User manual ABE_300
Biogas Chiller ABE_300
24
4.8
Configuration PID temperature
From the main screen by pressing F3 you access the password page,
introduce the password (123456) and press F4, the following screen appears.
SCREEN PID TEMPERATURE
• Reference: value of temperature that you want to have on the bottom plate.
• Proportional Gain: parameter of the PID control of temperature.
• Gain additional: parameter of the PID control of temperature.
• Derivative Gain: parameter of the PID control of temperature.
• Time of sampling: sampling time of PID control.
• Minimum Steering: minimum of PID.
• Maximum Steering: maximum of PID.
• Ramp slope: ramp of the PID.
• Ramp discasa: ramp down of the PID.
• Manual: enables or disables manual control.
Write 1 (ON) and to enter to enable manual control, writing in the manual control command value (0 -
100%) that you want to have. Write 0 to disable the manual control (OFF).
• Reverse PID: Writing 1 (ON) and to enter to enable the PID reverse. Write 0 (OFF) to disable the
PID reverse.