9. TROUBLESHOOTING

Reports on the display

Unit's behavior

Likely problem

SOLUTION

1 – Exchanger 1 over-

heated

unit is ventilating

Preheated electric exchanger or 

damaged sensor

Check that the air is flowing freely through the unit, that the 

electric exchanger cools down sufficiently, or that the safety 

thermostat of the el. reheating isn't damaged.

3 – Overheated preheating

unit is ventilating

Preheated electric preheater or 

damaged sensor

Check that the air is flowing freely through the unit, that the 

electric exchanger cools down sufficiently, or that the safety 

thermostat of the el. reheating isn't damaged.

4 – Supply fan error

Unit is not working

Overheated fan or defect on ther-

mal contact of inlet fan

Determine the cause of the overheating: defective bearing, short-

circuit...

5 – Exhaust fan error

Unit is not working

Overheated fan or defect on ther-

mal contact of inlet fan

Determine the cause of the overheating: defective bearing, short-

circuit...

6 – Inlet filter clogged

unit is ventilating

Check clogged filter

If the filter has been replaced or if it does not need to be re

-

placed, reset the filter clogging

7 – Exhaust filter clogged

unit is ventilating

Check clogged filter

If the filter has been replaced or if it does not need to be re

-

placed, reset the filter clogging

12 – CO2 sensor failure

unit is ventilating

Defective air quality sensor

Control the air quality sensor and its connection to the unit

16 – Inlet – External 

temperature sensor failure 

(T-EXT1)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

(professional service) 

17 – Inlet – Failure of the 

temperature sensor behind 

the exchanger (T-EXT2)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

(professional service) 

18 – Inlet – Temperature 

sensor failure in the supply 

canal (T-EXT3)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

(professional service) 

21 – Exhaust – Tempera-

ture sensor failure in the 

exhaust canal (T-INT1)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

(professional service) 

22 – Exhaust – Failure of 

the temperature sensor of 

the exchanger's anti-freeze 

protection (T-INT2)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

(professional service) 

25 – Room temperature 

sensor failure (T_Room)

unit is ventilating

Defective contact or sensor

Control the connection of the sensor and replace if needed 

74 – Flow reduction, mini-

mum temperature in the 

canal not reached

Limited operation of the unit

The minimum temperature in the 

canal was not reached

The temperature of the inlet and exhaust air is too low. Risk of 

undercooling of the building or condensation in the ventilation 

ductwork Possible failure of temperature sensor T-EXT3

The unit error is indicated with a red exclamation mark in the middle of the control display.  

Pressing the exclamation mark shows the information on the error, see table below.

Condensation fault

Unit is working

High level of condensate in the unit

Check if the sink is connected to the outlet of the condensate 

tank, the condition of the connection, and whether the sink is full 

of water.

Check the flow of the pipes and whether the position of the unit 

allows runoff.

The unit ventilates insuf-

ficiently or is noisy

Unit is working

Clogged filter or ductwork. 

Check the filters and whether the ductwork is not clogged

Содержание Whisper Air

Страница 1: ...INSTALLATION COMMISSIONING AND OPERATION Whisper Air EN ver 1 29 05 20...

Страница 2: ...ecting the unit please read carefully and follow all instructions below The manufacturer reserves the right to make changes including technical documen tation without previ ous notification Please kee...

Страница 3: ...act the supplier immediately After unpacking check that the unit and accessories are in good order Contact the supplier in case of any doubt Do not attempt to commission a damaged ventilation unit If...

Страница 4: ...r h e a t e r N a c h h e i z e i n r i c h t u n g D X C O B y p a s s fl a p B y p a s s K l a p p e P r e h e a t e r V o r w r m e r O p e r a t i o n a l d i a g r a m F u n k t i o n s s c h e m...

Страница 5: ...ur business since 1995 4 SPARE PARTS Number Description Controls Water coil Electric heater CO2 sensor Heat exchanger Fan motor exhaust air Actuator for the bypass Fan motor fresh air Pressure sensor...

Страница 6: ...DX CO By pass flap By pass Klappe Preheater Vorw rmer Operational diagram Funktionsschema Fan Ventilator Heat exchanger W rmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensa...

Страница 7: ...962 31 1203 150 367 802 Fan Ventilator Heat exchanger W rmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO By pass flap...

Страница 8: ...R S T U V W X HRWA2 040 1901 397 963 195 165 1408 228 198 250 1835 689 32 922 45 265 446 88 600 212 70 74 120 179 46 HRWA2 070 2171 455 1116 172 102 1649 261 228 315 2105 763 37 1054 38 295 465 96 650...

Страница 9: ...9 186 315 962 962 31 1251 169 367 802 Fan Ventilator Heat exchanger W rmetauscher Filter Filter Regulation die Regulation Condesate exhaust Kondensatausscheidung Afterheater Nachheizeinrichtung DX CO...

Страница 10: ...HRWA1 100 E 1000 EPM 1 55 F7 Coarse 60 G4 50 3 400 7 5 3770 3 400 11 8 6770 3 400 7 5 3770 151 HRWA1 100 X 1000 EPM 1 55 F7 Coarse 60 G4 50 1 230 5 770 3 400 9 3 3770 1 230 5 770 150 The listed weigh...

Страница 11: ...designed for installation in the vertical position Other installation position is not possible Installation of the unit shall allow a sufficient access for performing maintenance servicing and dismou...

Страница 12: ...eiling 1 Measure carefully the position of the holes for the threaded rods not included 2 Drill the holes 3 Install threaded rods of the appropriate length C D E C HRWA1 040 110 mm HRWA1 070 168 mm HR...

Страница 13: ...no 3 Allen wrench Movethecoverupwardstoremoveit Itissecuredbyauxiliarybrackets see following picture Removed cover with brackets 6 INSTALLATION Hang the unit from the rods and secure the holes in the...

Страница 14: ...UM AKOVAT PR KOVOU BARVOU AKOVAT ZE V ECH STRAN ELIKOST LAKOVAN PLOCHY 0 17 m2 284 6 340 R2 6 2 44 6 26 306 8 380 8 OZ N ZEV SLO MN MJ MJ IFS HRWA1 KONZOLE P 3 026 D14358 1 289 ks kg 2 3 1 4 A4 D C A...

Страница 15: ...threaded rods and anchors are not included 2 Measure carefully the position of the anchoring holes on the wall threaded rods and anchors are not included A B A HRWA2 040 802 mm HRWA2 070 934 mm HRWA2...

Страница 16: ...to the above steps see C 4 Deployunitonthepreparedanchoringandinsertthethreadedrods into the hinges on the unit Connect the hinges with anchors with M8 screws N hled na ukotven jednotky Inspect all m...

Страница 17: ...1 Carefully measure the position of the holes on the ceiling where the unit s ductwork will be connected A HRWA2 040 1408 mm HRWA2 070 1648 mm HRWA2 100 1920 mm B HRWA2 040 250 mm HRWA2 070 315 mm HR...

Страница 18: ...d rods and holes in the wall and properly secure Check securing For ductwork connected to the unit from the top the use of a condensate header is recommended due to the potential for condensed water t...

Страница 19: ...ics remove the following screws Electronic parts 1 Remove 12 screws on the lower side CAUTION Door is held closed by 2 safety latches to prevent door from swinging down quickly Once the 12 screws are...

Страница 20: ...ax 3 5 m min 100 mm 18 mm Siphon SK HL138 Wall mounted or embedded in wall type not included RECOMMENDED SIPHON TYPES Siphon SK AKS3 not included min 100 mm Condensate pump CERP MAXI ORANGE Please rea...

Страница 21: ...21 2VV Creating innovative solutions for you and your business since 1995 6 INSTALLATION CONNECTION OF THE WATER COIL C O SMU2 024 3 2 ZV3 24 1 ZV2 024 HRWA2 xxx V1 2x G HRWA2 xxx C3 2x G...

Страница 22: ...e installation check that the indication of the terminals corresponds to the wiring connection diagram In case of doubt contact the supplier and do not connect the unit under any circumstances The uni...

Страница 23: ...e connected through an earth leakage breaker according to the current model The unit must be connected in a way that it can be discon nected from the power supply with one breaker Table of minimum bre...

Страница 24: ...erstv vzduch 5 Flap outlet Klapa wydechu Aletta Scarico Klapka pro odvodn vzduch 6 Water pump Pompa wodna Pompa dell acqua Vodn erpadlo N Neutral Entr e 24VAC 24V GND GND GND CAPTEUR PR SENCE DX GENE...

Страница 25: ...in is properly connected That the installation corresponds to the instructions in the manual That no tools or objects have been left inside unit That the filters are clean CAUTION Alterations and chan...

Страница 26: ...intervals or ac cording to the demands of the operating environment Iftheunitisoutofserviceforalongperiod itisadvisableto turn it on for one hour at least every six months CAUTION The service of inte...

Страница 27: ...iltr ePM 10 60 M5 2 ps FILTR HRWA1 xxx M5 1 1 2 Standard Optional xxx 040 070 100 2 Replacing filters After replacing filters check that the filters are properly secured and close the door The followi...

Страница 28: ...e temperature sensor behind the exchanger T EXT2 unit is ventilating Defective contact or sensor Control the connection of the sensor and replace if needed professional service 18 Inlet Temperature se...

Страница 29: ...RING OVERHEATED ELECTRIC PREHEATER AND AFTER HEATER CAUTION The service of internal components must be done only by a professional Always disconnect the unit before servicing Firstly remove the cause...

Страница 30: ...ame pliers for precision mechanics Releasing the printed circuit Philips screw no 0 Plastic parts Ceiling insulation of front panels box cutter 10 CONCLUSION Once the it has been installed read carefu...

Отзывы: