Periodically the temperature and pressure relief valve should be checked
to insure that it is in operating condition.  Lift the lever at the top of the
valve several times until the valve seats properly and operates freely.

RELIEF VALVE

The temperature/pressure (T&P) relief valve is rated at 210°F (99°C) and
150 psi (1034kPa).  This valve is a safety device to protect against
abnormally high temperature and pressures.

Never remove T&P valve from the tank and reinstall in the drain line.  If
replacement of the valve is needed, it must be replaced with the
recommended valve and installed in its original location.

If the temperature/pressure relief valve discharges periodically, this may
be due to thermal expansion in a closed water supply system.  Contact
the water supplier or local plumbing inspector on how to correct this
situation.

A thermal expansion tank may be needed to allow water to expand.
Expansion tanks are available from A.O. Smith Water Products Company,
5621 W. 115th Street, Alsip, IL 60803.  Inspect the unit for proper operation.
Do not ignore the water discharge.  Never plug the T&P relief valve.

 

  DANGER

DANGER OF PERSONAL INJURY FROM SCALDING.  WATER FROM
T&P RELIEF VALVE MAY BE EXTREMELY HOT AND IS NOT
TEMPERED.  USE EXTREME CAUTION WHEN DISCHARGING
VALVE.  REPLACEMENT OF T&P VALVE SHOULD BE DONE BY A
TRAINED PROFESSIONAL OR A LICENSED PLUMBING
CONTRACTOR.

At least once a year, the temperature and pressure relief valve must be
checked to ensure that it is in operating condition. Lift the lever at the top

of the valve several times until the valve seats properly and operates freely.
If water does not flow, valve may be obstructed or corroded.  Remove
valve and inspect for corrosion. Have it replaced with the recommended
valve if necessary.

Removal and inspection of the valve should be done every three years.
Do not try to repair valve.  Doing so will result in improper operation which
may result in a tank explosion.  In areas with poor water conditions, it may
be necessary to remove and inspect the T&P valve more often than every
three years.

ANODE ROD MAINTENANCE

The anode rod is used to protect the tank from corrosion. Water tanks are
equipped with an anode rod.  The submerged rod sacrifices itself to protect
the tank.  Instead of corroding the tank, water ions attack and eat away
the anode rod.  This does not affect the water's taste or color.  The rod
must be maintained to keep the tank in operating condition.  Failure to
inspect and/or replace the anode rod will result in voiding the warranty.

Anode deterioration depends on water conductivity, not necessarily water
condition.  It may be necessary to have the anode rod inspected a few
times during the first year to see what effect the water has had.  A corroded
or pitted anode rod, in the first year, indicates high water conductivity and
should be checked and or replaced more often than an anode rod that
appears to be fairly clean.  Inspection should be conducted by a qualified
technician.

REPLACEMENT PARTS

Replacement parts may be ordered through dealers, authorized servicers
or distributors.  Refer to Yellow Pages for where to call or contact the
Water Products Company, 5621 West 115th Street, Alsip, IL 60803,
1-800-433-2545.  When ordering parts, specify complete model no., serial
no., (see rating plate), quantity and name of part desired.  Standard
hardware items should be purchased locally.

TROUBLE SHOOTING ELECTRIC WATER HEATERS

CAUSE

IMPROPERLY SEALED HOT OR COLD
SUPPLY CONNECTIONS, RELIEF VALVE
OR THERMOSTAT THREADS

LEAKAGE FROM OTHER APPLIANCES

OR WATER LINES

THERMAL EXPANSION IN CLOSED
WATER SYSTEM

IMPROPERLY SEATED VALVE

HIGH SULFATE OR MINERAL CONTENT
IN WATER SUPPLY

BACTERIA IN WATER SUPPLY

POWER SUPPLY TO HEATER IS NOT
ON

THERMOSTAT SET TOO LOW

HEATER UNDERSIZED

INCOMING WATER IS UNUSUALLY
COLD (WINTER)

