* PIPE RELIEF VALVE TO OPEN DRAIN

** 140°F (60°C)TO 150°F (66°C) SHOULD BE MAXIMUM WATER

TEMPERATURE MAINTAINED IN THE PRE-HEATERS.

120°F (49°C) SHOULD BE THE MINIMUM TEMPERATURE OF WATER
IN THE PRE- HEATERS.

CONNECT CIRCULATING LINE FROM FIXTURES, IF USED, TO COLD
WATER SUPPLY LINE OF PRE-HEATER.

CONNECT CIRCULATING LINE OF 180°F (82°C) OR BOOSTED WATER,
IF USED, TO INLET WATER LINE TO BOOSTER.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)

WITH OR WITHOUT BUILDING RECIRCULATION

 

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 24.
IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN
ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES

Содержание PREFERRED BPD 400

Страница 1: ...not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier AOS PREFERRED BPD400 DIRECT VENT COMMERCIAL GAS WATER HEATER GAS FIRED INDUCED DRAFT FOR DOMESTIC HOT...

Страница 2: ...PACITIES NATURALGAS Input Capacity TEMPERATURE RISE DEGREES F GALLONS PER HOUR LPH BTU Gallon 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F Model kw Hr Liters 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BPD 400 390 000 95 1316 987 789 658 564 493 439 395 359 329 304 282 114 3 360 4981 3735 2988 2490 2135 1868 1660 1494 1358 1245 1149 1067 Recovery capacities are ...

Страница 3: ...ODES SHUTOFFVALVE COLD WATER INLET MIXING VALVE TEMPERED WATER OUTLET HOT WATER OUTLET GAS SUPPLY Installation Information for Model BPD 400 100 Series ELECTRICAL CLEARANCES PRESSURES ORIFICES INPUT 120 24VAC 60Hz 5A FRONT SIDES TOP NATURAL NATURAL NATURAL 390kbtuh UNIT IS POLARITY SENSITIVE 6 15 cm 0 12 30 5cm Manifold 4 50 WC Sea Level 0 126 Inlet 7 00 WC 4500 0 126 Max Inlet 14 00 WC 8000 0 106...

Страница 4: ...ended Nonuse Periods 5 Insulation Blankets 5 High Altitude Installations 5 FEATURES 6 The Eliminator 6 High Limit Switch E C O 6 Circulating Pump 6 Dishwashing Machine Requirement 6 Electronic Ignition Control 7 Pilot Assembly 7 Gas Valve 7 Pressure Switch 7 Step Down Transformer 8 Burner Tray Assembly 8 Burner Tray 8 Burner 8 Burner Orifice 8 Blower Assembly 8 High Limit Switch 9 Shroud Assembly ...

Страница 5: ... 1 FAILURE TO REPLACE THE ORIFICES WILLRESULT IN IMPROPERAND INEFFICIENT OPERATION OF THE APPLIANCE RESULTING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESSOFSAFELIMITSWHICHCOULDRESULTINSERIOUSPERSONAL INJURY OR DEATH You should contact your gas supplier for any specific changes which may be required in your area As elevation above sea level is increased there is less oxyge...

Страница 6: ...RE1 HIGH LIMIT SWITCH E C O The dual bulb controller contains the high limit energy cutoff sensor see Figure 2 The high limit switch interrupts main burner gas flow should the water temperature reach 205 F 96 C In the event of high limit switch operation the appliance cannot be restarted unless the water temperature is reduced by at least 20 F 11 C and the high limit reset button on front of limit...

Страница 7: ... deliver water between these limits The National Sanitation Foundation also recommends circulation of 180 F 82 C water Where this is done the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater The circulation should be just enough to provide 180 F 82 C water at the point of takeoff to the dishwashing machine Adjust flow by means of the pl...

Страница 8: ...NER TRAY The burner tray holds the burners in place and is used to slide the entire assembly into the combustion chamber BURNERTRAY BURNER The appliance is equipped with 8 burners mounted in a burner tray assembly The burners are tubular in design with two rows of small slit burner ports The natural gas burners are made of aluminized steel and the LP version is a stainless steel material TUBULAR B...

Страница 9: ...LES ARE STORED OPERATED OR REPAIRED FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER S PILOT OR MAIN BURNER FLAMES CAUSING FIREOREXPLOSION SOMELOCALCODESPERMITOPERATIONOFGAS APPLIANCES IN SUCH AREAS IF THEY ARE INSTALLED 18 OR MORE ABOVE THE FLOOR THIS MAY REDUCE THE RISK IF LOCATION IN SUCH ANAREACANNOT BEAVOIDED DONOTINSTALLTHISWATERHEATERDIRECTLYONACARPETED...

