background image

 

  

 

  

 

 Qonnex 

Quick start 2-Wire v3.2 

WS.503b (MEMo3) web server 

The "MEMo3" webserver is a Modbus master module. 
All I/O modules are either connected to the RS485 bus 

or wirelessly connected via LoRa or FSK at 868MHz. 
From the Memo web server, these I/O modules are 

then powered, configured, read, logged and logically 

switched. Configuration and reading is done via the 
web browser on your tablet or PC without the need 

for software. The web server also includes http client functionality so that 
data can be uploaded to a central server for central management or 

backup. With MQTT token, web servers can be linked to each other or one 
can get remote access via the APP HTML.  

1. Connect: 

Power supply MEMo: 

 

(1)Top left of the module,  15 

Volts DC via 

the included MeanWell HDR-15-30 power 
supply. 

PAY ATTENTION TO POLARITY 

 !!Use 

wire with section 

0.5mm² 

and with solid 

core to fit in the terminals 

(2)Fuse this 

power supply SEPARATELY 

2P/6A  

RS485 Modbus:  

(3) Data cable: 

 use type EIB bus cable (max. 

80m) with section 

0.5mm² 

and with fixed 

core to fit into the bus clamps, or use special 

Modbus cable for longer distances. 

Topology Modbus:

 only 

in line

 so 

no

 

branches, both bus ends close between 

A and B

 terminal with supplied 

end resistor 120 Ohm. Memo3 is located at a terminus of the bus. 

(3)Connection: 

 depending on the type of module, only make the 

necessary connections: Ground(-)black, A yellow, B white, + red (+ is 

power supply to module RG.016 and REL.44).  

Network: 

 

MEMo3 has both  (8)WiFi 2.4 GHz and (4)LAN linking. By default, WiFi is 
disabled and LAN is set to DHCP

. When

 you connect to a router, Memo 

gets an IP address and this is displayed on the (7) display.  

Note

: MEMo3 (and  PC) 

MUST 

always be connected to the internet (load 

graphs into PC, upgrade, equalize clock,...) 
With a working MEMo3: Short press on the (5) reset button will reboot 

the MEMo3, long press on 

 the menu button (6) until the running bar is 

finished you will enter the (7) display menu

: Here you can upgrade or 

clear the MEMo3 

 

completely. Short  press (6) to cycle through menu and 

long press (6) to activate the selected function. 

2. Configuration via tablet or PC: 

When the power supply is switched on, the display 

(7) lights up and after 

about 30 seconds* the

 LAN IP address and port number can be read. 

After typing in the IP ":"+ port number ( e.g. 192.168.0.20

:

8080) 

in the web browser on PC or Tablet (e.g. Google Chrome, Edge, Safari,... ) 

you will be taken to the web page of the MEMo3 web server. 

*If WiFi is 

turned on, the display will show 'WiFi connect' and it will take a little longer, about 
120 seconds before the LAN address appears. For more information, see 'Activating 
WiFi via the REDIRECT method'. 

 

At CONFIGURATION/SETUP you can change this 

LAN

 IP address by  typing 

it in the IP address fields or by checking DHCP to give a new IP address by 

the router. After modification, press "SEND IP CONFIG" and then press a 

2nd time, after which the web server will reboot and after which you can 
load the web page with the new IP settings.  

Note

: If you unplug the RJ45 during rebooting, the MEMo3 will remain in 

DHCP mode, which is useful if you go to a new installation to 

automatically connect to the network.  

 

To read or change this LAN IP address and network settings or to make 

the WiFi connection with your network, you can also use the 2-Wire IP 
server scanner: 

https://www.2-wire.net/product/ip-serverscanner/ 

 From 

this 

Windows tool 

you can find all web servers within your network. Place 

the cursor  on the MEMo3 LAN IP address and  click on "Set IP and 

SSID/Key" to change LAN IP settings, or configure 

the WiFi connection from there.  

To activate WiFi via the 2-Wire IP server scanner: 

Activate WLAN by entering SSID and KEY and then 
tick DHCP and press OK. Automatically, the 

MEMo3 now gets a free and 

FIX

 IP address set 

which then appears on the MEMo3 display after 
the auto reboot.  

Then from this network 

WLAN IP ":"+ 
port number ( e.g. 
192.168.0.21:8080) in 
the web browser on PC 

or Tablet and then you 

will be taken to the web 
page of the MEMo3 via 

WiFi. 

 

To activate WiFi via the 

REDIRECT method: 

By briefly pressing the RESET button 

(5) of MEMo3, it will reboot. During 

this reboot, keep pressing the MENU button (6) 

until first 'Connect WiFi' 

and then 'Start WiFi portal' appears, then release. MEMo3 is now an 

'

access point

', called '2WIRE-MEMo'. Choose 'networking' on your laptop 

and if it works properly, the list should now read: '2WIRE-MEMO'. 

Select 

this network

. If you are asked for a key: '

adminMEMO'

. Automatically 

your web browser will open and after a maximum of 1 minute you will be 
redirected to a REDIRECT screen where you can enter the IP settings.  

REDIRECT page: 
Fill in the SSID and password of your network and  

if you enter your own IP addresses, they must be 

adjusted according to the settings of your own 
WiFi network. It is easier to enter '0.0.0.0' for the 

4 IP addresses and a port number e.g. '8085', and 
in this way the web server itself ensures that a 
free and fix IP address is set which appears on the 

display. Now press "SAVE" and then go back to 
default network. Then the WLAN IP ":"+ 

port number ( e.g. 192.168.0.21:8080) in the web 

browser on PC or Tablet and you will be taken to 
the web page of the MEMo3 via WiFi. 

 
The "CONFIGURATION" button will take you to 

the webpage below: 

 

Settings:

 enter general settings 

 

Channels:

 set resolution graphs and overview 

page 

2.1. Firmware Upgrade:

 

Go to "CONFIGURATION/SETTINGS" section 5, click on the "FIRMWARE 

VERSIONS" button and if your web server has an internet connection, it 
will display available version and installed version. 

To test the connection, first press "DOWNLOAD" and wait until all the 
firmware of the different modules have been downloaded and get a green 
tick before upgrading the MEMo3: To do this, press the "INSTALL" button 

and the web server will be upgraded. 

IMPORTANT: 

During the upgrade process, DO NOT interrupt the power or 

the internet connection or risk damaging the MEMo!! Wait at least a few 

minutes for the web server to REBOOT itself and return to the login page. 

TIP: 

You can also upgrade via the (7) display, see detailed manual. 

2.2. MODULES, adding energy meters 

Logged in as '

Level3

'=installer or 

'VRM'=expert, you can enter 

Modbus meters, MQTT meters or 
meters coming from the RF gateway 

(RG.016) or Relay interface (REL.44) 

from the homepage.  

Set Level3

: Click on 'EDIT GROUP-CHANNELS'. Enter '

Level3

' and click 

'

CANCEL

'. At the top left you can now read the current level status. 