Output 1 Levels
–
Min Max
75cm 90cm
- + Min Exit
Output 2
Type Probe Switch
Drain 1 1 Next
Output 2 Levels
–
Min Max
30cm 33cm
- + Min Exit
Explanation – the pump will operate as long as there is 33cm of more of water and the pressure switch
(normally closed at low pressure) is closed. The level cannot drop below 30cm, protecting the pump from
running dry, and as long as mains water is available will not drop below 75cm. Note that the mains back up
is set to only supply 15cm of water, so as not to use mains water unnecessarily.
Tank Alarms (Menu>Setup>Alarms)
This menu contains the settings for the high and low level alarms for each tank/probe. Once either of these
levels is exceeded, the BMS output will be activated, the red alarm LED on the panel will illuminate, and a
fault code will be stored.
The high and low alarm levels for a tank should of course be set beyond the normal operating levels of the
devices filling or draining the tank.
Fault Diagnosis
Diagnostic Menu (Menu>Diags)
This menu provides diagnostic options including the ability to view the state of all inputs, activate the
outputs, manually, compensate for level probe instability problems, and view any high or low level alarm
events that may have occurred.
Input Options (Menu>Diags>Inputs)
From this menu you can select whether you want to view or adjust inputs, activate or test outputs, or view
and clear faults previously logged.
View Inputs (Menu>Diags>Inputs>View Input)
In this screen you will be presented with an overview of the status of all 5 switch inputs, and the current
detected by the analogue level sensor inputs in MilliAmps.
Switches 10111
Tank 1 12.0 mA
Tank 2 0.0 mA
TC Series Controller v1.30
www.3ptechik.co.uk
09-August-2017
Page 17 of 28