Страница 10: ...g shall have a free area of at least one square inch per 1000 Btuh 2 225mm Kw of the total input of all appliances in the enclosure but not less than 100 square inches 645 square cm If the confined space is within a building of tight construction air for combustion ventilation and draft hood dilution must be obtained from outdoors When directly communicating with the outdoors or communicating with...

Страница 11: ...LVESOROTHERGASREGULATINGEQUIPMENT WARNING FAILURETO HAVE REQUIRED CLEARANCES BETWEEN WATER HEATER AND COMBUSTIBLE MATERIALWILLRESULT IN AFIRE HAZARD FIGURE 7 FACTS TO CONSIDERABOUT THE LOCATION VENTING THROUGH ROOF CLEARANCES 1 2 5 cm clearance for 4 or 6 PVC or CPVC piping from combustible surfaces for outlet piping 0 clearance for 4 or 6 PVC or CPVC piping from combustible surfaces for inlet pip...

Страница 12: ...LVE S SHALL NOT BE LESS THAN THE COMBINED BTU INPUT TO THE WATER HEATER S SUPPLYING WATER TO THE STORAGE VESSEL S THERMOMETERS Not Supplied Thermometers should be obtained and field installed as shown in the installation diagrams Thermometers are installed in the system as a means of detecting the temperature of the water in the appliance TEMPERATURE PRESSURE RELIEF VALVE This water heater is equi...

Страница 13: ...R THAN THE ONE SHOWNABOVE FAILURE TO USE THE CORRECT VOLTAGE CAN CAUSE PROBLEMS WHICH CAN RESULT IN DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE IF YOU HAVE ANY QUESTIONS OR DOUBTS CONSULT YOUR ELECTRIC COMPANY CAUTION IF WIRING FROM THE FUSE BOX OR CIRCUIT BREAKER BOX WAS ALUMINUM FOR THE OLD WATER HEATER REPLACE IT WITH COPPER WIRE IF YOU WISH TO REUSE THE EXISTINGALUMINUM WIRE HAVE THE CONNEC...

Страница 14: ...ith the water heater must be replaced it must be replaced with 105 C thermoplastic AWM wire or its equivalent CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING MINIMUM LINE VOLTAGE WIRE NO 14 AWG ...

Страница 15: ...R REFRIGERANTS SWIMMING POOL CHEMICALS CALCIUM AND SODIUM CHLORIDE WAXES BLEACH AND PROCESS CHEMICALS ARE TYPICAL COMPOUNDS WHICH ARE POTENTIALLY CORROSIVE Horizontal runs must be securely supported at 3 1 2 foot intervals and vertical runs supported at 5 foot intervals VENTING THROUGH AN OUTSIDE WALL Items supplied in the carton 1 One 4 inlet PVC Schedule 40 45 vent cap with screen 2 One 4 outlet...

Страница 16: ...EM EXAMPLE INSTALLATIONS FOR ALL MODELS The vent piping cannot under any circumstances be run downhill THE VENT PIPING CAN BE INSTALLED AS FOLLOWS 1 Horizontal runs require a minimum 1 8 3 mm rise per five feet 2 The total vertical and horizontal run cannot exceed the maximum length with number of 90 elbows as specified in the tables below If more elbows are required the venting distance must be r...

Страница 17: ...it 3 Clean pipe and fitting with a primer cleaner 4 Apply a thin coat of cement to fitting avoiding puddling inside 5 Apply a liberal coat of cement to pipe leaving no voids 6 QUICKLY assemble parts while cement is fluid If you wait too long recoat pipes 7 Push pipe completely into socket of fitting turning as it goes until it bottoms 8 Hold pipe and fitting together for 30 seconds Then carefully ...

Страница 18: ... wall of combustible construction CONNECTING VENT TO BLOWER 4 VENT PIPING 1 If making an immediate horizontal run of vent off the blower the 6 15 cm to 4 galvanized steel reducer and a PVC Schedule 40 street elbow are required for the inlet pipe and the 6 to 4 reducer and two CPVC Schedule 40 or 80 street elbows are required for the outlet vent Place the elbows in the required direction on the red...

Страница 19: ...ule 40 or 80 elbow is then cemented on to the end of the 4 pipe section CPVC Schedule 40 or 80 pipe for the first ten feet is then cemented to the upturned elbow VENTINGTHROUGHAROOF Items supplied in the carton 1 One 4 inlet PVC Schedule 40 45 vent cap with screen 2 One 4 outlet CPVC Schedule 80 45 vent cap with screen 3 Two 6 to 4 galvanized steel reducers 4 Two wire screens to fit one each 6 PVC...

Страница 20: ...of 1 2 pound per square inch 3 5kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5kPa WARNING Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or ...

Страница 21: ...NS FOR MODEL 100 400 BEFORE OPERATINGTHEWATERHEATER 1 Review the installation and instruction manual before turning on the electric power and gas supply to the water heater to safeguard against a possible dangerous malfunction of the water heater 2 The electrical supply to this water heater must NOT be turned on before the tank is completely full of water the gas supply is available and the ventin...

Страница 22: ...the venting manual reset switch and on to theignitionmodule The ignition module will then complete a circuit simultaneously to the spark ignitor and to the gas pilot valve solenoid The spark ignitor will begin sparking and the gas pilot solenoid will open allowing gas to pass to the pilot When a pilot flame has been established the flame sensor in the pilot burner assembly will signal the ignition...

Страница 23: ...ss cover 4 Set the thermostat to lowest setting 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand 6 Turn knob on gas control clockwise to OFF position 7 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you do not smell gas go to the next step 8 ...

Страница 24: ... F 49 C to 180 F 82 C SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE START UP CONDITIONS CONDENSATION Whenever the water heater is filled with cold water a certain amount of condensation will form while the burner is on A water heater may appear to be leaking when in fact the water is condensation This usually happens a When a new...

Страница 25: ...ria is non toxic to humans d an excess of active hydrogen in the tank This is caused by the corrosion protective action of the anode Smelly water may be eliminated or reduced in some water heater models by replacing the anode s with one of less active material and then chlorinating the water heater tank and all hot water lines Contact the local water heater supplier for further information concern...

Страница 26: ...NT SYSTEMS MAY PRESENTSERIOUSHEALTHRISKORASPHYXIATION WARNING CHEMICAL VAPOR CORROSION OF THE FLUE AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SPRAY CAN PROPELLANTS CLEANINGSOLVENTS REFRIGERATORANDAIRCONDITIONER REFRIGERANTS SWIMMING POOL CHEMICALS CALCIUM AND SODIUM CHLORIDE WAXES BLEACH AND PROCESS CHEMICALS ARE TYPICAL COMPOUNDS WHICH ARE POTENTIALLY CORROSI...

Страница 27: ... PRESSURE RELIEF VALVE WITH A NEW ONE WARNING IF THE TEMPERATURE PRESSURE RELIEF VALVE ON THE APPLIANCE WEEPS OR DISCHARGES PERIODICALLY THIS MAY BE DUE TO THERMAL EXPANSION YOUR WATER HEATER MAY HAVE A CHECK VALVE INSTALLED IN THE WATER LINE OR A WATER METER WITH A CHECK VALVE CONSULT THE WATER SUPPLIER AND OR PLUMBING CONTRACTOR FOR FURTHER INFORMATION DO NOT PLUG THE TEMPERATURE PRESSURERELIEFV...

Страница 28: ...OT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES INSTALLATION DIAGRAMS CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN D...

Страница 29: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 24 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMAL EXPANSION OF W...

Страница 30: ...LD KIT SPECIFICATIONS PAGE33 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE24 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER ...

Страница 31: ...ONNECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALL INACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE24 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOO...

Страница 32: ...NTHETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE24 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATERSUPPLIEDTOFIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VAL...

Страница 33: ...ter heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added ...

Страница 34: ...ically for lime scale removal from all types of water using equipment Available in 1 gallon 3 8L part no 4763 and 5 gallon 19L part no 4813 sizes Hydrochloric base acids are not recommended for use on glass lined tanks A O Smith Form No 4800 entitled Why When and How describes tank cleaning methods and materials UN LIME and the booklet may be obtained through your A O Smith dealer or distributor T...

Страница 35: ... to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEANDREPAIREXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are...

Страница 36: ...36 A O SMITH WATER PRODUCTS CO 500 Tennessee Waltz Parkway Ashland City TN 37015 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com email parts hotwater com ...

Отзывы: