4EVAC Impact Controller-Expander Скачать руководство пользователя страница 4

Hacousto Holland bv 
Industrieweg 87 
2651BC  Berkel & Rodenrijs 

 

Impact Controller – Expander 
User and installation manual 

Author: 

DD 

 

 

 

Page 

4

 of 

10

 

  

 

2.

 

Front panel 

 

 

Indicators (functions identically to the Impact Controller, except power supply fault): 

 

POWER 

Indicates if the Controller is being powered and if the system is booted properly. 

OFF 

Not powered 

GREEN continuous 

This device is powered and operational. 

GREEN blinking 

This device is booting after power up / reset. 

 

EVAC 

Indicates  that  the  system  is  in  Voice  Alarm,  where  at  least  one  zone  in  the  system  is  occupied  by  an 
emergency audio signal, i.e. a pre-recorded EVAC MESSAGE or LIVE EVAC, when a fireman mic is being 
used. 

OFF 

EVAC status is inactive (quiescent mode) 

RED continuous 

EVAC status is active 

 

GENERAL FAULT 

Indicates that the system is in FAULT condition (general fault indicator), where at least one device in the 
system is reporting a fault. 
 

OFF 

System is healthy 

YELLOW continuous 

Local fault is detected (this Controller-Expander) 

YELLOW blinking 

Local  device  (this  Controller-Expander)  is  healthy  and  at  least  one  remote 
device is reporting fault state 

 

POWER SUPPLY FAULT 

Not used.  
The Controller-Expander (in comparison to the Impact Controller) has no management interface to power 
supply equipment, so there are no local power supply faults to be reported. 

Содержание Impact Controller-Expander

Страница 1: ...ent describes the Controller Expander which is an optional network port expander dedicated to 4EVAC Voice Evacuation systems REVISION AND APPROVAL Rev Date Nature of Changes Approved By 01 09 03 2020 Preliminary draft DD 02 08 06 2020 Updated pictures minor corrections DD 03 11 06 2020 Corrections TvdH 04 05 08 2021 Technical specifications corrections AJH ...

Страница 2: ...ntents 1 What is the Controller Expander 3 2 Front panel 4 POWER 4 EVAC 4 GENERAL FAULT 4 POWER SUPPLY FAULT 4 SYSTEM FAULT 5 NETWORK FAULT 5 3 Rear panel 5 Local network 6 Global network 6 Device ID 6 Micro SD card 7 RESET button 7 4 Configuration settings 7 5 Network cabling 7 6 Connections and recommended cable types 8 7 Technical specifications 9 ...

Страница 3: ...nder may be used in the system only as an additional interface connected to the main network of 4EVAC VACIE main units Functionally the 4EVAC Controller Expander works as a network hub for additional L Net devices such as microphone stations In terms of interfacing the Controller Expander only features a DC power input and network ports Global Network and Local Network The Controller Expander incl...

Страница 4: ...upied by an emergency audio signal i e a pre recorded EVAC MESSAGE or LIVE EVAC when a fireman mic is being used OFF EVAC status is inactive quiescent mode RED continuous EVAC status is active GENERAL FAULT Indicates that the system is in FAULT condition general fault indicator where at least one device in the system is reporting a fault OFF System is healthy YELLOW continuous Local fault is detec...

Страница 5: ...tical functions including audio transmission reaction on control inputs etc are stopped until the fault is resolved OFF Firmware and settings OK YELLOW continuous CPU program fault YELLOW blinking o SD card fault o Config file not compatible o Wrong ID setting NETWORK FAULT Indicates when any device or link in the network is missing OFF Network OK YELLOW continuous At least one device from the Loc...

Страница 6: ...s not support 4E SW6 Global network G Net is a redundant network ring where multiple Controllers and Expanders may be connected into one system It is used to reliably synchronize data between all connected devices and for multi channel live audio transmission with very low latency G Net works as a redundant double ring between Controllers which keeps the global system intact in case of single link...

Страница 7: ... be reset only by a manual device reset RESET button Press it to trigger a hard reset of the Expander different from RESET button on front panel soft reset 4 Configuration settings The Controller Expander remains a G Net device and as such can be supplemented with max 16 L Net devices which will be local slaves of this Controller Expander The Controller Expander in comparison to Impact Controller ...

Страница 8: ...es and keep the correct pinout Connecting power pins to data pins will damage the network port 6 Connections and recommended cable types How many Connector type Signal type Additional information Recommended cable minimum Max length G Net port 2 RJ 45 Full duplex RS 422 Redundant ring with power delivery FTP CAT5e crossover 250m to next device L Net port 3 Daisy chain with power delivery DC Power ...

Страница 9: ...t 4 kg Mounting 19 rack mounting Operating conditions Temperature Ambient 5 40 C Max Temperature Device 65 C Relative humidity max 90 non condensing Storage temperature 40 70 C Network system Max number of devices in the network 254 Number of simultaneous network audio channels 2 Network audio transmission latency 0 3 ms per device Local network Architecture Master slave up to 16 slave devices per...

Страница 10: ...kel Rodenrijs Impact Controller Expander User and installation manual Author DD Page 10 of 10 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berkel Rodenrijs The Netherlands www 4EVAC com ...

Отзывы: