Device connection

Notes:

When the fire fighting equipment output signal is active (closed) it means that the Load circuits is powered by whether via Normal or

-

,

Reserve power source

.

When the fire linkage inputs are active

the ATS will switch to OFF position disconnecting LOAD from power sources.

,

To re-activate the device, the fire fighting signal must be removed and the Manual/Auto button must be pressed once. So, the ATS will

-

return to normal operation.

Normal Power     Reserve Power

Controller

Display Controller

Normal Power
Normal Power ON

Reserve Power
Reserve Power ON

Fire Linkage

Generator Control

DC24V Aux. Power

Load

L1  L2  L3  N

L1  L2  L3  N

L1  L2  L3  N

L1,L2,L3 - phase wire connections;
N - neutral wire connections.

CONTROLLER TERMINAL CONNECTIONS

101 - 103 : Normal Power external Indicator
outputs ( Active AC230V 0.5A)

101 - Indicator common neutral line
102 - Normal power indicator signal output
103 - Normal power ON signal output

201 - 203 Reserve power external indicator
outputs Active AC230V 0 5A

(

/ .

)

201 - Indicator common neutral line
202 - Reserve power indicator signal output
203 - Reserve power ON signal output

301 - 302 Auxiliary power supply

24VDC inputs

15-

301 - “+” input
302 - “-” input

401 - 404 Fire linkage control signal inputs and
feedback signal outputs

401 402 - Fire linkage signal passive inputs

,
,

403 404 - Feedback signal outputs  (active when ATS
transfer is in OFF position)

501 - 503 - Generator remote start control signal
outputs

501 - Control signal NO point
502 - Control signal common point
503 - Control signal NC point

Controller

4

N power
 indicator

R power
 indicator

Activ
e AC230V

 output

Activ
e AC230V

 output

Aux.power

Gener

ator

 control

Pa

ssiv
e output

Fire-linkage

 Control

Pa

ssiv
e output

Pa

ssiv
e input

Split

 interf

ace

Содержание 125A-4P-di

Страница 1: ...iary power supply only High density silver alloy contacts providing thousands operating cycles at 100 rated load Bridge type double break design not requiring special SCPD and matching AC 33B requirements Optimized magnetic blow out arc extinquish system allowing to reach 10le capacity Multi mode operation including manual transfer automatic transfer with without autorecovery and generator control...

Страница 2: ...Generator start signal activity 4 Fire linkage input activity ATS stops when fire linkage input active 5 Normal main power data indication zone 6 Reserve power data indication zone 7 Setting mode button 8 Auto Manual transfer mode selection button in the work mode and Save Escape button in the setting mode 9 OFF button in the manual control mode and the value decrease button in the setting mode 10...

Страница 3: ... 000 to 023 Generator exerciser timer minute setting press to change the timing of minute from 000 to 059 Generator exerciser timer second setting press to change the timing of second from 000 to 059 Generator exerciser time duration hour setting press to change the timing of hours from 000 to max 500 hours Generator exerciser time duration minute setting press to change the timing of minute From ...

Страница 4: ...r exerciser timer settings parameters A 12 A 22 are not configured To cancel the exerciser during the generator exerciser duration time change the switch mode to manual and press any button Controller functions Under over voltage detection Controller monitors configured under over voltage values of normal and reserve power supply phases When the under over voltage is detected for one of the power ...

Страница 5: ... 103 Normal Power external Indicator outputs Active AC230V 0 5A 101 Indicator common neutral line 102 Normal power indicator signal output 103 Normal power ON signal output 201 203 Reserve power external indicator outputs Active AC230V 0 5A 201 Indicator common neutral line 202 Reserve power indicator signal output 203 Reserve power ON signal output 301 302 Auxiliary power supply 24VDC inputs 15 3...

Страница 6: ...er EN55011 Radio frequency radiation Transmit test as per EN55011 Anti interference Test Static Discharge air discharge class 4 contact discharge class 3 as per IEC61000 4 2 Radio frequency electromagnetic field Class 3 as per IEC61000 4 3 and IEC61000 4 6 Fast transient pulse group Class 4 as per IEC61000 4 4 Surge Class 4 as per IEC61000 4 5 Short time voltage drop and voltage off passed Fault C...

Страница 7: ...29 70 29 29 29 27 4PRO ATS 250A 4P di 133 66 5 5 35 110 55 127 112 56 127 38 38 41 90 38 42 190 228 58 240 237 400 430 58 58 272 50 30 4PRO ATS 630A 4P di Display controller outline and split mounting dimensions overall dimensions Split mounting dimensions 3 2 1 4 5 6 Accessories RJ 45 Connector User manual Notes Outline Drawing Size ...

Отзывы: