background image

40

• 

Temperature Screen:

  Displays  the  sensed  temperatures  of  the  Outlet,  Inlet,  and 

Tank probes. Also displayed is the calculated Delta T (Outlet 

minus Inlet) for the system. Shorted (“Short”) and disconnected 

(“----”) probes are also displayed.

• 

System Status Screen:

  This screen is used to view status of switch inputs and output 

states. An asterisk (*) is displayed next to  label when status is 

“True” (the description is fulfilled).  For example, if water is flowing, 

or detected by flow sensor, then an “*” will appear in front of Flow 

label (i.e. *Flow).  Another example would be the MRHL switch.  

If  outlet temperature is too high the display will show: *MRHL.

The System monitors the inputs at these times:
•  Low Gas, Hi Limit, and Hi Gas - at all times for a fault condition.

•  Tstat - at all times for open/closed conditions. 

•  Flow - for an on condition when pump is on (no check for off state)

•  Blower Prover - Pre and Post purge.

•  Igniter Current - for an on condition approximately 18 seconds 

after the Igniter is turned on until the igniter is turned off and an 

off condition at all other times.

•  Flame - for an on condition approximately 5 seconds after the 

gas valve is turned on until the valve is turned off and at all other 

times for an off condition.

•  Blocked Flue, Blocked Inlet during heating mode

Control Status Screen:

Displays status that the MCB micros are in. The MCB has 5 possible 

states and the FCB have 9. The normal MCB states sequence is to 

move from Idle to Pre-Circulate  when a call for heat is initiated. Once 

heat has been satisfied or the Thermostat is opened, the sequence 

moves to Post-Circulate and then back to Idle. If a fault occurs at 

any time, the process jumps out of sequence and goes directly to 

the appropriate Hard or Soft Fault state.

Description of MCB control states:

•  Idle:

  The yellow “Standby” LED is turned on and system waits for a 

heat request (determined by Thermostat or controlling probe 

inputs). All  outputs  are  off  in  this  state  except  that  if  Post-

Circulate time is set to continuous, pump will be on. When heat 

request is received, system moves to Pre-Circulate state.

•  Pre-Circulate:

  The yellow LED is turned off and the green “Running” LED is 

turned on. The green LED will remain on for all other states 

except the fault states.  Cold purging clears out any combustion 

gas that may be in the combustion chamber. When purging is 

complete the system moves to the Heat State.

•  Heat Stage

  The  system  will  command  FCB  micros  to  start  their  heat 

sequence.  will be activated in order based on an algorithm that 

determines how much heat is needed. The system will remain 

in this state until heat request is satisfied, Tstat is opened, or a 

fault occurs.

•  Soft Fault State: (See “Fault Description” section for list of soft 

and Auto Reset faults.)

  Pump remains on for selected post-circulate time to cycle hot water 

out of boiler.  The FCB is commanded to shut down and Alarm 

output is turned on. Green LED turns off and red “Service” turns 

on. MCB remains in this state until one of following occurs:

 

•  One hour passes (automatic restart after one hour)

 

•  If Communications error system will automatically  

 

restart if communications re-establishes.

 

•  If user presses Select key while current error screen is   

displayed (Hard reset).

 

•  If high-limit error - the outlet temperature drops below the 

high limit trip point minus the high limit differential. (outlet 

water temperature drops to safe level). The fault is logged 

in the error history when the fault  state is exited.

 

•  Hard Fault State: (See “Fault Description” section for list of 

soft and Auto Reset faults.)  The pump remains on for the 

selected post-circulate time to cycle the hot water out of the 

boiler. The FCB is commanded to shut down and the Alarm 

output is turned on.  The green LED turns off and the red 

“Service” turns on and off (flashes). The only way to exit 

this state is for the user to press the Select key while the 

current error screen is displayed. The fault is logged in the 

error history when the fault state is exited.

While the MCB is in the Heating mode the FCB moves from Idle, to 

Pre-Purge, to Heat Igniter, to Check for Flame, and then to Heating. 

The process waits in this state until the call for heat is satisfied, the 

thermostat input is opened, or a fault occurs.  When heat is satisfied, 

the sequence continues to Post-Purge and then back to Idle.  If 

three tries for ignition has been selected on the MCB dipswitch and 

flame is not detected at the appropriate time, then the sequence 

moves to the Inter-Purge state for 15 seconds and the FCB heat 

sequence is repeated. If flame is still not detected after the third try 

the process declares a fault, jumps out of sequence and goes to 

the error state. Other types of faults detected at any time will also 

cause a jump to the error state.

Description of FCB control states:

•  Idle State:

  When any error is declared during idle state-The system will 

remain in this state until the MCB request a heating cycle, or a 

cold purge.

•  Pre-Purge State:

  The blower is turned on.  After 10 to 34 seconds (34 seconds for 

cold purging) the system switches to the Heat Igniter State.  

•  Heat Igniter State:

  Sequence  of  operation  is  as  follows:  “The  igniter  relay  is 

energized and heat up period begins. After 18-20 seconds, if  

igniter has reached a minimum of 2.8 amps, gas valve safety 

circuit is then activated. If in this amount of time, igniter fails to 

reach a minimum amp draw of 2.8 amps, unit will re-cycle up to 3 

times before locking out on igniter hardware failure. If igniter does 

reach minimum required amp draw of 2.8 amps, gas valve circuit 

is energized, and system advances to Flame Check status.

•  Check for Flame State:

  The  gas  valve  is  turned  on.   After  1.5  seconds,  the  system 

checks that the gas valve relay is on.  If it is not, the ignition 

trial is considered to have failed and the system advances to 

the Inter-Purge state, if any ignition trials remain, otherwise an 

error is declared.

  The flame sensor is checked.  If flame is detected, the igniter 

is turned off.  The state machine then advances to the Heating 

State.  If after 5 seconds, the flame is still not sensed then the 

ignition trial is considered to have failed.  The state machine 

advances to Inter-Purge if any ignition trials remain, otherwise 

an error is declared.

•  Heating State:

  The  system  remains  in  this  state  until  the  call  for  heat  is 

cancelled or a fault occurs.  The system returns to the Idle state 

if the call for heat is cancelled, or satisfied and to the appropriate 

fault state if a fault occur. 

•  Inter-Purge State:

  The gas valve and the igniter are turned off.  The blower is on.  

After approximately 15 seconds the system goes back to the 

Heating Igniter State.

•  Post-Purge State

  The gas valve and the igniter are turned off.  If this stage 

does  not  have  a  blower  the  system  returns  to  the  idle 

state. If it does have a blower then the blower is left on.  

After  approximately  25  seconds,  the  system  returns  to 

the  Idle  state.

•  Error State

  The gas valve and the igniter are turned off. The FCB micro tells 

the MCB micro which error has occurred. The system waits in 

Содержание VB/VW 1500, 2000

Страница 1: ...ur building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mu...

Страница 2: ...45 Venting Maintenance 46 Heat Exchanger Preventive Maintenance 46 Tube Cleaning Procedure 46 Replacement Parts 46 LIMITED WARRANTY 43 TABLE OF CONTENTS 2 safe installation use and service 3 APPROVAL...

Страница 3: ...hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Страница 4: ...etup and instructions before lighting Failure to implement the proper setup will result in improper and inefficient operation of the appliance resulting in production of increased levels of carbon mon...

Страница 5: ...hout water 4 Sooting If the boiler has been exposed to flooding it must be replaced LIQUEFIED PETROLEUM GAS MODELS Boilers for propane or liquefied petroleum gas LPG are different from natural gas mod...

Страница 6: ...d trademark of Allegheny Ludlum Corporation The installation must conform to all instructions contained in this manual and the local code authority having jurisdiction These should be carefully follow...

Страница 7: ...60hz and 30 amps TABLE 2 ROUGH IN DIMENSIONS Models VB VW 1500 VB VW 2000 Dimensions inches mm inches mm Flue Outlet Diameter 7 178 7 178 Air Intake Diameter 6 152 6 152 Water Inlet 2 5 inch NPT Water...

Страница 8: ...Igniter is a device that ignites the main burner see Figure 3 When 120 VAC is applied to the igniter suf fi cient heat is generated to ignite the main burner Although improvements have been made to s...

Страница 9: ...s to the gas valve during operation FLOW SWITCH The flow switch pictured in figure 6 activates when sufficient flow has been established Switch will not close when flow is restricted or is not present...

Страница 10: ...Temperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic heating loop The boiler will modulate its firing rate in response to the actual system tempe...

Страница 11: ...use type fusible plug cartridge or linkage T P relief valve should have a temperature rating of 210 F 99 C a pressure rating not exceeding lowest rated working pressure of any system compo nent and a...

Страница 12: ...far as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the bu...

Страница 13: ...zed louvers and grilles should be fixed in the open position FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions should be used to calculate the size number and placement of openings pro...

Страница 14: ...wo permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts should communicate directly w...

Страница 15: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 3...

Страница 16: ...let into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30...

Страница 17: ...tion directly through an outside wall see Figure 11A 3 Horizontal Direct Vent using TWT to exhaust flue prod ucts and PVC piping to bring combus tion air to the boiler from the outside see Figures 12...

Страница 18: ...um of 6 feet 2 0m separation between the air intake and the exhaust terminals HORIZONTAL INSTALLATION REQUIREMENTS 1 The vent system must terminate with a AL 29 4C Vent Through the Wall Termination TW...

