Features

Short description

T

changeover switch is

designed to transfer loads automatically

his

an microprocessor based PC class device

and manually from one power source to another in a wide variety of 1-3 phase applications.
The unit monitors 3-phase normal and reserve source voltages, sends remote start command to the
generating set and performs changeover switching between those 2 sources connecting the load circuits to a
power source having voltage and frequency within preset limits.
Device has a manual load switch lever, a manual/auto mode switch and a mechanical locking switch.
Inputs and outputs: fire linkage control, generator remote start, external indicators.
The front panel leds provide information about mains and generator power availability as well as a current
switch position.
The device display control panel shows device current state and source voltages and frequences and can be
placed on the switch front side or  in a distance of 1-3 meters from the device via standard Ethernet cable.
Power source voltage/frequency limits, transfer/start/stop delays, generator exerciser schedule and transfer
modes are front panel configurable.
Note: The delays apply in case if the device is connected to 24VDC auxiliary power supply only.

• High density silver-alloy contacts providing thousands operating cycles at 100% rated load;
• Bridge type double break design not requiring special SCPD and matching AC-33B requirements;
• Optimized magnetic blow-out arc extinquish system allowing to reach 10le capacity;
• Multi-mode operation including manual transfer, automatic transfer with/without autorecovery and
generator control under various configuration settings;
• 3 working positions: main power ON - backup power OFF; main power OFF - backup power ON; main and
backup power OFF;
• Microprocessor controlled operations;
• Reliable mechanical interlock and electric interlock;
• "Zero Position" technology. Device can be set to Zero Position under emergency situations with two way
power supply cut off meeting the fire fighting linkage requirements;
• Singleness motor drive providing  smooth, reliable, low noise operation;
• Driving motor energized during switching operations only and having outstanding energy saving;
• Mechanical interlock, making sure that the Normal power and Reserve Power sources work without
interference;
• Distinct ON and OFF positions and activity indicators;
• Electromechanical integration design with accurate changeover adopting an advanced logical control
technology and  high anti-interference ability;
• Easy installation using control circuit plug type terminal connections.

1-3 Phase, 230/400VAC, 50/60Hz

Automatic Transfer Switch

ATS-125A

-4P-di

(250А,630А)

Содержание 125A-4P-di

Страница 1: ...iary power supply only High density silver alloy contacts providing thousands operating cycles at 100 rated load Bridge type double break design not requiring special SCPD and matching AC 33B requirements Optimized magnetic blow out arc extinquish system allowing to reach 10le capacity Multi mode operation including manual transfer automatic transfer with without autorecovery and generator control...

Страница 2: ...Generator start signal activity 4 Fire linkage input activity ATS stops when fire linkage input active 5 Normal main power data indication zone 6 Reserve power data indication zone 7 Setting mode button 8 Auto Manual transfer mode selection button in the work mode and Save Escape button in the setting mode 9 OFF button in the manual control mode and the value decrease button in the setting mode 10...

Страница 3: ... 000 to 023 Generator exerciser timer minute setting press to change the timing of minute from 000 to 059 Generator exerciser timer second setting press to change the timing of second from 000 to 059 Generator exerciser time duration hour setting press to change the timing of hours from 000 to max 500 hours Generator exerciser time duration minute setting press to change the timing of minute From ...

Страница 4: ...r exerciser timer settings parameters A 12 A 22 are not configured To cancel the exerciser during the generator exerciser duration time change the switch mode to manual and press any button Controller functions Under over voltage detection Controller monitors configured under over voltage values of normal and reserve power supply phases When the under over voltage is detected for one of the power ...

Страница 5: ... 103 Normal Power external Indicator outputs Active AC230V 0 5A 101 Indicator common neutral line 102 Normal power indicator signal output 103 Normal power ON signal output 201 203 Reserve power external indicator outputs Active AC230V 0 5A 201 Indicator common neutral line 202 Reserve power indicator signal output 203 Reserve power ON signal output 301 302 Auxiliary power supply 24VDC inputs 15 3...

Страница 6: ...er EN55011 Radio frequency radiation Transmit test as per EN55011 Anti interference Test Static Discharge air discharge class 4 contact discharge class 3 as per IEC61000 4 2 Radio frequency electromagnetic field Class 3 as per IEC61000 4 3 and IEC61000 4 6 Fast transient pulse group Class 4 as per IEC61000 4 4 Surge Class 4 as per IEC61000 4 5 Short time voltage drop and voltage off passed Fault C...

Страница 7: ...29 70 29 29 29 27 4PRO ATS 250A 4P di 133 66 5 5 35 110 55 127 112 56 127 38 38 41 90 38 42 190 228 58 240 237 400 430 58 58 272 50 30 4PRO ATS 630A 4P di Display controller outline and split mounting dimensions overall dimensions Split mounting dimensions 3 2 1 4 5 6 Accessories RJ 45 Connector User manual Notes Outline Drawing Size ...