background image

13

HOT WATER

OUTLET

TO TANK

INLET

CHECK

VALVE

MIXING

VALVE

COLD

WATER

INLET

TEMPERED WATER

OUTLET

12” TO 15”

(30-38 cm)

CHECK

VALVE

figure 10

dishwashing machines

All  dishwashing  machines  meeting  the  national  Sanitation 

Foundation  requirements  are  designed  to  operate  with  water 

flow pressures between 15 and 25 pounds per square inch (103 

kPa and 173 kPa). Flow pressures above 25 pounds per square 

inch (173 kPa), or below 15 pounds per square inch (103 kPa), 

will result in improperly sanitized dishes. Where pressures are 

high, a water pressure reducing or flow regulating control valve 

should  be  used  in  the  180°F  (82°C)  line  to  the  dishwashing 

machine  and  should  be  adjusted  to  deliver  water  pressure 

between these limits.
The national Sanitation Foundation also recommends circulation 

of 180°F (82°C) water. Where this is done, the circulation should 

be  very  gentle  so  that  it  does  not  cause  any  unnecessary 

turbulence inside the water heater. The circulation should be just 

enough to provide 180°F (82°C) water at the point of take-off to 

the dishwashing machine.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 

circulating line on the outlet side of the pump. never throttle flow 

on the suction side of a pump. See Water Piping Diagrams in 

this manual.

closed water systems

Water  supply  systems  may,  because  of  code  requirements 

or  such  conditions  as  high  line  pressure,  among  others,  have 

installed  devices  such  as  pressure  reducing  valves,  check 

valves, and back flow preventers. Devices such as these cause 

the water system to be a closed system.

thermal expansion

As water is heated, it expands (thermal expansion). In a closed 

system the volume of water will grow when it is heated. As the 

volume  of  water  grows  there  will  be  a  corresponding  increase 

in water pressure due to thermal expansion. Thermal expansion 

can cause premature tank failure (leakage). This type of failure 

is  not  covered  under  the  limited  warranty.  Thermal  expansion 

can also cause intermittent Temperature-Pressure relief Valve 

operation:  water  discharged  from  the  valve  due  to  excessive 

pressure build up. This condition is not covered under the limited 

warranty. The Temperature-Pressure relief Valve is not intended 

for the constant relief of thermal expansion.

A  properly  sized  thermal  expansion  tank  must  be  installed  on 

all  closed  systems  to  control  the  harmful  effects  of  thermal 

expansion. Contact a local plumbing service agency to have a 

thermal expansion tank installed.
See Water Line Connections on page 19 and the Water Piping 

Diagrams beginning on page 34.

temperature-pressure relief ValVe

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

This  water  heater  is  provided  with  a  properly  rated/sized  and 

certified  combination  Temperature-Pressure  relief  Valve  (T&P 

valve) by the manufacturer. The valve is certified by a nationally 

recognized testing laboratory that maintains periodic inspection 

of  production  of  listed  equipment  of  materials  as  meeting  the 

requirements  for  relief  Valves  for  hot  Water  Supply  Systems, 

AnSI Z21.22 • CSA 4.4, and the code requirements of ASme.
If  replaced,  the  new  T&P  valve  must  meet  the  requirements 

of  local  codes,  but  not  less  than  a  combination  Temperature-

Pressure  relief  Valve  rated/sized  and  certified  as  indicated  in 

the  above  paragraph.  The  new  valve  must  be  marked  with  a 

maximum  set  pressure  not  to  exceed  the  marked  hydrostatic 

working pressure of the water heater (150 psi = 1,035 kPa) and 

a discharge capacity not less than the water heater Btu/hr or kW 

input rate as shown on the water heater’s model rating label.
nOTe: In addition to the factory installed Temperature-Pressure 

relief Valve on the water heater, each remote storage tank that 

may be installed and piped to a water heating appliance must also 

have its own properly sized, rated and approved Temperature-

Pressure  relief  Valve  installed.  Call  the  toll  free  technical 

support phone number listed on the back cover of this manual 

for technical assistance in sizing a Temperature-Pressure relief 

Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure 

relief Valve must not be removed from its designated opening 

nor  plugged.  The  Temperature-Pressure  relief  Valve  must  be 

installed directly into the fitting of the water heater designed for the 

relief valve. Install discharge piping so that any discharge will exit 

the pipe within 6 inches (15.2 cm) above an adequate floor drain, 

or external to the building. In cold climates it is recommended 

that it be terminated at an adequate drain inside the building. Be 

certain that no contact is made with any live electrical part. The 

discharge opening must not be blocked or reduced in size under 

any circumstances. excessive length, over 30 feet (9.14 m), or 

use of more than four elbows can cause restriction and reduce 

the discharge capacity of the valve.

Содержание BTR 500

Страница 1: ...ES 120 121 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance ...

