25
Servicing should only be performed by a Qualified Service Technician
TEST 4
–
UPPER TEMPERATURE PROBE CONTINUITY CHECK
OHMS RESISTANCE TABLE
° F
OHMS
70°
11,884
120°
3,759
140°
2,488
180°
1,169
TEST 4
Upper Temperature Probe continuity check.
Red wire to red wire – Turn supply power "Off" for this test.
IF.........
THEN............
Test indicates
no continuity
.
Replace probe.
Continuity
is indicated.
Probe should be okay (also verify Ohms resistance for water
temperature). (Reading will be approximate.)
CONDITIONS:
• Power On – Water below temperature set point.
• Red, water heater control “Reset Status” LED – OFF.
• "Call for Heat" LED Off.