TM-3POS-115 

3 Position Control Card 

Installation & Maintenance Manual

 

 

 

 

06/19/20 

www.atcontrols.com 

IOM08107 REVISION 02

 

  

 
INSTALLATION: 
 

  The TM-3POS-115 control card should be mounted to 

a metal bracket to properly dissipate the heat 
generated by the solid-state outputs.   

 

  A 1000 Ohm or 5000 Ohm potentiometer is used for 

position feedback and must connect to terminals 5, 6 
& 7.  The wiper will connect to terminal 6. The other 
two leads connect to terminal 5 and 7 so when the 
actuator is rotating CCW, the resistance or voltage is 
increasing between terminals 5 & 6.   

 

  The motor and capacitor connect to terminals 8, 9 & 

10.  The neutral from the motor connects to terminal 9 
and the lead that drives the motor CCW to terminal 8 
and the lead that drive the motor CW to terminal 10.   

 

  The incoming 115VAC power is connected to 

terminals 1 & 2, with LINE on terminal 1 and 
NEUTRAL on terminal 2.  

 

  A ground should be attached to a grounding lug 

inside actuator housing. 

 

  The 115VAC input control signals connect to terminal 

3 & 4. Each input should be powered through it’s own 
individual switch or relay contacts.  

 
 
OPERATION: 
 

The TM-3POS-115 control card can be operated to any 
of three different positions by providing 115VAC to input 
terminals 3 and 4.in two different positioning modes.  
 

IN 2 (#4)

 

IN 1 (#3) 

POSITION 

DEFAULT 

0 V

 

0 V 

MID 

0 V

 

115 V 

CW 

115 V

 

0 V 

CCW 

115 V

 

115 V 

MID 

 
CALIBRATION: 
 

  Set jumper JP1 to the S (Set) position and supply 

power to terminals 1 and 2. 

 

 

  Move to middle position using [CW] or [CCW] 

buttons.  Adjust the potentiometer to its mid-range. 
This is indicated when the voltage between terminal 5 
& 6 is approximately 2.5VDC, or somewhere between 
2.25VDC and 2.75VDC. Tighten the potentiometer 
gear and cam shaft gear set screws.

 

 

  Press [SET 1 + 2] button to program this position into 

memory as the position to move to when Input 1 and 
Input 2 are supplied 115V.

 

 

  Move actuator to clockwise position using [CW] or 

[CCW] buttons. Press [SET 1] button to program this 
position into memory. This will be the position the 
actuator moves to when Input 1 is supplied 115V.

 

 

  Move actuator to counter-clockwise position using 

[CW] or [CCW] buttons. Press [SET 2] button to 
program this position into memory. This will be the 
position the actuator moves to when Input 2 is 
supplied 115V.

 

 

  Move the jumper JP1 from the S (SET) position to    

R (RUN) position.  The actuator can now be tested 
with the inputs to terminal 3 & 4.  

 

 
 

NOTE:

 The actuator can be programmed to any of the 

three positions for any of the input logic. Just move the 
actuator to the desired position, and press the button 
corresponding to the desired input functionality.  

 
 
 
 

 
 
 

 

A-T Controls product, when properly selected, is designed to perform its intended function safely during its useful life.  However, the purchaser or user of A-T Controls products 
should be aware that A-T Controls products might be used in numerous applications under a wide variety of industrial service conditions.  Although A-T Controls can provide 
general guidelines, it cannot provide specific data and warnings for all possible applications.  The purchaser / user must therefore assume the ultimate responsibility for the 
proper sizing and selection, installation, operation, and maintenance of A-T Controls products.  The user should read and understand the installation operation maintenance 
(IOM) instructions included with the product and train its employees and contractors in the safe use of A-T Controls products in connection with the specific application.  
 
While  the  information  and  specifications  contained  in  this  literature  are  believed  to  be  accurate,  they  are  supplied  for  informative  purposes  only.  Because  A-T  Controls  is 
continually improving and upgrading its product design, the specifications, dimensions and information contained in this literature are subject to change without notice.  Should 
any question arise concerning these specifications, the purchaser/user should contact A-T Controls.   
 
For product specifications go to 

http://download.a-tcontrols.com/

 

 

A-T Controls, Inc. • 9955 International Boulevard, Cincinnati, OH 45246 • Phone: (513) 530-5175 • Fax: (513) 247-5462 • 

www.atcontrols.com

 