Страница 2: ...g Diagrams 34 Manifold Kits 49 Limited Warranty 50 notes 51 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Information 4 Precautions 5 Grounding Instructions 5 Hydrogen Gas Flammable 5 Introduction 6 Abbreviations Used 6 Qualifications 6 features and components 7 The Eliminator self cleaning system 7 High Limit Switch 7 Electronic Ignition Control 7 Exhaust Induce...

Страница 3: ...cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances listed in the Act DANGER WARNING CAUTION CAUTION DANGER indicates an imminently ...

Страница 4: ...iment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service agency for installation and service Excessive gas pressure to gas valve can cause serious injury or death Do not use water heater with any gas other than the gas shown on the rating label Turn o...

Страница 5: ...system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the time it is open General Safety Information Verify the power to the water heater is turned off before performing any service procedures Read and understand this instruction manual and the safety messag...

Страница 6: ...gas supply and electrical supply are required in addition to electrical testing skills when performing service ANSI Z223 1 2006 Sec 3 3 83 Qualified Agency Any individual firm corporation or company that either in person or through a representative is engaged in and is responsible for a the installation testing or replacement of gas piping or b the connection installation testing repair or servici...

Страница 7: ...d manual resetting of high limit control preceded by higher than usual water temperature is evidence of high limit switch operation The following is a possible reason for high limit switch operation A malfunction in the thermostatic controls would allow the gas valve to remain open causing water temperature to exceed the thermostat setting The water temperature would continue to rise until high li...

Страница 8: ...0 1 50 1 50 1 50 1 50 812 857 BTR500 147 322 207 44 196 171 69 53 3 171 20 70 1 50 1 50 1 50 1 50 1 50 1 50 368 389 Model Input Rate Btu Hr Kw Hr Approximate Tank Cap G L Recovery Rating Capacities GPH and LPH at temperature rise indicated 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BTR 500 500 000 85 1616 1212 970 80...

Страница 9: ...E 5 MINIMUMCLEARANCESTONONCOMBUSTIBLECONSTRUCTION MODEL A RIGHT SIDE B LEFT SIDE C BACK D CEILING BTR 500 0 0 0 12 30 5 cm Locating the Water Heater Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION When installing the heater consideration must be given to proper location Location selected should be as close to the stack or chimney as practic...

Страница 10: ... flow to the burners DO NOT allow insulation to come within 9 inches 23 cm of floor within 2 inches 5 cm of bottom cover to prevent blockage of combustion air flow to the burners DO NOT cover the instruction manual Keep it on the side of the water heater or nearby for future reference DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the ...

Страница 11: ... Call the local gas or utility company to verify Btu per cubic foot content before calling for technical assistance and have that information available Note The actual firing rate of the water heater must not exceed the input rating on the water heater s rating label under any circumstances Note Due to the input rating reduction at high altitudes the output rating of the appliance is also reduced ...

Страница 12: ...60 C Less than 5 seconds 130 F 54 C About 30 seconds 120 F 49 C More than 5 minutes Gas Pressure Requirements Natural gas models require a minimum gas supply pressure of 4 5 W C Propane gas models require a minimum gas supply pressure of 11 W C The minimum supply pressure is measured while gas is not flowing static pressure AND while gas is flowing dynamic pressure The supply pressure static and d...

Страница 13: ...mal expansion tank installed See Water Line Connections on page 19 and the Water Piping Diagrams beginning on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized temperature pressure relief valve must be installed in opening provided Can result in overheating and excessive tank pressure Can c...

Страница 14: ...tems and Thermal Expansion on page 13 If you do not understand these instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance Contaminated Air Breathing Hazard Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN CSA B149 1 To avoid i...

Страница 15: ... Construction In unconfined spaces in buildings infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases However in buildings of unusually tight construction for example weather stripping heavily insulated caulked vapor barrier etc additional air must be provided using the methods described in the Confined Space section that follows Confined Space A Confine...

Страница 16: ...0 square inches 645 cm2 Outdoor Air Through One Opening Figure 15 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 15 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches l50 mm from the front of the appliance The opening shall directly communicate with the outdoors o...

Страница 17: ...e aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Venting Installa...

Страница 18: ... 8 8 7 500 000 2 Ft 10 10 10 9 9 8 8 7 500 000 3 Ft 10 10 9 9 9 8 7 7 Multiple Fan Assisted Water Heaters Total Vent Height Feet Number of 500 Heaters Combined Input btu hr 6 8 10 15 20 30 50 100 Manifold and Common Vent Diameter Inches 2 1 000 000 14 14 12 12 10 10 9 8 3 1 500 000 16 16 14 14 14 12 12 10 4 2 000 000 18 18 16 16 14 14 12 12 Combination of Multiple Fan Assisted and Natural Draft Wa...

Страница 19: ...ation diagrams on pages 34 48 are typical The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject to freezing temperatures Install in accordance with all local codes Water Line Connections This manual provides detailed installation diagrams see pages 34 48 of this manual for typical methods of application for the water heater s Wa...

Страница 20: ...allations in the state of North Carolina due to the material of the tube Polypropylene Where such code restrictions exist use only lower inlet tank connection This may also require a heat trap check local codes The Top Outlet connection may still be used on these applications Plug or cap all unused openings in the tank before filling with water TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPER...

