Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4Evac SW6 / SW6-LITE INSTALLATION and USER
GUIDE V04
Author:
TC
Page 25 of 26
Technical specifications
All information provided in this document is subject to change without notice. 4EVAC may also make improvements and/or changes
in the products described in this information at any time without notice.
4E-SW6
Inputs
Number / type
2 x 50/70/100V audio inputs
Rating
max. 500W continuous per input (2ch)
Surveillance
20kHz impedance measurement with EOL
Outputs
Number / type
6 x 50/70/100V loudspeaker lines
Rating
20W to 200W continuous per output.(6-lines)
Surveillance
Built-in
20kHz AC monitoring of EOL module, short/open/impedance deviation
Loopdrive
Loop DC monitoring with short-circuit isolators, short/open/earth leakage, EN54-17
Number of zones
max. 6 zones per SW6
Power consumption
24V (L-Net / 24V DC in)
continuous 175mA (quiescent), peak 225mA (all relays activated)
Audio performance
Frequency response
20 Hz – 20 kHz
Local network interface
Architecture
Master-slave, up to 16 slave devices per main controller unit
Connection
RJ-45, powered daisy chain, digital audio & control data, redundant
Cabling
X-over FTP CAT5e (or higher)
Current rating via single link
max. 500 mA via L-Net port,
Max. length of L-Net link
250 m
Mechanical
Dimensions HxWxD)
9 x 11.8 x 6.5 cm
Weight
375 g
Housing material
ABS
IP rating
IP 30
Mounting
DIN rail
Operating conditions
Temperature (ambient)
10–40°C
Temperature (max. device)
65°C
Relative humidity
max. 90% (non condensing)
Storage temperature