14
MANIFOLD KITS
ALL DIMENSIONS IN INCHES.
TWO HEATERS
Part
Model
Number
H
W
D
A
DRE/DVE-52
9003429
66 1/4
56 3/4
27 1/4 13 1/4
DRE/DVE-80
9003429
70 1/2
60 1/4
31 1/4
9 3/4
DRE/DVE-120
9003429
73 1/4
64 1/2
35 3/4
5 1/2
Inlet and outlet size — 1 1/2
THREE HEATERS
Part
Model
Number
H
W
D
A
DRE/DVE-52
9003430
66 1/4
91 3/4
27 1/4 13 1/4
DRE/DVE-80
9003430
70 1/2
95 1/4
31 1/4
9 3/4
DRE/DVE-120
9003430
73 1/4
99 1/2
35 3/4
5 1/2
Inlet and outlet size —2 1/2
FOUR HEATERS
Part
Model
Number
H
W
D
A
DRE/DVE-52
9003431
66 1/4 126 3/4
27 1/4 13 1/4
DRE/DVE-80
9003431
70 1/2 130 1/4
31 1/4
9 3/4
DRE/DVE-120
9003431
73 1/4 134 1/2
35 3/4
5 1/2
Inlet and outlet size —2 1/2
Electrical
GENERAL
The installation must conform to these instructions, the local code
authority having jurisdiction, and the requirements of the power
company. In the absence of codes requirements follow the current
version of NFPA-70. The National Electrical Code which may
be ordered from National Fire Protection Association, 1
Batterymarch Park, Quincy, MA 02269.
WARNING
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK
OF ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION.
The
water heater should be connected to a separate grounded branch
circuit with overcurrent protection and disconnect switch. The
water heater should be grounded in accordance with national and
local codes.
Check the heater model and rating plate information against the
characteristics of the branch circuit electrical supply.
DO NOT
CONNECT THE HEATER TO AN IMPROPER SOURCE OF
ELECTRICITY.
Contact the heater supplier for conversion
information if necessary.
Voltage applied to the heater should not vary more than +5% to -
10% of the model and rating plate marking for satisfactory
operation.
DO NOT ENERGIZE THE BRANCH CIRCUIT FOR ANY REASON
BEFORE THE HEATER TANK IS FILLED WITH WATER. DOING
SO WILL CAUSE THE HEATING ELEMENTS TO BURN OUT.
The branch circuit is connected to the heater wiring through an
opening provided on the heater.