Quick start 2-Wire v3.2
2.3. CHANNELS, Setting Channels:
As
an example1
, connect a 3 phase EMM.630.
(1) Make sure you are in 'Level3'. (2)Click on 'GROUP1'. (3)Click on 'CH0'.
(4) Select
module
'EMM220-630'.(5)Select
mode
'Energy'. (6)Enter the
Modbus address of the EMM.630 vb '1'. (7)Enter Modbus sub-address (
0=phase1, 1=phase2, 3=Phase3) '0'. (8) Enter an appropriate name
' IMPORT'. (9) 'GENERATE' and (9)a read the Modbus instruction
to the meter. (10) 'TEST RX' and read the meter's response with the
translation for 'VOLT','CURRENT','POWER',VA','PF'.(11)Set to 'PAY' and
press (9) 'GENERATE' and (9)a read the new 'meter reading' instruction to
the meter. (10)'TEST RX' and read the meter's response with the
translation for meter reading (12) 'SAVE' this setting. From now on we log
phase 1 (voltage, current, power, VA, PF) and the import meter readings
of an EMM.630. Press 'DAY' or 'MONTH' to read the graphs.
As example 2:
logging phase 2 of a 3-phase meter
(1)'EDIT GROUP-CHANNEL' to create a second channel on the help screen
via (2)the blue 'ADD CHANNEL' button. After "ADD CHANNNEL" is the new
channel number and in brackets possibly an unused channel number. It is
preferable to choose this unused channel number by entering it in 'Group
Name / Channel Nr' and only then pressing '"ADD CHANNEL" (3)Click on
'CH1'. (4)Enter channel '0' and click (5)'LOAD' to load a copy of 'CH0'. (6)
Enter sub-address '1' (=Phase2) and change the name (7) to '
EXPORT'. (8)'SAVE this configuration. (9) gives a sorting table of Modbus
addresses. Press again (9) to hide.
Result
: You have now connected your first Modbus meter. Every minute
voltage, current, ... of phase 1 and phase 2 logged together with the
import (= consumption) and the export (= injection) meter reading with
which consumption graphs are then calculated.
From this 'Level3' you can create up to 64 energy channels (CH0.. CH63),
and these can be set as Modbus meters or as measurements from the
REL.44, RG.016,... More information can be found in the detailed manual.
Sort:
As long as the 'SORT CHANNELS' button on the left is turned on (red) you
can grab a channel and drag it to another place or in a different group.
Once done, confirm by clicking 'SAVE LAYOUT'.
Creating Groups
Click on 'EDIT GROUP-CHANNELS' and then 'ADD
GROUP' to create a new group.
Delete a group: select the group in the left page
and then click on 'EDIT GROUP-CHANNELS' and use the 'DELETE GROUP x'
button to delete the group.
Rename a group: select the group in the left sheet and then click on 'EDIT
GROUP-CHANNELS'. Enter a new name under 'Group name' and confirm it
with the green button 'RENAME GROUP x'.
3. General remarks:
There are
NO
services associated with the purchase of a MEMo3
module. (NO: installation, configuration, backup, energy advice,...)
Look online for the latest version of this leaflet, the detailed manual
MEMo3b manual or the MEMo3b video tutorial.
It is important to work with the latest firmware in the web server
and the 2-Wire modules so upgrade! (see tutorial).
MEMo3 is a 3rd generation data logger. The SD card of MEMo3 is
NOT compatible with the SD card of MEMo1 and MEMo2
Remote access can be done via port-forward (see FAQ), or the
HTML-APP
.
A stable internet connection
is required for proper operation
.
The MEMo configuration, and 2 year logs are stored on the internal
SD card.
If something goes wrong with this SD card, all data will be
lost
. The solution is a backup subscription with a cloud application
provider.
After
each submission, take a printout (at SETTINGS)
of the
configuration of the modules and save it on PC.
MEMo3 'MENU' key (6) (top right):keep pressing until the menu
appears on the display:
FW CSS-JS / FW Memo / ERASE ALL/ EXIT
Each time you press the button (6) briefly, the menu 1 position continues.
If you have the desired menu (CSS-JS or FW MEMO): press ( 6) until this
menu becomes active. After loading the firmware, the WS.503 will
automatically reboot. (internet required!).
4. Technical data
General:
Power supply MeanWell: 230 Vac/50 Hz – protect with fuse 2P/6A
Web server power supply: 15 VDC/2 A, power consumption: 2 VA.
Internal SD card 4 GB
Operating conditions:
Operating temp. 10 °C to 50 °C; Storage temp.: -10
°C to 60
°C
Maximum humidity: 90%, no condensation. Highest point: 2000m
Physical Properties:
Housing: plastic, self-extinguishing according to . UL94-V0 Degree of
protection: IP20, EN 60529 Mounting on DIN rail, width 2 modules
Dimensions (H x W x L): 62mm x 90mm x 36mm, Weight: approx. 65
grams
Connections:
Power Supply: 15VDC/1A Stabilized
Bus: RS485 Modbus RTU(GAB+) at 9600.8N1 max 32 modules
RF LORA-FSK transceiver 868 MHz, 100mW
Ethernet connection with integrated transformers 10/100Mbit/sec
WiFi 2.4GHz 802.11 b/g/n , Tx power 19.5 dBm, Rx sensitivity -97dBm.
Labels:
RoHS: Non-toxic, cf. Guidelines WEEE/RoHS
CE: In accordance with EMC and low voltage directive: HBES – EN 50090-
2-2 and EN60950 – 1: 2006.
5. Installation instructions
Installation must be carried out by a certified installer and in accordance
with the regulations in force. The module must be built into a fireproof
fuse box. During installation, the following must be taken into account
(non-exhaustive list):
- the applicable laws, standards and regulations.
- the state of the art at the time of installation.
- This manual, which only mentions general provisions and should be read
in the context of each specific installation.
- the rules of good workmanship.
- the specified specs in this manual, otherwise there is a risk of damage to
the module.
This manual must be attached to the electrical installation file. On the 2-
Wire website you can always find the most recent manual of the product.
6. Support
Would you like to have the product repaired in case of a possible defect?
Please contact your supplier or order "inspection module" online.
7. Warranty provisions
The warranty period is two years from the date of delivery. The delivery
date is the invoice date of purchase of the product by the consumer. If no
invoice is available, the production date applies. The consumer is obliged
to inform Qonnex bvba in writing of the lack of conformity, and this at the
latest within two months after discovery. In the event of a lack of
conformity, the consumer is only entitled to a free repair or replacement
of the product, which is determined by Qonnex.
Qonnex is not responsible for a defect or damage resulting from incorrect
installation, improper or negligent use, incorrect operation,
transformation of the product, maintenance in violation of the
maintenance instructions or an external cause such as moisture damage
or damage due to overvoltage. The mandatory provisions in national
legislation on the sale of consumer goods and the protection of
consumers in countries where Qonnex sells directly or through
distributors, agents or permanent representatives take precedence over
the above provisions.
Qonnex bv B-9310 Aalst Belgium
[email protected] www.2-wire.net