Страница 21: ...ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only type 105 C thermoplastic or equivalent and 2500 C type F must be used for the flame sensor and igniter leads The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neutral connection...

Страница 22: ...VERSION OF THE NATIONAL FUEL GAS CODE To prevent damage care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet Apply joint compounds pipe dope sparingly and only to the male threadsofpipejoints Donotapplycompoundstothefirsttwothreads Use compounds resistant to the action of liquefied petroleum gases BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEA...

Страница 23: ... and avoid unnecessary service calls However the user should not attempt repairs which are not listed under the USER column General NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS CONTROL ...

Страница 24: ...rt of the control system and any gas control which has been under water Do not touch any electric switch do not use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas suppliers instructions FOR YOUR SAFETY READ BEFORE OPERATING STOP Read the safety information above on this label Set thermostat to lowest setting 5 1 3 3 4 Turn off all elect...

Страница 25: ...by the normal method or if a suitable draft cannot be obtained a blower type flue gas exhauster must be employed to assure proper venting and correct combustion Check the Igniter Assembly At least once a year check the igniter assembly Figure 23 and the main burner Figure 24 for proper operation Refer to the following igniter assembly and main burner sections Igniter Assembly For access to igniter...

Страница 26: ...ng BTR 500 heater T 7 56 seconds H 1050 Btu Btuh 3600 7 56 X 1050 500 000 Btuh Compare with the BTR 500 model and rating Should it be necessary to adjust the gas pressure to the burners to obtain the full input rate the steps below should be followed 3 Remove the regulator adjustment sealing cap fig 25 and adjust the pressure by turning the adjusting screw with a screwdriver Clockwise to increase ...

Страница 27: ...ting properly Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temperature Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG TH...

Страница 28: ...ater Do not smoke or have open flame or sparks in vicinity of heater Do not mix UN LIME with other chemicals Do not allow contact with magnesium aluminum or galvanized metals RecommendedProcedureforPeriodicRemoval of Lime Deposits from Tank Type Commercial Water Heaters The amount of calcium carbonate lime released from water is in direct proportion to water temperature and usage see chart The hig...

Страница 29: ...tion for contact with eyes Keep out of reach of children NOTE THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT 1 Turn off fuel and or power supply to heater Also turn off power to any electrical device or equipment which is attached or part of the system 2 Open hot water side of faucet closest to heater ...

Страница 30: ...EL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING Start Up Conditions SMOKE ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start up This is due to burning off of oil from metal parts and will disappear in a short while STRANGE SOUNDS Possible noises ...

Страница 31: ...ox Turn on the water heater If this fails to correct the problem contact your plumber or service representative further information regarding anode replacement and this chlorination treatment If the smelly water persists after the anode replacement and chlorination treatment we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem Do not re...

Страница 32: ...32 Sequence of Operation Flow Chart Description of this flow chart can be found in the SEQUENCE OF OPERATION section found on page 23 FIGURE 29 ...

Страница 33: ...outside of tank normal Rumbling Sediment accumulation on bottom of tank Drain a quantity of water through drain valve If rumbling persists call a service agent Delime heater Ticking or metallic sounds Expansion and contraction normal Pounding Air chambers in piping have become waterlogged Drain piping system and refill Heater must be off while this is being done Combustion noises Too much primary ...

Страница 34: ... s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WIT...

Страница 35: ...mostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES A...

Страница 36: ...s and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TE...

Страница 37: ...ump between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WA...

Страница 38: ...stat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Страница 39: ...stat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Страница 40: ...at should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Страница 41: ...TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS BOOSTER WATER RETURN PRE HEATED WATER TO BOOSTER BOOSTER WATER TO FIXTURES HOT WATER T...

Страница 42: ...F VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS EXPANSION TANK BOOSTED WATER OUTLET TYPICAL BOOSTER HEATER PRE HEATER PRE HEATER MUST BE IDENTICAL HEATERS FINISHED FLOOR COLD WATER S...

Страница 43: ... LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER TO FIXTURES HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK PIPE T...

Страница 44: ... than the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENT...

Страница 45: ...er than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIRE...

Страница 46: ...URE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS EXPANSION TANK COLD WATER SUPPLY HOT WATER TO FIXTURES FINISHED FLOOR HOT WATER RETURN PIPE T ...

Страница 47: ...Temperature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER TO ...

Страница 48: ...k Temperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER...

Страница 49: ...49 Manifold Kits MANIFOLD KITS TWO UNIT MANIFOLD KIT PART NO 9003426205 THREE UNIT MANIFOLD KIT PART NO 9003427205 FOUR UNIT MANIFOLD KIT PART NO 9003428205 MODEL DIMENSION A BTR 500 81 5 ...

Страница 50: ...50 Limited Warranty ...

Страница 51: ...notes ...

Страница 52: ...500 Tennessee Waltz Pkwy Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2010 A O Smith Corporation All rights reserved ...

Отзывы: