8

TABLE 3

EQUIVALENT LENGTH OF FITTINGS IN FEET

Pipe Size (IPS)

1

1.25 1.5

2

2.5

3

4

Std. Tee through side 5.5

7.5

9.0 12.0 14.0 17.0 22.0

Std. E11

2.7

3.7

4.3 5.5

6.5

8.0 12.0

45°F E11

1.2

1.6

2.0 2.5

3.0

3.7 5.0

Plug Cock

3.0

4.0

5.5 7.5

9.0 12.0 16.0

 WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 13.8” WATER COLUMN (1/2 POUND PER SQUARE INCH)
SUPPLY GAS PRESSURE.  HIGHER GAS PRESSURE
REQUIRES SUPPLEMENTAL REDUCING SERVICE
REGULATION. EXPOSURE TO HIGHER GAS SUPPLY
PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS
WHICH COULD RESULT IN FIRE OR EXPLOSION.  IF
OVERPRESSURE HAS OCCURRED SUCH AS THROUGH
IMPROPER TESTING OF GAS LINES OR EMERGENCY
MALFUNCTION OF THE SUPPLY SYSTEM,  THE GAS VALVE
MUST BE CHECKED FOR SAFE OPERATION.  MAKE SURE
THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS
AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST
BLOCKAGE.  THESE ARE PARTS OF THE GAS SUPPLY
SYSTEM, NOT THE HEATER.  VENT BLOCKAGE MAY OCCUR
DURING ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS
PIPE IS CLEANED ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT
TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE
PIPING.  THE DIRT LEG MUST BE READILY ACCESSIBLE AND
NOT SUBJECT TO FREEZING CONDITIONS

. INSTALL IN

ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS
SUPPLIERS.  REFER TO THE 

NATIONAL FUEL GAS CODE.

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipes to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints.  Do not apply compound to the first two
threads.  Use compounds resistant to the action of liquefied
petroleum gases.

DISCONNECT THE APPLIANCE AND ITS MANUAL GAS
SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM
DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2
PSIG.

  GAS SUPPLY LINE MUST BE CAPPED WHEN

DISCONNECTED FROM THE HEATER.  FOR TEST
PRESSURES OF 1/2 PSIG OR LESS, THE APPLIANCE NEED
NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM
THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL
GAS SHUTOFF VALVE.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE. 

 USE SOAP AND WATER SOLUTION OR

OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF
LOCATING GAS LEAKS.  

DO NOT USE MATCHES, CANDLES,

FLAME OR OTHER SOURCES OF IGNITION FOR THIS
PURPOSE.

PURGING

Gas line purging is required with new piping or systems in which
air has entered.

 

 CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS
EXPERIENCED IN THIS TYPE GAS SERVICE.  TO AVOID RISK
OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT
ENTER CONFINED AREAS OR SPACES WHERE IGNITION
CAN OCCUR.  THE AREA MUST BE WELL VENTILATED AND
ALL SOURCES OF IGNITION MUST BE INACTIVATED OR
REMOVED.

GAS METER SIZE – CITY GASES ONLY

Be sure that the gas meter has sufficient capacity to supply the
full rated gas input of the water heater as well as the requirements
of all other gas fired equipment supplied by the meter.  If gas
meter is too small, request the gas company to install a meter
having adequate capacity.

GAS PRESSURE REGULATOR

DO NOT SUBJECT COMBINATION GAS VALVE TO INLET GAS
PRESSURE OF MORE THAN 14 I.W.C. A SERVICE
REGULATOR IS NECESSARY IF HIGH GAS PRESSURES ARE
ENCOUNTERED.

The gas pressure regulator vent line must be vented to the
outside of the building.

POWER BURNER

For information relating to the power burner supplied with this
water heater, refer to the power burner manual provided.

LIFTING LUGS

This water heater is supplied with lifting lugs.  Prior to lifting, insure
that the lugs are threaded into their receptacles as tight as
possible.

These lugs may be removed after installation.  Sheet metal covers
are provided to cover the receptacle openings.

WIRING

The rating plate provides the electrical information needed to size
the water heater branch supply circuit.

Typical water heater electrical diagrams are provided in this
manual (pages 9 and 10). The actual diagram, corresponding to
each water heater, is provided with each water heater, and may
differ from the diagrams shown in this manual.

The BTP unit burner is wired to the water heater control
compartment as shown in the following diagram. The electrical
service should be connected to the N & L Terminals located in
the control compartment. Ground from control compartment to
suitable ground.

All electrical work must be installed in accordance with the National
Electrical Code (latest version) and local requirements.  

AN

ELECTRICAL GROUND IS REQUIRED TO REDUCE THE RISK

Содержание BTP-140-140

Страница 1: ...tilate the room then call your gas supplier or service agent Keep area clear until a service agent has been called MODELS BTP 140 140 thru 600 2500 INCLUDING BTPD BTPN COF COBT COMMERCIAL GAS OIL AND...

Страница 2: ...s Association Labortories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 TABLE OF CONTENTS This manual is supplemented by the power burner manual All information including start up and maintenance...

Страница 3: ...OW OF COMBUSTION AND VENTILATING AIR ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas LPG ar...

Страница 4: ...rsion from American Insurance Association 85 John Street New York NY 11038 Note Some gas utility companies derate the heating value of the supplied gas at high elevations Your authorized A O Smith Sta...

Страница 5: ...T 18 Inches FRONT 18 Inches BACK 0 Inches Back 6 Inches TOP 5 Inches Top 12 Inches LEFT SIDE 0 Inches LEFT SIDE 6 Inches RIGHT SIDE 0 Inches RIGHT SIDE 6 Inches NOTE If a chimney connector is used the...

Страница 6: ...RECIRCULATION OF FLUE GASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts during shutdown periods Remove all soot or other obstruct...

Страница 7: ...LOCATED IN FREEZING AREAS DO NOT THREAD OR CAP THE END OF THIS LINE RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE DISCHARGE LINE SHALL BE INSTALLED TOALLOW COMPLET...

Страница 8: ...OM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOS...

Страница 9: ...9 TYPICAL WIRE DIAGRAM BTP 270 2 500 KBTUH COF 800 2 500 KBTUH COBT 400 2 500 KBTUH TYPICAL WIRE DIAGRAM BTP 140 255 KBTUH...

Страница 10: ...10 TYPICAL WIRE DIAGRAM COF 140 720 KBTUH TYPICAL WIRE DIAGRAM COBT 140 300 KBTUH...

Страница 11: ...te to ask the agent any questions which you may have regarding the units start up operation or maintenance A MAINTENANCE section is included at the rear of this manual Any service required should be p...

Страница 12: ...finished flushing 4 Turn on the heater electrical disconnect switch MAINTENANCE SCHEDULE Component Operation Interval Required Flushing Monthly Sediment Tank Removal Semi Annually Lime Scale UN LIME...

Страница 13: ...ined through your A O Smith dealer or distributor To clean heater through cleanout opening proceed as follows 1 Turn off water inlet valve the heater electrical disconnect switch and open drain valve...

Страница 14: ...FIGURE 3 To test gate for operation gently tap gate and observe DO NOT OIL The red solid fuel tabs supplied with the draft regulator must be removed See instructions supplied with Draft Regulator TROU...

Страница 15: ...et system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the water heater or plumbing system will be damaged When such...

Страница 16: ...ENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a...

Отзывы: