CARBON MONOXIDE SENSORS

KCO SERIES

GAS & SPECIAL

TY SENSORS

2008 KELE CATALOG • www.kele.com • USA 888-397-5353 • International 901-382-6084

195

GAS & SPECIALTY SENSORS

DESCRIPTION

KCO Series Carbon Monoxide Sensors are available
in analog or relay versions. The sensors are provided in
heavy-duty steel enclosures, and the sensors use low-
temperature components that are ideal for open parking
garages in cold climates.

FEATURES

• Two-stage alarming (KCO-R)
• 0-200 ppm 4-20 mA output (KCO-A)
• Microprocessor-controlled recalibration (KCO-A)
• Heavy-duty enclosures
• Operating temperature down to -4°F (-20°C)
• Low-temperature option available -20°F (-29°C)
• Temperature and humidity compensated

KCO-R
The KCO-R is a two-stage carbon monoxide sensor with a relay output for each stage. If the CO level rises above
the warning stage setpoint for over 30 seconds, the warning relay, amber warning LED, and a three-minute mini-
mum “on” timer will activate. Once below the setpoint, the relay and LED will reset. If the concentration continues to
rise and exceeds the alarm stage setpoint for 10 minutes, the alarm stage relay and red LED will activate.
Calibration of the unit requires the application of a hydrated test gas.

KCO-A
The  KCO-A is a microprocessor-controlled sensor with a 4-20 mA analog output based on a 0-200 ppm sensing
range. The microprocessor controls the heating of the sensor and subsequent reading of the CO level. The micro-
processor compensates for any drift in the sensor over time. The microprocessor system includes self-diagnostic,
self-restarting, and remote failure reporting. The output signal will drop below 4 mA if a fault is discovered. If power
problems cause the unit to malfunction, the unit will self-check and restart. Calibration of the unit requires the appli-
cation of a hydrated test gas, and the push of a button performs the recalibration.

INSTALLATION

Note: Front covers are blank

KCO-R
Power

24 VAC/VDC ±20%, 260 mA

Power with LT option

1.125A

Indicators

Amber

Warning

Red

Alarm 

Flashing green/red

Power on, microprocessor 
operating

Warning stage delay

30 sec

Range

0-250 ppm

Response time

Under 30 sec

Relay contacts

120 VAC, 2A resistive

Setpoints

Warning 50 ppm, alarm 100
ppm (reset 5-10 ppm change)

KCO-A
Output signal

4-20 mA into 500

Ω

max

Scale 

0-200 ppm carbon monoxide

Power

24 VAC ±20%, 10 VA

Power with LT Option

34 VA

Analog resolution

12 bit

Reading delay

10 minutes

KCO-R, KCO-A
Operating temp

-4° to 185°F (-20° to 85°C)

Sensor type

Solid-state metal oxide 
semiconductor

Humidity

5% to 95% noncondensing

Enclosure dimensions 6.25"H x 6.125"L x 3"D

(15.9 x 15.6 x 7.6 cm)

Accuracy

±5%

Sensor drift

±10% 2 years

Sensor life

10 years

Weight

3.0 lb (1.4 kg)

Warranty

18 months

SPECIFICATIONS

KCO-A-H

KCO-R-H

Содержание Macurco CM-21A

Страница 1: ... CM 21A Carbon Monoxide Detector and Controller User Instructions for 3M Macurco CM 21A Low voltage dual relay Carbon Monoxide CO detector and controller Important Keep these User Instructions for reference 1 ...

Страница 2: ...A mounts on a standard 4x4 electrical box and becomes cover for the box Supervised system any internal detector problem will cause the fan relay to activate Optional calibration kit is available One screw allows access for calibration Specifications Power 3 watts from 12 to 24 VAC or VDC Current 12 V 0 25 amps 24 V 0 12 amps Shipping Weight 1 pound Size 4 1 2 x 4 x 2 1 8 in Color gray Connections ...

Страница 3: ...ve feet above the floor 3 See applicable building code for fan size vs air changes per periods of time 4 Make sure there are air inlets to provide adequate air flow throughout the building Typical multiple CM 21A installation space sensors equally relay red red yel yel blue brn org POWER 12 24V ALARM RELAY SPDT fan RELAY CM 21A coil MAIN FAN POWER exhaust fan RELAY 12 or 24 vdc coil Alarm Control ...

Страница 4: ...20 mA analog output based on a 0 200 ppm sensing range The microprocessor controls the heating of the sensor and subsequent reading of the CO level The micro processor compensates for any drift in the sensor over time The microprocessor system includes self diagnostic self restarting and remote failure reporting The output signal will drop below 4 mA if a fault is discovered If power problems caus...

Страница 5: ...pm N O N C Warning Relay Factory setting 50 ppm N O N C T3 T2 L2 KCO A 24 VAC 4 20 mA SIG OUT L1 L2 WIRING 50 ppm 50 100 ppm relay settings KCO R only R Relay output carbon monoxide sensor MODEL KCO DESCRIPTION H Hinged cover enclosure KCO R H 50 ppm Example KCO RH 50 ppm Carbon monoxide sensor with relay output and hinged cover enclosure A Analog output carbon monoxide sensor LT Low temperature o...

Отзывы: