background image

ECQ

Electronically commutated motors for the drive 
of fans

Operating Instructions

L-BAL-F061-GB 2022/20 Index 005

Part.-No. 00702130-GB

english

Summary of Contents for ECQ

Page 1: ...ECQ Electronically commutated motors for the drive of fans Operating Instructions L BAL F061 GB 2022 20 Index 005 Part No 00702130 GB english ...

Page 2: ... Product overview 6 3 1 Application operational area 6 3 2 Functional description 6 3 3 Motor protection 6 3 4 Transport storage 7 3 5 Disposal recycling 7 4 Installation 7 4 1 Mounting the motor 7 4 2 Connection cable junction box 8 4 3 Connection of the motor 8 5 Commissioning 10 6 Service work 10 6 1 Maintenance servicing 10 6 2 Cleaning 11 7 Enclosure 11 7 1 Technical data 11 7 2 Manufacturer ...

Page 3: ...rating instructions apply to specific units only and are in no way valid for the complete system Use these operating instructions to work safely with and on the device They contain safety instructions that must be complied with as well as information that is required for failure free operation of the device Keep these operating instructions together with the device It must be ensured that all perso...

Page 4: ...e corresponding precautions are not taken Info Important additional information and advice for user 2 2 Product safety The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable The device and its accessories must only be used in a flawless condition and installed and operated in compliance with the assembly instructions and or operating instr...

Page 5: ...dden to carry out work on electrical live parts The 5 electrical safety rules must be observed The safe isolation from the supply must be checked using a two pole voltage detector Opening of motor is prohibited Loosening the screws will void the warranty Any faults detected in the electric system modules operating equipment must be corrected immediately If these faults are not corrected the device...

Page 6: ...rated controller They are designed exclusively for driving axial fans The motors are designed for continuous operation S1 operation and are thermally protected Depending on version motors with a fixed speed or motors with three speeds rating plate Motors with three speeds Three pre programmed speeds are possible rating plate which are activated depending on the connection of the additional control ...

Page 7: ...essary commission a specialist company with the waste disposal 4 Installation 4 1 Mounting the motor Attention Check the device for damage e g cracks dents or damage to the electric cables before assembly Start up is not allowed in the case of transport damage Mounting is only to be undertaken by trained service personnel The system manufacturer or the machine builder and or the user is responsibl...

Page 8: ...ater cannot penetrate through to the controller housing from the connection cables 4 3 Connection of the motor Danger due to electric current The mains voltage must comply with the EN 50160 quality characteristics and the defined standard voltages in IEC 60038 Connect the motor only to electrical circuits that can be disconnected with an all pole isolating switch The device owner is responsible for...

Page 9: ...3 rpm 2 Speed step 2 rpm 1 Speed step 1 If the black wire is connected with the brown wire the motor runs at speed step 3 If the black wire is connected with the blue wire the motor runs at speed step 2 If the black wire is not connected the motor runs at speed step 1 Danger due to electric current A dangerous voltage maximum line voltage is applied at the black connecting wire speed control input...

Page 10: ...ted the device system is potentially very dangerous The device system must therefore not be operated when it is faulty Fuses must always be only replaced never repaired or bridged The specifications for the maximum series fuse must always be adhered to see Technical data Only fuses cited in the electrical circuit diagram may be used The fan or motor is maintenance free due to the use of ball bearin...

Page 11: ...issible rel humidity 85 no condensation Electromagnetic compatibility for the standard voltage 230 400 V according to IEC 60038 Interference emission according to EN 55014 1 domestic household applications Interference immunity according to EN 61000 4 4 industrial applications Harmonics current In accordance with EN 61000 3 2 Please ask manufacturer for the individual harmonic oscillation levels o...

Page 12: ...Our products are manufactured in compliance with valid international standards and regulations If you have any questions about how to use our products or if you are planning special applications please contact ZIEHL ABEGG SE Heinz Ziehl Straße D 74653 Künzelsau Phone 07940 16 0 Fax 07940 16 300 info ziehl abegg de 7 3 Service address Please refer to the homepage at www ziehl abegg com for a list o...

Reviews: