INTELLI-VENT TROUBLESHOOTING GUIDE
Technical Training Department
Ashland City, Tennessee © 2005
13 of 24
ERROR CODES - 7, 8, 9 - INTERNAL CONTROL FAILURES
Self diagnostic tests have found a problem with the gas valve driver circuit, internal
microprocessor, or the internal circuits.
Check / Repair:
•
Turn the power off for 10-20 seconds then on again to clear these error codes.
•
If any of these error codes persist or cannot be cleared - replace the Intelli-Vent™
control.
ERROR CODE 10 - FLAME SENSED OUT OF SEQUENCE
Flame signal has been sensed out of proper sequence.
Check / Repair:
•
Insure flame sensor ceramic insulator is not cracked - replace ignitor assembly if
defective.
•
Turn the power off for 10-20 seconds and then on again to clear this error code.
•
Replace the Intelli-Vent™ control if this error code persists.
7
8
9
10