Instruction Manual

PRINTED IN THE U.S.A  0905

   PART NO. 185363-001

KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE

WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.

POWER VENTED GAS MODELS W/HOT SURFACE IGNITION

NOT FOR USE IN MANUFACTURED (MOBILE) HOMES

ALL TECHNICAL AND WARRANTY QUESTIONS:

 SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.

 

RESIDENTIAL GAS WATER HEATERS

• 

For Your Safety

 •

AN ODORANT IS ADDED TO THE GAS USED

BY THIS WATER HEATER.

C3 Technology® Gas Water Heaters meet the new
ANSI Z21.10.1 standard that deals with the accidental or
unintended ignition of flammable vapors, such as those
emitted by gasoline.

GAMA certification applies to
all residential gas water
heaters with capacities of 20
to 100 gallons with input rating
of 75,000 BTU/Hr. or less.

A DIVISION OF A. O. SMITH CORPORATION

Ashland City, TN 37015

w w w.hotwater.com

Содержание 185363-001

Страница 1: ...AREUNSUCCESSFUL PLEASEWRITETOTHECOMPANYLISTEDONTHERATINGPLATEONTHEWATERHEATER RESIDENTIAL GAS WATER HEATERS For Your Safety ANODORANTISADDEDTOTHEGASUSED BYTHISWATERHEATER C3 Technology Gas Water Heate...

Страница 2: ...it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features and use of flammable vapor ignition resistant water heaters and have a...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...rules the water heater will not operate properly It could cause DEATH SERIOUSBODILYINJURYAND ORPROPERTYDAMAGE This manual contains instructions for the installation operation and maintenance of the ga...

Страница 5: ...lve U Ground Joint Union V Drip Leg Sediment Trap W Drain Valve X Gas Valve Thermostat Y Drain Pan Z Air Intake Screen Base Pan AA Inner Door BB Outer Door CC HSI Burner Assembly DD Air Intake Screen...

Страница 6: ...an others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law...

Страница 7: ...or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan W...

Страница 8: ...or exceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insu...

Страница 9: ...e inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 7 FIGURE7 2 When communicating with the outdoors through vertical ducts each opening shall h...

Страница 10: ...capped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take speci...

Страница 11: ...e installed directly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm abov...

Страница 12: ...a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 7 700 feet 2 347 meters input rating should be reduced at the rate of 4 percen...

Страница 13: ...eatercomeswiththeblowerassemblyinstalled 2 After the unit is set in place make sure the blower assembly is still mounted securely and the air intake screen of the blower assembly is installed in the d...

Страница 14: ...ater heater to an existing vent or chimney It must be vented separately from all other appliances Nonmetallic vent may be used if it has Heat Deflection Temperature HDT 66 psi or 455 kPa of at least 1...

Страница 15: ...F 79 C some installations will have water condensate in the vent piping If this occurs then adequate means of draining and disposing of the condensate needs to be made by the installer CONDENSATE Cond...

Страница 16: ...re 16 3 The venting system shall terminate at least 4 feet 1 2 m below 4 feet 1 2 m horizontally from or 1 foot 0 31 m above any door window or gravity air inlet into any building The manufacturer als...

Страница 17: ...is supplied for decorative purposes only and is not a requirement for the vent termination if not needed by the installer VERTICAL VENT THROUGH ROOF This unit is approved for venting through the roof...

Страница 18: ...cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cle...

Страница 19: ...ance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristlebrush Thisprocesssoftensan...

Страница 20: ...d HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off...

Страница 21: ...ater Mixing valves are available at plumbing supply or hardware stores see Figure 2 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermos...

Страница 22: ...sion tanks are available for ordering through a local plumbing contractor Contact the local water heater supplier or service agency for assistance in controlling these situations STRANGESOUNDS Possibl...

Страница 23: ...hrough the ViewportontheInnerDoor seeFigure1 Themainburnershouldprovide completecombustionofgas igniterapidly givereasonablyquietoperation and cause no excessive flame lifting from the burner ports If...

Страница 24: ...to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature pressure relief valve with a...

Страница 25: ...f the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on...

Страница 26: ...sor 26 FV Sensor Bracket 27 Nipple with Heat Trap 28 Secondary Anode with Heat Trap Not Shown Optional Now that you have purchased this water heater should a need ever exist for repair parts or servic...

Страница 27: ...r not positioned correctly 3 Low voltage to the water heater 4 Electric polarity to unit is incorrect test and correct Problem in the gas valve driver circuit 1 Turn power to the water heater off for...

Страница 28: ...ines should be utilized by a qualified service agent When calling for service notify the service agent that this is a Flammable Vapor Ignition Resistant Product TROUBLESHOOTING GUIDELINES TROUBLESHOOT...

Страница 29: ...29 NOTES...

Страница 30: ...30 NOTES...

Страница 31: ...suse abuse or alteration of it any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDERTHISLIMITEDWARRANTY THE...

Страница 32: ...32 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com...