Test Installation
Follow these procedures to verify you have
correctly installed the 3M-30.
TO CHECK FAN
(If you connected the G wire):
Move the fan switch to
ON.
Verify that air is blowing from the
system. Move the fan switch back to
AUTO
.
TO CHECK HEAT
Set the mode switch to
HEAT
.
Touch the temperature display to bring up the MANUAL screen.
Touch the
+
icon and raise the target temp to 90
o
F; allow the system 2 minutes to respond.
Verify that heat is blowing from the system.
Return mode to
OFF
.
If you have a heat pump, leave mode in
OFF
for 4 minutes before checking COOL.
TO CHECK COOL
(do not operate AC if the outside temp is below 65
o
F)
Set the mode switch to
COOL
.
Touch the
-
icon and lower cool target temperature to 50
o
F.
Allow the system 5 minutes to respond.
Verify that cool air is blowing from the system.
Return mode to
OFF.
FAN
MODE -
HEAT-OFF-COOL