MENU - SUBUNITS

Use this menu to set the behaviour of the IC-S regulators 

connected as SLAVE

Number of SLAVE 

regulators:

0 ~ 10

Ad 1)

Ad 2)

Ad 1)

 – Use one door contact as main. Its status will be sent to the 

           SLAVE regulators and it will no longer be necessary to connect it to each

           regulator, if required.

 

Not allowed = the door contact will not transmit to the SLAVE regulator from the MASTER

 

 

Allowed = the door contact will transmit to the SLAVE regulator from the MASTER

Ad 2)

 – Activates in the main screen the icon to turn

           each SLAVE regulator ON/OFF If inactive, all the SLAVE 

           regulators will be turned on or off simultaneously

 

Not allowed = The SLAVE regulators are turned on/off simultaneously

 

 

Allowed = The SLAVE regulators can be turned on/off individually 

 

 

        form the main screen

1. CONTROL

Slave address parameter:

ADDRESS

SLAVE UNIT

ADDRESS

SLAVE UNIT

1

1

6

6

2

2

7

7

3

3

8

8

4

4

9

9

5

5

A

10

This MENU is available only for units with water heat exchanger

 it allows for advanced setting of water heat exchanger regulation.

 The MENU for setting the blowers when closing and opening 

doors. It allows for advanced settings of blower control.

Setting blower power limits

for open doors.

 Min - Max

The time for which the blower 

will be operational from the mo-

ment the desired temperature is 

ac0.3°C on the ROOM 

sensor in closed door mode. This 

setting is available only when 

the ROOM regulation sensor 

is selected (1616/Temperature 

sensor)

The set limits on blower power restrict the extent of blower control for open and closed 

doors. This restriction is applied to manual and automatic control of blower power. Exceed-

ing limits in any blower power setting is signalled when the setting element turns red with 

the text overruns.

Setting blower power limits

 limits for

 closed doors. 

Min - Max

Maximum temperature for 

return water

Setting periods for

 blower movement.

Only at 0:00 time and in 

Standby mode.

Minimum water flow

can be set only for 

analog control of blower.

MENU - Adv. WATER SETTING

MENU - Adv. fan setting

Содержание AirGENIO SUPERIOR

Страница 1: ...LE A AirGENIO CONN CABLE UTP AirGENIO PWR SOURCE 24VCD AirGENIO TEMP SENSOR 3 2M AirGENIO CONTROL PANEL AirGENIO PCB MODULE B AirGENIO TEMP SENSOR 10M AirGENIO PRESSURE LP AirGENIO PCB MODULE G AirGENIO I BUS 300MM AirGENIO PRESSURE HP AirGENIO PCB MODULE GL AirGENIO PCB SUPPORT AirGENIO PRESSURE VHP AirGENIO PCB MODULE K Package contents Qty Package contents Qty Package contents Qty NOTE ver 1 23...

Страница 2: ...on original accessories START UP After connecting power supply the display lights up and the data is loaded The device is ready to be activated once the service data has fully loaded The remote control has a touch screen The device is controlled tapping the symbols on the screen They only inform about status not errors They inform about errors Clicking on them opens a screen with the error report ...

Страница 3: ...h closed doors Air flow settings with closed doors Language Display backlight Parameters Date and time AirGENIO app QR code Back to previous screen Confirm return Confirm return Display required air flow 20 steps Reduce or increase opening s air flow with closed doors Display the current air flow status Current date and time Reduce or increase required tempe rature Actual temperature at selected s...

Страница 4: ...ode Only MANUAL Required heating rate in manual mode CANCEL Confirm return Confirm return Back to main screen Back to main screen Confirmation of selection Tap on a day to set different time modes Tap to add a new time mode Button to copy the day plan to another day Copy return Unless otherwise set the unit goes on stand by mode after the timer expires There are 5 languages available Confirm retur...

Страница 5: ...n be entered manually or by using a QR code for quick pairing of the unit Pairing smart device 1 Pairing using QR code IC3 gate 1 After scanning QR code from the controller press Save for saving the unit to the app 2 Manual pairing IC3 gate 1 00 Enter the IP addre ss from controler Enter the PIN from the controller Device s name After entering all the information from the control ler press Save fo...

Страница 6: ...ailed behaviour of the inputs and outputs of the regulators MENU FILTER TIMER MENU TEMPERATURE SENSOR Current timer status Set the time after which a notice will appear in the main screen 1000h 5000h Shows the status of the clogged filter in the main screen RESET button use after replacing filters Use this menu to set the period in motor hours after which you will be reminded to replace the filter...

Страница 7: ... control the regulator with a multi level panel Use this menu to set heating limits in summer months If the outside temperature sensor is not set the summer heating mode will operate only according to the selected time and the temperature will not be taken into account Options None Limit inactive On Off Only On Off and access to the information menu are enabled in the main screen On Off Temp Flow ...

Страница 8: ...g a specific temperature Time of shutter operation per minimum rotation of the motor from closed doors Time of shutter operation per maximum rotation of the motor from closed doors Blower power with open doors The temperature the shutter attempts to reach with open doors In this menu it is possible to specify which sensor will be active and the temperature the shutter will attempt to reach after c...

Страница 9: ... 8 8 4 4 9 9 5 5 A 10 This MENU is available only for units with water heat exchanger it allows for advanced setting of water heat exchanger regulation The MENU for setting the blowers when closing and opening doors It allows for advanced settings of blower control Setting blower power limits for open doors Min Max The time for which the blower will be operational from the mo ment the desired temp...

Страница 10: ...et for each control which then addressed according to it Ad 1 Ad 1 Sets the CAN address of the control panel so up to 2 control panels may be connected to the MASTER regulator Options CP 1 control panel s address is 1 CP 2 control panel s address is 2 Enable disable automatic switch of summer winter time Electric connection Option 1 CP 1 CP 2 CAUTION Each panel must have its own address otherwise ...

Страница 11: ...or malfunction 53 54 Unit out of order Temperature sensor malfunction on terminals 53 54 Check that the sensor is correctly connected to the electronics or test it measuring its resistance the resistance value at 20 C is around 10kW 61 Room temperature sensor malfunction 55 56 Unit out of order Temperature sensor malfunction on terminals 55 56 Check that the sensor is correctly connected to the el...

Страница 12: ...N 3 1 CONCLUSION In case of any doubt or query do not hesitate to contact our sales or technical support departments www 2vv cz 2VV s r o Fáblovka 568 533 52 Pardubice Czech Republic support 2vv cz 420 466 741 811 ...