3M Quick Term II Скачать руководство пользователя страница 4

D.  Install Lug or Connector

1.  Install lug or connector per manufacturer’s instructions.  See Crimping Table below when

using 3M type lugs.

NOTE: when installing in enclosed
switchgear or transformers maintain
clearances required by
manufacturers.

CRIMPING TABLE FOR 3M STEM TYPE CONNECTORS

Conductor 

3M

 Stem Recommended Crimping Tools

Size Conn. No. Manufacturer Mech. Tool Die (No. Crimps) Hydraulic Tool Die (No. Crimps)

#1 Sol.

#1 ,#2

1/0

SC0002
SC0001
SC0010

BURNDY

KEARNY

T &B

ANDERSON

MD6

O-51,O-52

TBM8

-

BG(4).W-243(4)

5/8 (4)

OLIVE (2)

-

Y35,Y39,Y45**

TBM 15

VC 6

U25ART(2),U243(2)

50*(2)

UNIVERSAL (2)

2/0
3/0
4/0

SC0020
SC0030
SC0040

BURNDY

KEARNY

T &B

ANDERSON

MD6

O-51 ,O-52

TBM8

-

W660(3),840(5)

840(5)*

WHITE(4)

-

Y35,Y39,Y45**

WH-1 ,WH-2

TBM 15

VC 6

U28ART(2)

840(2)

66(3)

UNIVERSAL (2)

250 - 1000 kcmil

Crimp According to Manufacturer's Directions

‘3M’, ‘Cold Shrink and ‘Scotchlok’ are trademarks of 3M

Important Notice to Purchaser:

All statements, technical information and recommendations related to the Seller’s products are based on information believed to be reliable, but
the accuracy or completeness thereof is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its
intended use. The user assumes all risks and liability whatsoever in connection with such use.

Any statements or recommendations of the Seller which are not contained in the Seller’s current publications shall have no force or effect unless
contained in an agreement signed by an authorized officer of the Seller. The statements contained herein are made in lieu of all warranties expressed
or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are hereby
expressly disclaimed.

SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY INCLUDING BUT NOT LIMITED
TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECT OR CONSEQUENTIAL DAMAGES SUSTAINED OR
INCURRED BY REASON OF THE USE OF ANY OF THE SELLERS PRODUCTS.

Electrical Products Division

6801 River Place Blvd.

Austin, TX 78726-9000

Litho in USA

© 1997 3M
78-8111-0842-8

Содержание Quick Term II

Страница 1: ...e Shielded Cable 15 kV Class 5671 5672 Number of Pages 4 Issue Date 9 9 97 Scale Not to Scale Issue 78 8111 0842 8 DIMENSION TABLE Kit No A B 15 kV Cond Size Range AWG kcmil Primary Insul O D Range inch mm 5 6 71 10 254 mm Depth of Lug or 2 2 50 637 1 120 16 2 28 4 mm 5 6 72 10 254 mm Stem Connector Barrel 250 I000 940 1 810 23 9 46 0 mm IEEE Std No 48 1975 Class 3 Termination 15 kV Class Kit Cont...

Страница 2: ...onnection Figure 2 2 WIRE SHIELD a Remove jacket as shown in Figure 3 and dimension table below Be sure to allow for depth of lug B b Wrap 2 full wraps of Scotch 24 Shielding Tape over shielding wires at jacket edge Cut off excess 24 Tape Figure 3 c Bend shielding wires back over 24 tape and cut off excess at cable jacket edge Figure 3 d Remove cable semi con as shown in Figure 3 3 Remove cable in...

Страница 3: ...Figure 4 Note Cinch tighten the applied coil after final wrap C Install Termination 1 Cover the edge of the 13 tape or semi con material with a liberal coating of silicon grease Figure 4 NOTE ON THIS PRODUCT THE SILICONE GREASE DOES NOT SERVE AS A LUBRICANT IT MUST BE USED TO FILL THE STEP AT THE LEADING EDGE OF 13 TAPE OR THE STEP AT THE SEMI CON CUTOFF Spread silicone grease over the entire expo...

Страница 4: ... Seller s products are based on information believed to be reliable but the accuracy or completeness thereof is not guaranteed Before utilizing the product the user should determine the suitability of the product for its intended use The user assumes all risks and liability whatsoever in connection with such use Any statements or recommendations of the Seller which are not contained in the Seller ...

Отзывы: