INSTALLATION INSTRUCTIONS

 

(800)  397-5777 (CANADA)    

SERIES NS4-MCW MULTI-CANDELA FOUR WIRE APPLIANCE

 

www.wheelockinc.com 

          

(WALL MOUNT VERSION)

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

GENERAL: 

Wheelock’s Series NS4-MCW Multi-Candela Horn Strobe provides four selectable candela settings (15, 30, 75, 110).  The NS4-
MCW allows for independent operation of the strobe circuit and the horn circuit.  It is the ideal choice for retrofit applications as well 
as new installations.  The NS4-MCW Appliance is UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired 
and UL Standard 464 for Audible Signal Appliances. The NS4-MCW is also ULC Listed under Standard CAN/ULC-S526-M87 for 
Visual Signaling Appliances and Standard CAN/ULC-S525-99 for Audible Signaling Appliances for Fire Alarm Systems.  It is listed 
for 

indoor use only

 and equipped with an NS Mounting Plate (NSMP) that can be mounted to single-gang, double-gang, 4” backbox, 

100mm European backbox or SHBB surface backbox (See Mounting Options). This strobe model is Listed for 

wall mounting only

.  

The NS-MCW Appliance uses a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan

 lens to provide maximum 

visibility and reliability for effective visible signaling. 

 

The horn portion of the NS4-MCW Appliance can be field set to provide either Continuous Horn or Code 3 Horn.  The sound output 
can be field set for High (HI) or Low (LO) dBA. 

 

The NS4-MCW Horn Strobe can also be used with a Sync Module (SM), Dual Sync Module (DSM) or Power Supply (PS-12/24-8) to 
provide synchronized strobe and synchronized Code 3 signal.   

 

This strobe model is designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage.  All 
inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP. 

NOTE

:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters 

WARNING:  THE NS HORN STROBE IS A "FIRE ALARM DEVICE - DO NOT PAINT." 

 

NOTE

:  All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems 

CAN/ULC

-S524-01 and Canadian Electrical Code, Part 1.  Final acceptance is subject to Authorities Having Jurisdiction. 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

 

Table 1:  Ratings Per UL and ULC 

 Regulated 

Strobe 

Settings Voltage 

Candela 

 (VDC/VRMS) 

Voltage Range Limit 

Per UL 1971 

(VDC/VRMS) 

Voltage Range Per 

CAN/ULC-S526-M87 

(VDC/VRMS) (cd) 

NS4-24MCW 24  16.0-33.0 

20.0-33.0 

15/30/75/110 

 

Table 2:  dBA Sound Output for 24VDC 

Description Volume  Reverberant 

Per UL 464 

Anechoic Per CAN/ULC-S525-99 

  

16.0VDC 

24.0VDC 

33.0VDC 20.0VDC 24.0VDC  31.0VDC 

 

Low 77 81 33 87 89  91 

Continuous 

Horn 

High 83 87 90 90 92  94 

 

Low 

  72* 

76 

79 

87 

89 

91 

Code 3 Horn 

High 

79 

82 

86 

90 

92 

94 

ULC Directional Characteristics:  Rated output 92dBA (Unit set on high volume and 24VDC) 

-3dBA:  60 degrees left, 40 degrees right 
-6dBA:  70 degrees left, 70 degrees right 

NOTES:  

1. The Strobe will produce 1 flash per second over the "Regulated Voltage" range.  2. Anechoic dBA is measured on axis in 

a non-reflective (free field) test room using fast meter response.  For peak dBA (measured with peak meter response), add 5dBA to 
anechoic values as shown in Table 2.  Reverberant dBA is a minimum UL rating based on sound pressure measurements in a 
reverberant test room.  3. This model is UL Listed for indoor use with a temperature range of +32oF to +120oF (0oC to +49oC) and 
maximum humidity of 93% RH 

±

 2%. 

 

NOTE:  THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  THE MAXIMUM NUMBER 
OR STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47. 

 

Copyright 2001 Wheelock, Inc.  All rights reserved. 

Summary of Contents for NS4-24MCW

Page 1: ...on of circuit wiring by a FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING THE NS HORN STROBE IS A FIRE ALARM DEVICE DO NOT PAINT NOTE All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is...

Page 2: ...30 1 210 The time duration for the peak current is 1 millisecond NOTE Inrush current is less than rated peak current Table 3A UL ULC Horn Current Ratings AMPS UL Voltage ULC Voltage High dBA Low dBA 16 0VDC 20 0VDC 0 019 0 012 24 0VDC 24 0VDC 0 028 0 015 33 0VDC 31 0VDC 0 039 0 018 16 0VRMS 20 0VRMS 0 029 0 016 24 0VRMS 24 0VRMS 0 044 0 019 33 0VRMS 31 0VRMS 0 061 0 022 WARNING MAKE SURE THAT THE ...

Page 3: ... 8 4 7 5 9 18 8 22 27 5 31 90 3 8 8 7 5 15 18 8 38 27 5 48 Table 4A Vertical Plane UL 1971 Vertical 15cd 30cd 75cd 110cd Angle in deg UL Min Typ 15cd UL Min Typ 30cd UL Min Typ 75cd UL Min Typ 110cd 0 15 0 23 30 0 49 75 0 116 110 0 155 5 13 5 26 27 0 51 67 5 123 99 0 166 10 13 5 21 27 0 42 67 5 105 99 0 139 15 13 5 19 27 0 39 67 5 95 99 0 134 20 13 5 19 27 0 36 67 5 82 99 0 116 25 13 5 17 27 0 34 ...

Page 4: ...t specified by ANSI NFPA for standard emergency evacuation signaling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose Figure 1 Showing Location of Jumper Plug and Candela Selector JUMPER PLUGS CANDELA SELECTOR TOP PLUG NO PLUG HI LOW CODE 3 HORN STB AUD WARNING TO PREVENT ELECTRIC SHOCK DO NOT REMOVE THIS COVER NO USER SERVICEABLE PARTS INSIDE 15 75 1...

Page 5: ...DULE When the sync module is used the audible tone will be Code 3 sound only Refer to Sync Module Installation Instruction sheets SM P83123 DSM P83177 or PS 12 24 8 P83862 for additional information Audible will operate only with power applied to both strobe and audible Figure 8 1 The NS4 MCW Appliance has in out wiring terminals that accepts two 12 to 18 American Wire Gauge AWG wires at each scre...

Page 6: ...tress on the product from wiring C A B D FLUSH MOUNTING STD SINGLE GANG BACKBOX 6 32 X 7 8 SCREWS NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPLIED MAXIMUM NUMBER OF CONDUCTORS BACKBOX DEPTH AWG 18 AWG 16 AWG 14 AWG 12 2 1 2 8 4 4 4 3 1 8 8 8 8 8 MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 8 8 8 8 NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPL...

Page 7: ... for each mounting option is supplied 7 Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product 8 When terminating field wires do not use more lead length than required Excess lead length could result in insufficient wiring space for the signaling appliance 9 Use care and proper techniques to position the field wires in the backbox so th...

Page 8: ...idelines or restrictions on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 of t...

Page 9: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Reviews: