78-8096-4635-5-C
3
Instructions for 5/8 kV Pigtail Non-Shielded Feeder Cables
1.0 Prepare Cable According to Standard Procedures
NOTE: The Scotch
®
Stress Control Tape 2220 will not be used for non-shielded cable.
1.1 Check to be sure cables fit within cable kit range as shown in Table 1.
1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available,
remove for depth of lug barrel.
2.0 Install Lugs
2.1 Install and crimp lugs per manufacturer’s direction. See back page if 3M
™
Scotchlok
™
Lugs are used.
2.2 Clean insulation for approximately 6" using solvent saturated cloths provided in kit.
2.3 FOR 8kV ONLY. Fill lug/insulation gaps with Scotch
®
Linerless Rubber Splicing Tape 130C (Figure 1).
Large Lug
Small Lug
Scotch
®
Linerless Rubber Splicing Tape 130C
Scotch
®
Linerless Rubber Splicing Tape 130C
Figure 1
2.4 Bolt lugs together. See Table 1 for maximum bolt length. See Figure 2 for proper bolt/lug arrangement.
Large Lug
Small Lug
Bolt Should Be Inserted Thru
Hole Of Smaller Lug First
Washer
Figure 2