4EVAC Compact 500 Скачать руководство пользователя страница 21

Hacousto Holland bv 

Industrieweg 87 

2651BC  Berkel & Rodenrijs 

 

4EVAC Compact 500 quick guide 

DoP OD 16.47 

Author: 

DD 

Design revision: 

2.0 

 

Page 21 of 33 

  

 

 

Memory card 

The Compact 500 is supplied with a pre-installed micro SD memory card. The memory card contains a 

complete Compact 500 system configuration file, including audio messages. 
The configuration file is prepared in the 4EVAC Manager - Windows GUI application. More information 

about creating configuration settings can be found in the 4EVAC Manager User Manual.  
 

 

Location of memory card on the main board. 

The memory card is under constant surveillance, as well as its content. When the memory card is removed, 

damaged or its contents are corrupted, the Compact 500 will report a system fault. During the system fault 

caused by a memory error, the Compact 500 enters SAFE STATE, where the system stops all functions and 

requires a reboot. This state can be reset only through a manual device reset. 

 

Close-up of memory card socket. 

Содержание Compact 500

Страница 1: ...of Compact 500 Voice Evacuation System It explains how the hardware of Compact 500 should be installed and configured Quick guide is addressed to the trained technical personnel such as installers se...

Страница 2: ...ESET inputs 11 System status relay outputs 11 6 5 1 EVAC out 12 6 5 2 FAULT out 12 6 5 3 RESET out 12 GPI GPO 12 Loudspeaker lines 13 6 7 1 Bridging to 200 W 13 6 7 2 EOL board 16 Analog audio input B...

Страница 3: ...transformers number of amplifier units depends on the hardware config you ordered DIN rail with 16A fused manual mains switch Integrated EN54 4 power supply equipment with temperature compensated cha...

Страница 4: ...officially certified by the manufacturer Any actions carried out in Access Level 3 without the manufacturer s explicit approval may lead to incorrect settings or hardware damage causing serious syste...

Страница 5: ...steps 1 Place the bracket on the wall Optimal height of the top is 170 cm above floor level 2 Using wall plugs fix the bracket in 3 points 3 Optionally in the space between the left and right edge of...

Страница 6: ...rder to open the cabinet follow the steps below 1 Find two round openings in the front top part of the cabinet where fixing screws are placed 2 Undo both screws using a hex key also known as Allen wre...

Страница 7: ...enrijs 4EVAC Compact 500 quick guide DoP OD 16 47 Author DD Design revision 2 0 Page 7 of 33 After opening the Compact 500 you should see following functional sections as shown on the picture below Co...

Страница 8: ...ircuit follow the instruction below 1 Before installing the battery measure the voltage of each battery separately Open circuit voltage of a well functioning healthy 12V battery should be in range of...

Страница 9: ...ire metal housing of Compact 500 Dropping an unprotected battery lead on any part of the hardware housing or battery brings high risk of a short circuit and may damage the hardware and the battery The...

Страница 10: ...e lead long black to the negative pin of battery B 7 Check the voltage of each battery again separately and the total voltage of both batteries 8 Cover all battery terminals with insulating rubber cap...

Страница 11: ...ring which requires two resistors of 4 7k 10k in order to detect an input active inactive state as well as a short and open fault EOL resistors must be located directly at the triggering output inside...

Страница 12: ...ctivated closed while the fault status is reported by the voice evacuation system Also activated when the Compact 500 is not powered 6 5 3 RESET out Activated closed immediately after a manual reboot...

Страница 13: ...in Compact 500 offers 2 audio channels max 100W each By default both channels are working independently each with a 100V output Loads greater than 100W up to 200W are handled by bridging outputs of b...

Страница 14: ...Author DD Design revision 2 0 Page 14 of 33 6 7 1 1 Single channel For single channel mode 2x100W two jumpers on the amplifier unit must be set to the 100V position center position One jumper per chan...

Страница 15: ...guide DoP OD 16 47 Author DD Design revision 2 0 Page 15 of 33 6 7 1 2 Bridged For bridged mode 1x200W four jumpers must be set to the 50V position left right position Two jumpers per channel Jumper s...

Страница 16: ...xposing the EOL board to temperatures exceeding 145 C will damage the EOL circuit and cause an open fault of the loudspeaker line The purpose of the EOL is to create a reference load at the monitoring...

Страница 17: ...microphone feature you can disable it in the configuration settings and use analog audio input 2 as an external audio input for background music Network ports 4EVAC Compact 500 offers 5 ports RJ 45 fo...

Страница 18: ...will damage the network port 6 9 1 Global network G Net G Net works as a redundant ring between Compact 500 main units It is dedicated to secure a reliable system bus which keeps the global system int...

Страница 19: ...Net ports have individual settings for 24V DC power over G Net for remote G Net devices Power over G Net is set by means of hardware jumpers located next to the G Net port Power over G Net is dedicate...

Страница 20: ...s such as paging consoles It is dedicated to provide a powered bus to peripheral devices Every L Net port is powered with 24V DC and power over L Net is always enabled L Net capacity of single a Compa...

Страница 21: ...Windows GUI application More information about creating configuration settings can be found in the 4EVAC Manager User Manual Location of memory card on the main board The memory card is under constan...

Страница 22: ...mory card may be removed and mounted during system runtime hot plug Mounting the memory card requires a manual device reset afterwards Device ID setting The compact 500 is equipped with a rotary switc...

Страница 23: ...ated to the relatively high energy pulse at system inrush always plug or unplug the battery fuse when the system is powered from the mains supply Power the system up and down according to the followin...

Страница 24: ...2550 B After changing a battery setting you should reboot the charger board Press the RESET button on the charger board Why is it important The power supply equipment of the Compact 500 implements a v...

Страница 25: ...C Blink double Main power supply output voltage high 33 V DC ON Main power supply not detected BATT fault yellow Indicates battery fault OFF Battery OK Blink single Battery voltage low 25 8 V DC Blink...

Страница 26: ...done manually for all lines at once If any line would not calibrate it will stay in the not calibrated state which is indicated on the amplifier unit see amplifier indications in next chapter Other l...

Страница 27: ...ompact 500 quick guide DoP OD 16 47 Author DD Design revision 2 0 Page 27 of 33 EOL is disconnected EOL impedance setting is incorrect In case of one or more lines not calibrating follow the indicatio...

Страница 28: ...indicators per channel GREEN LED amplifier power on fault status RED LED impedance measurement You can identify the status of every channel and line according to the table below Visual blinking sequen...

Страница 29: ...mpact 500 quick guide DoP OD 16 47 Author DD Design revision 2 0 Page 29 of 33 Every amplifier channel corresponds to the loudspeaker line as follows AMP 0 AMP 1 AMP 2 AMP 3 A B A B A B Backup amplifi...

Страница 30: ...number of individual triggering signals from to fire detection system 1000m EVAC FAULT RESET out 3 Potential free relay output n a 1000m GPI 8 Pull down input n a Depends on length typ N x 0 75 1 5mm2...

Страница 31: ...s Evac manual control EVAC message ALERT message SILENCE RESET fireman mic with PTT button Fireman microphone Integrated Fireman Mic with priority and electrical monitoring Power supply equipment Buil...

Страница 32: ...ull config without batteries 29 kg Housing material Steel ABS IP rating IP 30 Mounting Wall mounted box Network system Max number of devices in the network 255 Max number of zones 255 Max total system...

Страница 33: ...odenrijs 4EVAC Compact 500 quick guide DoP OD 16 47 Author DD Design revision 2 0 Page 33 of 33 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 265...

Отзывы: