3 4 19mm Approx 7 178mm Cement Mortar Steel Interior Wall Grille Optional See Note 3 125 8 314mm 3 4 19mm Approx Bird Screen Do Not Block Drain Holes With Cau...

Страница 54: ...age to electronic or electrical components from incorrect or fluctuating power supply stray static electricity or building automation network inputs 5 Inaccessibility of unit for service or parts inst...

Страница 55: ...clude Wall Sleeves Alu minum Louvers Aluminum Grilles Caster Kits End Panels Spare Filters MicroTech II Remote Wall Sensors temperature See instructions shipped with accessories and install according...

Страница 56: ...across the top of a door window louver or wall sleeve opening that supports the weight of the structure above it LONWORKS An enabling technology for creating inter operable control net works Develope...

Страница 57: ...er Illustration Typical 6 Installing The Unit Ventilator 31 35 Installing VentiMatic Shutter 53 54 Installing Wall Sleeve 18 26 L Lifting Moving and Stacking 4 Louver Installation Considerations 11 Lo...

Страница 58: ......

Страница 59: ......

Страница 60: ...ale including Limited Product Warranty Consult your local McQuay Representative for warranty details Refer to Form 933 43285Y To find your local McQuay Representative go to www mcquay com This documen...

Отзывы: