Important notes

Information on the installation manual

This manual enables operating or service personnel
to correctly install the product described below and
to use it safely and efficiently.

It is essential that these individuals read and fully
understand this manual before starting any work.
The basic prerequisite for safe working is to comply
with the safety notes and all instructions in this
manual.

The local regulations for health and safety at work
and general safety regulations also apply.

Safety

Correct use

The explosion-proof pocket filter insert PFG-Ex is
used as a prefilter or final filter in ventilation and air
conditioning systems to separate fine dusts from
the air. The filter may be used in areas with poten-
tially explosive atmospheres, namely zones 1 and 2
as well as 21 and 22.

The filter must be connected to the earth. All con-
ductive and electrostatic dissipative parts must be
interconnected and connected to the earth.

Do not use the filter for conductive dusts. Make
sure that no metal particles can get into the filter.

ATEX labelling:

II 2G Ex h IIC Gb
II 2D Ex h IIIB Db

Conformity with directive

2014/34/EU

Equipment group (2014/34/EU)

II

Equipment category (2014/34/EU)

2

Hazardous areas (1999/92/EC)

Zones: 1, 2, 21, 22

Other procedural instructions and documents
related to areas with potentially explosive atmos-
pheres as defined in directive 1999/92/EC as well
as the industry-specific guidelines for use, handling,
maintenance and disposal of air filters for ventilation
and air conditioning systems SWKI 2003 and VDI
6022 also apply.

Airflow velocity and nominal volume flow rate

If the filter is used correctly and if the nominal
volume flow rate is maintained, the airflow velocity
on the filter will usually not exceed 2.69 m/s, not
even when the final differential pressure is reached.

Use test and monitoring systems, e.g. differential
pressure monitors or flow meters, to ensure that the
nominal volume flow rate is maintained.

Incorrect use

 WARNING!

Danger due to incorrect use!

Incorrect use of the filter can lead to dangerous
situations.

Use the filter only in the zones mentioned
above.

Use the filter only with the earth cable in
place.

Installation and mainte-
nance manual

GB/en

PFG-Ex

Explosion-proof pocket filter

TROX GmbH

Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Phone: +49 (0) 2845 2020
Fax: +49 (0) 2845 202265
E-mail: [email protected]
Internet: http://www.trox-
technik.com

A00000069495, 10/2022, 

©

 2022 TROX GmbH

 

PFG-Ex Explosion-proof pocket filter

1

Содержание PFG-E Series

Страница 1: ...ment group 2014 34 EU II Equipment category 2014 34 EU 2 Hazardous areas 1999 92 EC Zones 1 2 21 22 Other procedural instructions and documents related to areas with potentially explosive atmos pheres as defined in directive 1999 92 EC as well as the industry specific guidelines for use handling maintenance and disposal of air filters for ventilation and air conditioning systems SWKI 2003 and VDI ...

Страница 2: ... transport damage and complete ness Then put the product back into its packaging Supply package Filter PFG Ex Earth cable ATEX label Installation and maintenance manual Transport Do not remove the protective wrapping until just before installation Storage Please note Store the product only in its original packaging Protect the product from the effects of weather Protect the product from humidity d...

Страница 3: ...aged or incomplete filter Installation Personnel Properly trained person Protective equipment Industrial safety helmet Light respiratory protection Protective gloves Before you start changing filters switch off the ven tilation and air conditioning system if necessary purge the system with fresh air beforehand 1 Remove the existing filter and the earth cable 2 Then clean the system as required 3 I...

Страница 4: ...ion Make sure that the terminal connec tion cannot come loose Check the electrical resistance between the filter frame and the system component with an ohm meter The electrical resistance must not exceed 1 MΩ mega ohms 5 Finally affix the supplied ATEX sticker to the outside of the filter inspection access so that people can see it Filter change inserting filters PFG Ex Explosion proof pocket filt...

Страница 5: ...erential pressure has been reached if this is more economic Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacterial toxic or radioactive particles are considered hazardous waste and have to be disposed of by an authorised business in compliance with local reg...

Отзывы: