WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.

Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

EN

NL

WARNING

WARNING

WARNING

WARNING

WARNING

LET OP

LET OP

LET OP

LET OP

LET OP

INSTALLATION GUIDE 

Please read this document very carefully to avoid battery monitor malfunction and/or fire hazards!

INSTALLATIE VOORSCHRIFT 

Bestudeer dit document uiterst zorgvuldig om schade aan de accumonitor en/of brandgevaar te voorkomen!

Mounting CDU + Shunt

Montage CDU + Shunt

The shunt must always be installed into the negative line!

Installing the shunt into the positive line may damage the battery monitor!

All fuses must be located as close as possible to the battery terminals.

All thick lines in the connection diagrams on the left, represent the main 

current lines. These lines must be wired with a wire type which can handle 

the full battery current!

The battery negative terminal may only contain one cable, which is the one 

going to the shunt. If there are other cables connected to this terminal as 

well, this may result in wrong readings on the display.

Always connect the battery negative terminal to the ‘BATTERY -’ stud of the 

shunt. Connecting this terminal to the ‘- SYSTEM’ stud, will result in wrong 

readings on the display.

De shunt moet altijd worden opgenomen in de minleiding. De accumonitor 

kan beschadigen wanneer de shunt in de plusleiding wordt opgenomen!

Alle zekeringen moeten zo dicht mogelijk bij de accupolen geplaatst worden.

Alle vet getekende lijnen in de aansluitschema’s aan de linkerzijde geven het 

hoofdstroom circuit aan. Deze lijnen dienen bedraad te worden met een kabel 

diameter welke geschikt is voor de maximale accu stroom.

De minpool van de accu mag maar één kabel bevatten, namelijk de kabel 

welke op de shunt moet worden aangesloten. Wanneer er ook nog andere 

kabels op de minpool aangesloten zijn, zal dit leiden tot foutieve waarden op 

het display.
Sluit de minpool van de accu altijd aan op de ‘BATTERY -’ bout van de shunt. 

Wanneer de minpool wordt aangesloten op de ‘- SYSTEM’ bout, zal dit leiden 

tot foutieve waarden op het display. 

status

B1

ALARM

(SUP)

B2

B3

QLINK

88mm

88mm

CDU

CDU

Rubber washer

Rubber pakking

Mounting panel

Montage paneel

Locking nut

Sluitmoer

Do not use mounting screws with 

countersunk heads.

Gebruik geen montage schroeven met 

verzonken kop.

36mm

OR

OF

Supply cable (included)

Voedingskabel (bijgesloten)

1)

Programmable alarm contact

1)

Programmeerbaar alarm contact

Additional  port

3)

for accessory control

Extra  poort

3)

voor accessoire besturing

2)

Temperature sensor input

2)

Temperatuur sensor ingang

Active shunt

Actieve shunt

Battery negative (system ground)

accu negatief (systeem min)

CDU Cable (included)

CDU Kabel (bijgesloten)

CDU (Control & Display Unit)

CDU (Bedienings- en display unit)

Battery positive (to load)

accu positief (naar belasting)

4)

12V, 24V or 48V

battery

4)

12V, 24V of 48V

accu

Main battery positive (to load)

Hoofd accu positief (naar belasting)

Battery negative (system ground)

accu negatief (systeem min)

12V, 24V or 48V

Main battery

12V, 24V of 48V

Hoofd accu

12V, 24V or 48V

Auxiliary battery 2

12V, 24V of 48V

‚Auxiliary’ accu 2

12V, 24V or 48V

Auxiliary battery 3

12V, 24V of 48V

‚Auxiliary’ accu 3

Aux battery 2 positive

‚Aux’ accu 2 positief

Aux battery 3 positive

‚Aux’ accu 3 positief

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

3 x M8 busbar

(TBS art# 5073160)

Connection diagram of single battery setup

Aansluitschema voor een opstelling met één accu

Connection diagram of a multi battery setup

Aansluitschema voor een opstelling met meerdere accu's

+B1 +B2 +B3

+B1

1A-5A fuse

1A-5A zekering

+

+

+

+

-

-

Installation warnings

Installatie waarschuwingen

EN

NL

!

Always disconnect the battery negative cable first before installation.

Ontkoppel altijd eerst de minleiding van de accu voor aanvang van de installatie.

!

Always connect the battery negative cable last when the installation has been completed.

Sluit de minleiding van de accu altijd als laatste aan wanneer de installatie voltooid is.

WARNING

LET OP

Make sure that the batteries you install are in good health and preferably 

fully charged.

Installeer alleen ‘gezonde’, bij voorkeur reeds volledig opgeladen accu's.

•  Wear proper, non-absorbent gloves, complete eye protection, and clothing

    protection. Avoid touching your eyes and wiping your forehead while working near

    batteries.

•  If battery acid contacts skin or clothing, wash immediately with soap and water. If

    acid enters your eye, immediately flood it with running cold water for at least 15

    minutes and get medical attention immediately.

•  Never smoke or allow a spark or flame near batteries.

•  Use extra caution to reduce the risk of dropping a metal tool on the battery. It could

    spark or short circuit the battery or other electrical parts and could cause an

    explosion.

•  Remove all personal metal items, like rings, bracelets, and watches when working

    with batteries. Batteries can produce a short circuit current high enough to weld

    metal to skin, causing a severe burn.

•  If you need to remove a battery, always remove the negative terminal from the

    battery first. Make sure all accessories are off so you don't cause an arc.

General battery precautions

Algemene accu waarschuwingen

EN

NL

•  Draag fatsoenlijke niet geleidende handschoenen, een veiligheidsbril en eventuele

    kleding protectie wanneer met accu’s gewerkt wordt. Voorkom het aanraken van de

    ogen en de huid met vervuilde handschoenen.

•  Wanneer accu zuur in aanraking komt met de huid of kleding, spoel deze onmiddelijk

    af met water en zeep. Wanneer dit zuur in uw ogen komt, spoel uw ogen dan

    minimaal 15 minuten met koud stromend water schoon en waarschuw een dokter

    voor verdere hulp.

•  Voorkom roken en open vuur of vonken in de buurt van accu’s.

•  Voorkom het risico van vallende metalen gereedschappen op de accupolen. Dit kan

    vonken en kortsluitingen veroorzaken, wat kan resulteren in gevaarlijke explosies.

•  Verwijder metalen sieraden zoals ringen, kettingen en horloges wanneer

    werkzaamheden worden verricht aan accu’s. Accu’s kunnen zeer hoge

    kortsluitstromen genereren welke tot ernstige brandwonden kunnen leiden.

•  Wanneer een accu verwijderd moet worden, de minleiding altijd als eerste

    loskoppelen. Zorg er voor dat alle accu verbruikers uitgeschakeld zijn, om vonken bij

    het loskoppelen te voorkomen.

Common battery configurations

Veel voorkomende accu configuraties

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

100Ah

12V

200Ah

24V

200Ah

48V

200Ah

TBS Expert Modular installation guide rev2endf

12V configuration

12V configuratie

24V configuration

24V configuratie

48V configuration

48V configuratie

5mm

Active shunt

Actieve shunt

Keep these cables

 as short as possible!

Houd deze kabels

zo kort mogelijk!

1)

 Normally open or normally closed potential free relay contact. Contact ratings 5A@30Vdc or 1A@70Vdc.

1)

 Normaal geopend of normaal gesloten potentiaalvrij relais contact. Contact specificaties 5A@30Vdc of 1A@70Vdc.

2)

 Battery temperature sensor is optional and should be attached to the main battery. Sensor kits are offered in lengths of 3m and 10m.

2)

 Accutemperatuursensor is optioneel en moet worden aangebracht op de hoofd accu. Sensor kits worden aangeboden in lengten van 3m 

   en 10m.

3)

 Besides accessories, the additional  port can also be used to connect to a second CDU.

3)

 Naast accessoires, kan de extra  poort ook gebruikt worden voor het aansluit en van een tweede CDU.

Placement of rubber covers

Plaatsing van rubber afdekkapjes

Please see the above illustration on how to cover unused ports of the active shunt 

module. A selection of rubber cover parts is included in the package.

Zie hierboven hoe ongebruikte aansluitingen op de actieve shunt afgedekt kunnen 

worden. Een selectie van rubber afdekkapjes is bijgesloten in de verpakking.

Both the active shunt and the rear side of the CDU must be located in a dry environment

De actieve shunt en de achterzijde van de CDU moeten zich in een droge omgeving bevinden

!

4)

 For more information on the midpoint voltage measurement capability for 24V and 48V battery banks, please see appendix 1 in the

   online owner’s manual available on our website www.whisperpower.com.

4)

 Voor meer informatie over ‚middelpunts’ spanningsmeting voor 24V en 48V accubanken, zie appendix 1 in de online gebruiksaanwijzing

   welke beschikbaar is op onze website www.whisperpower.com.

DCM Link Plate (50mm pitch)

(TBS art# 5079072)

Do not expose the CDU front panel to water and/or direct sunlight for a prolonged time

Stel het frontpaneel van de CDU niet langdurig bloot aan water en/of direct zonlicht

!

52 - 54mm

11 - 24mm

0.5 - 13mm

Nut | Moer

Spring washer | Veerring

Washer | Ring 

Cable lug | Krimpoog 

5)

 Assembly sequence of nut, washers and cable lug:

5)

 Assemblage volgorde voor moer, ringen en krimpoog:

5)

5)

battery monitor 

WBM Modular Smart Shunt

INSTALLATION MANUAL

WBM Modular Smart Shunt

  

Battery Monitoring