LEAKING HOT WATER FROM PIPES OR
FIXTURES

HIGH TEMPERATURE LIMIT SWITCH
ACTIVATED

THERMOSTAT SET TOO HIGH

HIGH TEMPERATURE LIMIT SWITCH
ACTIVATED

SCALE ACCUMULATION ON ELEMENTS

SEDIMENT BUILD-UP ON TANK
BOTTOM

SOLUTION

TIGHTEN THREADED CONNECTIONS

INSPECT OTHER APPLIANCES NEAR WATER
HEATER

INSTALL THERMAL EXPANSION TANK (DO NOT
PLUG T & P RELIEF VALVE)

CHECK RELIEF VALVE FOR PROPER OPERATION

DRAIN AND FLUSH HEATER THOROUGHLY, AND
REFILL

CHLORINATE WATER SUPPLY

TURN DISCONNECT SWITCH ON OR CONTACT
ELECTRICIAN

REFER TO TEMPERATURE REGULATION

REDUCE HOT WATER USE

ALLOW MORE TIME FOR HEATER TO REHEAT

HAVE PLUMBER CHECK AND REPAIR LEAKS

CONTACT DEALER TO DETERMINE CAUSE:  SEE
TEMPERATURE REGULATION

REFER TO TEMPERATURE REGULATION

CONTACT DEALER TO DETERMINE CAUSE:  SEE
TEMPERATURE REGULATION

CONTACT DEALER TO CLEAN OR REPLACE
ELEMENTS

DRAIN & FLUSH THOROUGHLY

PROBLEM

WATER LEAKS (SEE LEAKAGE CHECKPOINTS
ON PAGE 7

LEAKING TEMPERATURE & PRESSURE RELIEF
VALVE

HOT WATER ODORS (CAUTION:
UNAUTHORIZED REMOVAL OF THE ANODE(S)
WILL VOID THE WARRANTY. FOR FURTHER
INFORMATION, CONTACT YOUR DEALER.)

NOT ENOUGH OR NO HOT WATER

WATER TOO HOT

WATER HEATER SOUNDS

Содержание ELECTRIC WATER HEATER

Страница 1: ...nstructions can result in fire asphyxiation serious personal injury or death Do not cover the temperature pressure relief T P valve Do not cover the instruction manual Keep it on the side of the water heater or nearby for future reference Do obtain new warning and instruction labels from A O Smith for placement on the blanket directly over the existing labels EXTENDED NON USE PERIODS WARNING Hydro...

Страница 2: ...2 UPRIGHTS LOWBOYS COMPACTS TABLE TOPS FIGURE 1 GET TO KNOW YOUR WATER HEATER INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES ...

Страница 3: ...ge 2 for typical installation Make sure a suitable pipe thread sealant is used to prevent leakage TEMPERATURE AND PRESSURE RELIEF VALVE A NEW TEMPERATURE AND PRESSURE RELIEF VALVE COMPLYING WITH THE STANDARD FOR RELIEF VALVES FOR HOT WATER SUPPLY SYSTEMS ANSI Z21 22 MUST BE INSTALLED IN THE HEATER IN THE MARKED OPENING PROVIDED THE VALVE MUST BE OF A SIZE INPUT RATING THAT WILL BE ADEQUATE FOR YOU...

Страница 4: ...4 WIRING DIAGRAMS DANGER TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS FIGURE 2 ...

Страница 5: ... degrees of angular rotation and the corresponding change in temperature Thus rotating the temperature adjustment indicator 30 angular degrees will result in a 10 degree Fahrenheit change in water temperature TEMPERATURE ADJUSTMENT To change the temperature setting DANGER 1 Turn off the heater electrical supply Do not attempt to adjust thermostat with power on 2 Remove the thermostat access panels...

Страница 6: ...od must be maintained to keep the tank in operating condition Failure to inspect and or replace the anode rod will result in voiding the warranty Anode deterioration depends on water conductivity not necessarily water condition It may be necessary to have the anode rod inspected a few times during the first year to see what effect the water has had A corroded or pitted anode rod in the first year ...

Страница 7: ...ation due to the panel or in sulation not being in place Drain valve leakage could be from the valve itself Either correct the problem or replace the valve To check for leakage where threaded portion enters tank insert Q tip or similar absorbent material between jacket opening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Contact your dealer as i...

Страница 8: ... or any part thereof including freezing fire floods or lightning any misuse abuse or alteration of it any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS Such cost...

Отзывы: