
45
2VV.
Creating innovative solutions for you and your business since 1995.
6.3-2.3 External control
•
Low voltage switching contact - maximum possible con-
tact load 12 V, 0.4 A.
•
CABLE: cable with two leads with min. diameter 0.5 mm
2
Max. length 50 m.
•
The contact is regularly on. When disconnected, the unit
turns off.
ATTENTION!
Not part of the supply
6.3-2.4 Fire contact
TECHNICAL DATA
•
Low voltage switching contact - maximum possible con-
tact load 12 V, 0.4 A.
•
CABLE: cable with two leads with min. diameter 0.5 mm2
Max. length 50 m.
•
The contact is regularly connected. When disconnected,
the ventilation unit operates according to the preset ven-
tilation capacity.
6.3-2.7 Movement sensor
Low voltage switching contact - maximum possible con-
tact load 12 V, 0.4 A.
CABLE: cable with two leads with min. diameter 0.5 mm2
. Max. length 50 m. The contact is regularly disconnected.
When connected, the ventilation unit operates according
to the preset ventilation capacity.
6.3-3 Control unit
To activate the unit, it is necessary to connect the remote
control with the unit using a control cable (data cable)
•
Slacken the bolt on the bottom of the remote control
•
Open the case of the remote control
•
Cut a hole for the cable
•
Insert the control cable to the connector of the remote
control
•
Fix the control panel to the wall
•
Close and screw up the control panel case
6. INSTALLATION