www.hotwater.com

For Technical Information and Automated Fax Service, call 800-527-1953. A.O. Smith Corporation reserves the right to make produ ct changes or improvements without prior notice.

MODEL

NUMBER

FIRST

HOUR

RATING

GALLONS

ENERGY

FACTOR

GAL.

CAP.

BTU

INPUT

PER HOUR

RECOVERY

90 ºF RISE

GALLONS

PER HOUR

A

B

C**

D

E

F

VENT

OUTLET*

APPROX.

SHIPPING

WEIGHT

(LBS)

GDV-40

73

.62

40

38,000

41

68

54-3/4 22-1/4

16

12-1/4 45-1/4 Co-Axial

167

GDV-50

87

.60

50

42,000

45

76

63-3/4 22-1/4

16

12-1/4

54

Co-Axial

185

GDVT-50

88

.59

50

50,000

55

76

64-3/4 22-1/4 16-1/4 12-1/2 55-1/2 Co-Axial

187

GDV-75

131

.59

75

55,000

60

76

65-3/4 26-1/4 16-1/4 12-1/2 55-1/2 Co-Axial

310

Recovery capacities based on actual performance tests.
* Dual-channel system has 3˝ vent pipe inside 6˝ air intake pipe, for the 40 & 50–gallon models.

The 75 gallon model uses a 4” x 7” co-axial pipe.

All Models Have 2” Foam Cavity.
Water connection 3/4” male all models. 
75 gallon water connections are 12” on center.
** Allow 25 1/4¨ for 40 and 50–gallon models and 29 1/2¨ for 75–gallon models for
front–to–back dimensions for air intake at the rear of the heater.
GDV–40 Models are ENERGY STAR

®

 qualified.

DIMENSIONS IN INCHES

E

F

B

A

D

FRONT

MAX VENT

80 

C

EXTERIOR

WALL

6   DIA.

MIN VENT

17 

42°

47°

25-1/4

TOP

DRAIN

T&P

Important! Vent Installation and Termination Requirements

Maximum horizontal vent distance is 80” to outside of exterior wall.
Minimum horizontal vent distance is 17” to outside of exterior wall.
Vent pipes may be trimmed (cut) for short vent installations.
For vent installation less than 30” the vent restrictor is required.

Place restrictor over the flue outlet on heater before installing the outlet vent 
pipe to the heater.

Recommended installation height for the heater vent pipe should be

68” for 40 gallon models and 76” for the 50-gallon and 75-gallon 
models (vent height). 

Offset Vent Arrangement

1. When replacing an existing direct vent model, 

the new vent pipe may drop from the minimum 
vent height as much as 7 1/4” to exit through the 
existing vent opening in the exterior wall.

2. Vent may have one horizontal 90 degree turn before 

exiting through exterior wall (Do not combine both 
offset vent arrangements in one installation) (See 
examples in the installation manual)

High Rise Vent Arrangement

3. When vent termination is more than 80” above the 

base of the heater. The horizontal vent run must be 
a minimum of 22” from the center of the heater to 
the outside exterior wall surface. (See example in the 
installation manual)

Vent termination clearance hole through the exterior 

wall should be approximately 7” diameter.

Snow accumulation and drifting should be considered 

when locating the termination.

An optional wire grill vent cap protector is available 

through the parts department. Part number 9006627005.

See the installation manual for complete installation 

and venting requirements.

Residential Gas Water Heaters

DIRECT-VENT

AOSRG45700

Page 2 of 2

July 2011R

40 & 50 gal.

25-1/4

75 gal.

29-1/2

6” DIA. on 40 & 50 Gal. Models

7” DIA. on 75 Gal. Models

75 gal. vent 
termination 
cap is not 
interchangeable
with vent cap
on 40 & 50 gal.
models