Страница 19: ...r parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation FIGURE 11 VERTICAL TERMINATION FIGURE 11A HORIZONTAL THROUGH THE WALL TERMIN...

Страница 20: ...ED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions should comply with NFPA 720 and be ANSI UL 2034 listed and CSA certified SIGNAGE A metal...

Страница 21: ...nt terminal NOTES If the exhaust vent terminal is within 10 3 0m of a wall or parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation...

Страница 22: ...R PARAPET ON SIDEWALL VENT INSTALLATION REFER TO 11A and 12 FOR SPACING SPECIFICATIONS FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS CLEARANCES SUPPORT ETC REFER TO FIGURES 11 AND 11A VERTICAL AIR INT...

Страница 23: ...expansion tank as shown in Figure 13 The sizing of the expansion tank for a closed system is very important and is directly related to the total water volume of the system Refer to Systems and Equipme...

Страница 24: ...ee support phone number on the back of this manual to order the Quad Thermistor Probe On domestic hot water applications the Remote Temperature Probe or the optional Quad Thermistor Probe must be inst...

Страница 25: ...ugh improper testing of gas lines or emergency malfunction of supply system the gas valves must be checked for safe operation Make sure that the outside vents on supply regulators and the safety vent...

Страница 26: ...the three voltage tests below Refer to Figure 12D for these tests Confirm RMS voltage between H and GND 108 VAC minimum 132 VAC maximum N and H 108 VAC minimum 132 VAC maximum N and GND 1 VAC maximum...

Страница 27: ...8 000 12 636 000 11 700 000 11 232 000 10 452 000 9 360 000 8 580 000 7 800 000 7 176 000 kW 10 508 7 219 5 848 4 980 4 432 4 021 3 701 3 427 3 290 3 061 2 741 2 513 2 284 2 102 Table 7 Suggested Pipe...

Страница 28: ...NE BOILER PRIMARY SECONDARY HYDRONIC PIPING SYSTEM LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE...

Страница 29: ...NK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITC...

Страница 30: ...STORAGE TANK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER...

Страница 31: ...DB F7 3 AMP FUSE PDB F3 7 5 AMP FUSE MCB II F1 24VDC GENERATION MCB II R K6 RELAY COIL MCB II MR HIGH LIMIT FLOW SWITCH LWCO SWITCH OPTIONAL LOW GAS SWITCH HIGH GAS SWITCH OPTIONAL EXTERNAL ENABLE OPT...

Страница 32: ...ed 7 Must be ON low gas switch always used 8 Spare n a 9 Spare n a 10 Spare n a MCB II DETAIL B DIP SWITCH SW2 FUNCTIONS ON IS POS ITION AWAY FR OM BOAR D S E DGE 1 Spare not used 2 High gas switch ON...

Страница 33: ...AL LEGEND 120VAC WIRING LOW VOLTAGE WIRING CAT 5 COMM CABLE AVAILABLE OPTION NOTE1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED REPLACE WITH EQUIVALNET GAUGE WIRE INSULA...

Страница 34: ...essure Close bypass valve and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to permit manual ventin...

Страница 35: ...make further adjustments on the outlet and bypass valves until the desired inlet and outlet water temperatures are reached MANIFOLD PRESSURE CONNECTIONS Take the manifold pressure refer to Table 1 by...

Страница 36: ...36 LIGHTING AND OPERATING INSTRUCTIONS...

Страница 37: ...fully adjust the low fire gas setting to achieve the CO2 level prescribed in above reference table Note The rotation of the Low Fire adjustment is opposite of the High Fire as follows Clockwise rotati...

Страница 38: ...t will operate with the voltage and current level provided Pump MCB 120VAC required on systems that do not have an external pump Provides electrical power to directly operate a pump or the coil of an...

Страница 39: ...idle state as displayed by the Standby LED The control will continue to monitor heat demand and state of other system devices Upon a drop of water temperature below the set parameters the control will...

Страница 40: ...when the fault state is exited Hard Fault State See Fault Description section for list of soft and Auto Reset faults The pump remains on for the selected post circulate time to cycle the hot water ou...

Страница 41: ...soft lockout condition will occur and burner will be shut off This fault condition is automatically cleared when temperature drops below high limit setpoint minus high limit differential AUTO HIGH LI...

Страница 42: ...nwards in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of...

Страница 43: ...the MCB and reading the resistance across the two active pinsontheconnectoratthe end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F L...

Страница 44: ...ction of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be directly...

Страница 45: ...to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber coupling on the blower adaptor in order to move the blower 4 Loosen the seven bolts on the blower adapter at...

Страница 46: ...xist As the water is heated these tend to drop out depositing as scale or lime This scale must be removed before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime r...

Страница 47: ...his boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts...

Страница 48: ...48 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: