FSE Series Electric Actuator
Installation & Maintenance Manual
19
November 18, 2022
www.atcontrols.com
Engineering\documents\products\IOM\Iom08026.docx
b. Output Signal Setting (switches 3 – 5)
Output Signal
Switch State
4 – 20 mA
3 = OFF, 4 = ON, 5 = OFF
2 – 10 V
3 = ON, 4 = OFF, 5 = ON
c. Fail Position Setting (switches 6 – 8)
Switch S6 ON
Switch S6 OFF
20mA / 5V / 10V command is for fully closed (CW)
position
20mA / 5V / 10V command is for fully open (CCW)
position
Input Signal Fully Open (90°) Fully Closed (0°)
4 – 20 mA
4 mA
20 mA
1 – 5 V
1 V
5 V
2 – 10 V
2 V
10 V
Input Signal Fully Open (90°) Fully Closed (0°)
4 – 20 mA
20 mA
4 mA
1 – 5 V
5 V
1 V
2 – 10 V
10 V
2 V
Lost Signal Position
Switch State
Fully Open (90°)
7 = OFF, 8 = ON
Fully Closed (0°)
7 = ON, 8 = OFF
In Place
7 = ON, 8 = ON
Lost Signal Position
Switch State
Fully Open (90°)
7 = ON, 8 = OFF
Fully Closed (0°)
7 = OFF, 8 = ON
In Place
7 = ON, 8 = ON
The input signal type is set by switches 1 and 2. Switch 6 is used to set the corresponding relationship
between the value of the input signal and the operation direction of the actuator.