background image

Controller

User manual

URDR001A

Summary of Contents for URDR001A

Page 1: ...Controller User manual URDR001A ...

Page 2: ...2 URDR001A User manual ...

Page 3: ...s Led 11 6 2 Keys 12 7 Controller Functions 12 7 1 Modification of main and alarm setpoint value 12 7 2 Automatic Tune 12 7 3 Manual Tune 12 7 4 Tuning once 13 7 5 Synchronized tuning 13 7 6 Digital input functions 14 7 7 Automatic Manual regulation for output control 14 7 8 Heater Break Alarm on CT Current Transformer 15 7 9 Dual Action Heating Cooling 15 7 10 LATCH ON Function 16 7 11 Soft Start...

Page 4: ...ld alarm referred to command setpoint active over par 123 AL 1 F Ab c u A 52 13 d Absolute or threshold alarm referred to command setpoint active below par 123 AL 1 F Ab c L A 52 13 e Band alarm par 123 AL 1 F band 52 13 f Asymmetric band alarm par 123 AL 1 F A band 52 13 g Upper deviation alarm par 123 AL 1 F up dev 53 13 h Lower deviation alarm par 123 AL 1 F Lo dev 53 13 1 Alarms label 53 14 Fa...

Page 5: ...ems Only qualified personnel should be allowed to use device and or service it and only in accordance to technical data listed in this manual Do not dismantle modify repair any internal component Device must be installed and can operate only within the allowed environmental conditions Overheating may lead to risk of fire and can shorten the lifecycle of electronic components 1 1 Organization of sa...

Page 6: ...k the voltage or current and attach the noise filter as close as possible to the Digital Controller Allow as much space as possible between the Digital Controller and devices that generate powerful high frequencies high frequency welders high frequency sewing machines etc or surge A switch or circuit breaker must be provided close to device The switch or circuit breaker must be within easy reach o...

Page 7: ... from 25 85 C Thermoresistances PT100 PT500 PT1000 Ni100 PTC 1K NTC 10K β 3435K Input V mA 0 1 V 0 5 V 0 10 V 0 20 o 4 20 mA 0 60 mV Pot Input 1 150 KΩ CT 50 mA Tolerance 25 C 0 2 1 digit on F s for thermocou ple thermoresistance and V mA Cold junction accuracy 0 1 C C Impedence 0 10 V Ri 110 KΩ 0 20 mA Ri 5 Ω 0 40 mV Ri 1 MΩ Relay outputs Config as command and alarm output Contacts Q1 5 A 250 VAC...

Page 8: ...gs This controller has been designed and manufactured in conformity to Low Voltage Directive 2006 95 EC 2014 35 EU LVD and EMC Directive 2004 108 EC 2014 30 EU EMC For installation in industrial environments please observe following safety guidelines Separate control line from power wires Avoid proximity of remote control switches electromagnetic contactors powerful engines Avoid proximity of powe...

Page 9: ... one side only AI1 PT NI100 Shield Schermo Rosso Red Bianco White Rosso Red 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire connection short circuit terminals 13 and 15 When shielded cable is used it should be grounded at one side only RED ROSSO RED ROSSO WHITE BIANCO AI1 Shield Schermo PTC NTC 15 14 For thermoresistances NT...

Page 10: ...n It is recommended to use the twisted and shielded cable for communica tions 5 1 f Digital output 0V DO1 PNP 9 10 Digital output PNP including SSR for command or alarm Range 12 VDC 25 mA or 24 VDC 15mA selectable by parameter 282 v out 5 1 g Analogue output AO1 AO1 V mA 12 11 Linear output in mA or V galvanically isolated configurable as command alarm or retransmission of process setpoint The sel...

Page 11: ...meter value being inserted 6 1 Meaning of Status Lights Led 3 C1 ON when the command output 1 is active In versions with single analog input it is ON when the valve is opening In the versions with two analog inputs in case of command 1 on the motorized valve it is permanently ON when the valve is opening and flashing during the closing phase 4 C2 ON when the command output 2 is active In versions ...

Page 12: ...matic tuning procedure allows a precise regulation without delving into the PID regulation algorithm Selecting Auto on par 73 tun 1 for the regulation loop 1 or on par 98 tun 2 for the regulation loop 2 the controller analyzes the proces oscillations and optimizes the PID parameters Led TUN flashes If the PID parameters are not yet selected at the device switch on it is automatically launched the ...

Page 13: ...w PID values When the procedure ends the controller switches off the command output and selects the value 4 on word 1216 The master who will always read the word 1216 will control the various zones and when all will have finished will bring to 0 the value of word 1216 the various devices will regulate the temperature independently with the new calculated values N B The master must read the word 12...

Page 14: ...tion down k simulate button operation fnc k simulate button FNC operation set k simulate button SET operation EXT AL External Alarm The controller goes to STOP and the alarms are disabled To return to START condition one of following events is required switching off and on the controller activation of the digital input if the relative parameter is st St by pressure SET button if par 286 s k s f se...

Page 15: ... f AL 5 f has to be configured as cooL The command output must be connected to the actuator responsible for heating while the alarm will control cooling action Parameters to be configured for the heating PID are ac t 1 HeatCommand output action type Heating P b 1 Heating proportional band i t 1 Integral time of heating and cooling d t 1 Derivative time of heating and cooling c t 1 Heating time cyc...

Page 16: ...end par 5 u L i 1 to the maximum position of the sensor par 10 Ltc 1configured as stndr It is also possible to fix the point in which the controller will display 0 however keeping the scale range between L L i 1and u L i 1using the virtual zero option by selectin u 0 sto or u 0 t on on par 10 Ltc 1 Selecting u 0 t on the virtual zero must be reset at each switching on selecting u 0 sto the virtual...

Page 17: ...vated 7 12 Pre Programmed cycle Pre programmed cycle function activates by setting Enab on parameter 263 pr cY Controller reaches setpoint 1 basing on the gradient set on parameter 266 SS Gr then it reaches max power up to setpoint 2 When the process reaches max power this setpoint is maintained for the time set on parameter 270 ma t i At expiry process will reach ambient temperature according to ...

Page 18: ...n a timer ends another starts the sequence repeats itself cyclically To change the duration of the counting time follow the steps below Press Display Do 1 SET Press until timE 1or time 2visualized on display 1 2 Digits on display 1 changes Increase or decrease time value for the selected timer To start the keyboard count follow the steps below Press Display Do 1 FNC Press until time 1or time 2visu...

Page 19: ...ints are saved with a delay of 10 seconds after the last modification Changes made to words that are different from those reported in the following table can lead to malfunction ModbusRTUprotocolfeatures Baud rate Selectable on parameter 319 bd rt 1200bit s 28800bit s 2400bit s 38400bit s 4800bit s 57600bit s 9600bit s 115200bit s 19200bit s Format Selectable on parameter 320 s p p 8N1 8N2 8E1 8E2...

Page 20: ...t3 Alarm 4 Bit1 Alarm 2 Bit4 Alarm 5 Bit2 Alarm 3 Bit5 Alarm 6 RO 0 1009 Error flags 1 Bit0 AI1 process error sensor 1 Bit1 Reserved Bit2 Cold junction error Bit3 Safety error Bit4 Generic error Bit5 Hardware error Bit6 Error H B A partial rupture of the load Bit7 Error H B A SSR in short circuit Bit8 Overcurrent error Bit9 Parameters out of range error Bit10 CPU eeprom writing error Bit11 RFid ee...

Page 21: ...p 1 degrees with tenth R W EEPROM 1203 Setpoint 4 of regulation loop 1 degrees with tenth R W EEPROM 1208 Alarm 1 setpoint degrees with tenth Alarm 1 upper setpoint if Par 123 AL 1 F A band R W EEPROM 1209 Alarm 2 setpoint degrees with tenth Alarm 2 upper setpoint if Par 141 AL 2 F A band R W EEPROM 1210 Alarm 3 setpoint degrees with tenth Alarm 3 upper setpoint if Par 159 AL 3 F A band R W EEPROM...

Page 22: ...1 tare 2 reset tare R W 0 1249 Value of remote setpoint by command 1 serial R W 0 1251 Alarm 1 lower setpoint if Par 123 AL 1 F A band degrees with tenth R W EEPROM 1252 Alarm 2 lower setpoint if Par 141 AL 2 F A band degrees with tenth R W EEPROM 1253 Alarm 3 lower setpoint if Par 159 AL 3 F A band degrees with tenth R W EEPROM 1254 Alarm 4 lower setpoint if 177 AL 4 F A band degrees with tenth R...

Page 23: ...lityregisters R W Reset value 0 Device type RO EEPROM 1 Software version RO EEPROM 5 Slave address RO EEPROM 6 Boot version RO EEPROM 50 Automatic addressing WO 51 System code comparison WO 500 Loading default values write 9999 R W 0 510 Setpoints storing time in eeprom 0 60 s R W 10 999 Process subjected to the visualization filter RO 1000 Process degrees tenths for temperature sensors digits for...

Page 24: ... tun 1 SYncH 0 autotuning function OFF 1 command output OFF forced cooling 2 command output ON forced heating 3 autotuning ON 4 autotuning finished R W 0 1026 Zero tare AI1 1 tare 2 reset tare R W 0 1099 Process subjected to the visualization filter and decimal point selection RO 0 1100 Process with decimal point selection RO 0 1101 Setpoint 1 with decimal point selection R W EEPROM 1102 Setpoint ...

Page 25: ...odel identifi cation and the reading of the parameters The graphic interface shows the advancement and switches to the second tab DATA It is now possible to move the smartphone away from the controller to make the required modifications more easily The device parameters are divided into collapsible groups and are displayed with name current value and reference index to the manual Click on a row to...

Page 26: ...ET when viewing Memoskip the product starts without uploading any data from the memory card 10 Loading default values This procedure allows to restore factory settings of the device Press Display Do 1 FNC for 3 sec Display 1 shows PASS while display 2 shows 0000with the 1st digit flashing 2 c or d Modify the flashing digit and move to the next one pressing SET Enter password 9999 3 FNC to confirm ...

Page 27: ...tion Set the product parameters so that they are suitable for the system to be controlled If they are not suitable unexpected operations may occasionally cause materials damage or accidents 12 Table of configuration parameters GROUP A A in 1 Analogue input 1 1 SEN 1 Sensor AI1 Analogue input configuration sensor AI1 selection tc k Tc K 260 C 1360 C Default tc s Tc S 40 C 1760 C tc r Tc R 40 C 1760...

Page 28: ...p 54 degrees tenths for temperature sensors Default 0 9 G ca 1 Gain Calibration AI1 Value multiplied to the process value to calibrate the working point Ex to correct the range from 0 1000 C showing 0 1010 C set the parameter to 1 0 100 0 100 0 Default 0 0 10 Ltc 1 Latch On AI1 Automatic setting of limits for AI1 linear input diSab Disabled Default Stnrd Standard v 0 sto Virtual Zero Stored v 0 t ...

Page 29: ...from 5 to 10V 4 20 S R Command 4 20 mA on analogue output AO1 with split range function the analogue output sets the cooling action from 4 to 12mA and heating action from 12 to 20mA c VAL c Servo valve command with open loop on Q2 and Q3 relays Command AL 1 AL 2 AL 3 AL 4 AL 5 c o2 Q2 Q1 Q3 DO1 DO2 AO1 c o1 Q1 Q2 Q3 DO1 DO2 AO1 c SSr DO1 Q1 Q2 Q3 DO2 AO1 c vAL Q1 open Q2 close Q3 DO1 DO2 AO1 c 0 1...

Page 30: ...s relay or valve open Contact or valve open Default CLose Contact or valve closed If the command output 1 is digital output SSR off Digital output OFF Default on Digital output ON If the command output 1 is 0 10V 0 V 0 V Default 10 v 10 V If the command output 1 is 0 20 mA or 4 20 mA 0 ma 0 mA Default 4 ma 4 mA 20 ma 20 mA 21 5ma 21 5 mA 44 c Ld 1 Command Led 1 Defines led C1 state corresponding t...

Page 31: ...iN is selected on parameter 46 c S p 1 Command Setpoint Protection 1 9999 30000 digit1 p 54 degreesfor temp sensors Default 0 52 53 Reserved Parameters Group C Reserved parameters Group C GROUP D res Reserved 54 72 Reserved Parameters Group D Reserved parameters Group D GROUP E reG 1 Autotuning and PID 1 73 tun 1 Tune 1 Selects autotuning type for command 1 diSab Disabled If proportional band and ...

Page 32: ...hreshold 1 Selects deviation from command setpoint 1 to calculate the intervention threshold of Off Over Setpoint 1 function 9999 9999 digit1 p 54 degrees tenths for temp sensors Default 0 82 c t 1 Cycle Time 1 Cycle time for P I D regulation of process 1 for P I D on remote control switch 15 s for PID on SSR 2s For valve refer to parameter 47 va t 1 1 300 seconds Default 15 s 83 co F 1 Cooling Fl...

Page 33: ...Proportional Band 1 Selects the max proportional band 1 value selectable by the automatic tune for the P I D regulation of process 1 0 10000 digit1 p 54 degrees tenths for temp sensors Default 80 0 92 mn i 1 Minimum Integral Time 1 Selects the min integral time 1 value selectable by the automatic tune for the P I D regulation of process 1 0 0 1000 0 seconds Default 30 0 s 93 o c L 1 Overshoot Cont...

Page 34: ...And Asymmetric band alarm command setpoint alarm setpoint 1 H and command setpoint alarm setpoint 1 L c aux Auxiliary for job distribution on the command output It cyclically replaces the command output for the time set on the parameter 134 A 1 de Se A 1 de 0 it is activated parallel to the command output It does not work in case of valve control and can only be activated on an alarm if A 1 de is ...

Page 35: ...Open contact Default CLose Closed contact 133 A 1 Ld Alarm 1 Led Defines the status of the led A1 in correspondence of the relevant output o c ON with open contact or DO switched off c c ON with closed contact or DO switched on Default 134 a 1 de Alarm 1 Delay Alarm 1 Delay 60 00 60 00 mm ss hh mm if AL 1 F c aux Default 00 00 Negative value delay when exit alarm status Positive value delay when e...

Page 36: ...And Asymmetric band alarm command setpoint alarm setpoint 2 H and command setpoint alarm setpoint 2 L c aux Auxiliary for job distribution on the command output It cyclically replaces the command output for the time set on the parameter 152 A 2 de If A 2 de 0 it is activated parallel to the command output It does not work in case of valve control and can only be activated on an alarm if A 2 de is ...

Page 37: ...ntact or closed valve If the alarm output is digital SSR off Digital output OFF Default on Digital output ON 151 A 2 Ld Alarm 2 Led Defines the status of the led A2 in correspondence of the relevant output o c ON with open contact or DO switched off c c ON with closed contact or DO switched on Default 152 a 2 de Alarm 2 Delay Alarm 2 Delay 60 00 60 00 mm ss hh mm if AL 2 F c aux Default 00 00 Nega...

Page 38: ...rrent Alarm a bAnd Asymmetric band alarm command setpoint alarm setpoint 3 H and command setpoint alarm setpoint 3 L c aux Auxiliary for job distribution on the command output It cyclically replaces the command output for the time set on the parameter 170 A 3 de If A 3 de 0 it is activated parallel to the command output It does not work in case of valve control and can only be activated on an alar...

Page 39: ...ppear 168 A 3 S e Alarm 3 State Error Alarm 3 output status in case of error If the alarm output is relay open Contact or open valve Default CLose Contact or closed valve If the alarm output is digital SSR off Digital output OFF Default on Digital output ON If the alarm output is 0 10V 0 V 0 V Default 10 v 10 V If the alarm output is 0 20 mA or 4 20 mA 0 ma 0 mA Default 4 ma 4 mA 20 ma 20 mA 21 5m...

Page 40: ...upture tMr 1 Related to timer 1 tMr 2 Related to timer 2 tMr 1 2 Related to both timers rEM Remote The alarm is enabled by the word 1238 d i 1 Digital Input 1 Active when digital input 1 is active d i 2 Digital Input 2 Active when digital input 2 is active H b A Heater Break Alarm and Overcurrent Alarm a bAnd Asymmetric band alarm command setpoint alarm setpoint 4 H and command setpoint alarm setp...

Page 41: ... output status also after a power failure A rEs t Automatic reset with timed activation The alarm remains active for the time set on the parameter 188 a 4 de even if the conditions generating it are missing To be able to act again the alarm conditions must disappear 186 A 4 S e Alarm 4 State Error Alarm 4 output status in case of error If the alarm output is digital SSR off Digital output OFF Defa...

Page 42: ...e in case of sensor rupture tMr 1 Related to timer 1 tMr 2 Related to timer 2 tMr 1 2 Related to both timers rEM Remote The alarm is enabled by the word 1239 d i 1 Digital Input 1 Active when digital input 1 is active d i 2 Digital Input 2 Active when digital input 2 is active H b A Heater Break Alarm and Overcurrent Alarm a bAnd Asymmetric band alarm command setpoint alarm setpoint 5 H and comman...

Page 43: ...e output status also after a power failure A rEs t Automatic reset with timed activation The alarm remains active for the time set on the parameter 206 a 5 de even if the conditions generating it are missing To be able to act again the alarm conditions must disappear 204 A 5 S e Alarm 5 State Error Alarm 5 output status in case of error If the alarm output is digital SSR off Digital output OFF Def...

Page 44: ...e otherwise heating reg A i 0 Analogue Input 0 Set AI to zero M reS Manual reset Reset the outputs if selected as manual reset t 1 run Timer 1 run The timer 1 count with activated D I t 1 s E Timer 1 Start End D I starts and stops the timer 1 impulsive t 1 Sta Timer 1 Start D I starts the timer 1 impulsive t 1 End Timer 1 End D I stops the timer 1 impulsive t 2 run Timer 2 run The timer 2 count wi...

Page 45: ...1 impulsive t 1 End Timer 1 End D I stops the timer 1 impulsive t 2 run Timer 2 run The timer 2 count with activated D I t 2 s E Timer 2 Start End D I starts and stops the timer 2 impulsive t 2 Sta Timer 2 Start D I starts the timer 2 impulsive t 2 End Timer 2 End D I stops the timer 2 impulsive Lo cfG Lock configuration and setpoints up key Simulates the functioning of up key down k Simulates the...

Page 46: ...ction is activated at starting 9999 30000 digit1 p 54 degrees tenths for temp sensors Default 1000 269 SS ti Soft Start Time Max Softstart duration if the processs will not reach the threshold selected on par SS tH within the selected time the controller starts to regulate on setpoint 00 00 Disabled 00 01 24 00 hh mm Default 00 15 270 MA ti Maintenance Time Maintenance time for pre programmed cycl...

Page 47: ...ault dsp 1 2 Display 1 and 2 d 1 2 Ld Display 1 2 and led 281 u M P c User Menu Pre Programmed Cycle Allows to modify rising falling gradient and rentention time form the user menu in pre pro grammed cycle functioning To access parameter modification press SET disab Disabled Default ris Gr Only rising gradient ma ti Only retention time ri G m t Rising gradient and retention time faL Gr Only fallin...

Page 48: ...witch The controller changes the regulation setpoint alternating between Set1 Set2 and Set3 4t swi 4 Threshold Command Setpoint Switch The controller changes the regulation setpoint alternating between Set1 Set2 Set3 and Set4 A i 0 Analogue Input 0 Set analogue input to zero zero tare GROUP S ct Current Transformer 287 ct F Current Transformer Function Enables the C T input and selects the net fre...

Page 49: ...grees if temperature Default 0 301 r 1 u L Retransmission 1 Upper Limit Retransmission 1 upper limit range 2 value related to 10 V or 20 mA 9999 30000 digit1 p 54 degrees if temperature Default 1000 302 r 1 s e Retransmission 1 State Error Determines retransmission 1 value in case of error or anomaly If the retransmission output is 0 10V 0 V 0 V Default 10 v 10 V If the retransmission output is 0 ...

Page 50: ...es off the command output 0 Offline disabled Default 0 1 600 0 tenths of second 323 327 Reserved Parameters Group V Reserved parameters Group V GROUP W timr Timer 328 tmr 1 Timer 1 Enabling Timer 1 diSab Disabled Default Enab Enabled En StA Enabled and active at start 329 t b t 1 Time Base Timer 1 Selects time base for timer 1 mm SS minutes seconds Default hh MM hours minutes 330 a tm 1 Action Tim...

Page 51: ... Alarm Intervention Modes 13 a Absolute or threshold alarm active over par 123 AL 1 F Ab uP A Time Hysteresis parameter 0 Alarm output OFF OFF ON ON Alarm Spv Pv Absolute alarm active over Hysteresis value greater than 0 Par 128 a 1 HY 0 Time Hysteresis parameter 0 Alarm output OFF OFF ON ON Alarm Spv Pv Absolute alarm active over Hysteresis value lower than 0 Par 128 a 1 HY 0 13 b Absolute or thr...

Page 52: ...F band Command Spv Time Hysteresis parameter 0 Hysteresis parameter 0 Pv Alarm Spv Alarm Spv Alarm output ON OFF OFF OFF ON ON Band alarm hysteresis value greater than 0 Par 128 a 1 HY 0 Command Spv Time Hysteresis parameter 0 Pv Alarm Spv Alarm Spv Alarm output ON OFF OFF OFF ON ON Hysteresis parameter 0 Band alarm hysteresis value lower than 0 Par 128 a 1 HY 0 13 f Asymmetric band alarm par 123 ...

Page 53: ...HY 0 NB with hysteresis value less than 0 A 1 HY 0 the dotted line moves under the alarm setpoint Command Spv Time Hysteresis parameter 0 Pv Alarm Spv Alarm output OFF OFF ON ON Lower deviation alarm value of alarm setpoint less than 0 and hysteresis value greater than 0 Par 128 A 1 HY 0 NB with hysteresis value less than 0 A 1 HY 0 the dotted line moves under the alarm setpoint 13 1 Alarms label ...

Page 54: ...d to AI1 broken or temperature out of range Control connection with probes and their integrity E 06 PRobe 2 Error Sensor connected to AI2 broken or temperature out of range Control connection with probes and their integrity E 08 SYSTEM Error Missing calibration Call assistance E 80 rfid Error Tag rfid malfunctioning Call assistance Notes Updates 1 Display of decimal point depends on setting of par...

Page 55: ...1 37 rEs Reserved 31 38 Ac t 1 Action type 1 31 39 c HY 1 Command Hysteresis 1 31 40 L L S 1 Lower Limit Setpoint 1 32 41 U L S 1 Upper Limit Setpoint 1 32 42 c re 1 Command Reset 1 32 43 c S e 1 Command State Error 1 32 44 c Ld 1 Command Led 1 32 45 c de 1 Command Delay 1 32 46 c S p 1 Command Setpoint Protection 1 32 47 vA t 1 Valve Time 1 33 48 a ma 1 Automatic Manual 1 33 49 ini S Initial Stat...

Page 56: ...y Alarm 1 Hysteresis 36 129 A 1 L L Alarm 1 Lower Limit 36 130 A 1 u L Alarm 1 Upper Limit 37 131 a 1 re Alarm 1 Reset 37 132 A 1 S e Alarm 1 State Error 37 133 A 1 Ld Alarm 1 Led 37 134 a 1 de Alarm 1 Delay 37 135 A 1 S p Alarm 1 Setpoint Protection 37 136 A 1 Lb Alarm 1 Label 37 137 140 Reserved Parameters Group G 37 GROUP H AL 2 Alarm 2 141 AL 2 f Alarm 2 Function 38 142 143 Reserved Parameters...

Page 57: ...te Error 43 187 rES Reserved 43 188 a 4 de Alarm 4 Delay 43 189 A 4 S p Alarm 4 Setpoint Protection 43 190 A 4 Lb Alarm 4 Label 44 191 194 Reserved Parameters Group J 44 GROUP K AL 5 Allarme 5 solo su URDR001A 13ABC e URDR001A 23XX T 195 AL 5 f Alarm 5 Function 44 196 rEs Reserved 44 197 rEs Reserved 44 198 A 5 5 o Alarm 5 State Output 44 199 A 5 o t Alarm 5 Output Type 45 200 a 5 Hy Alarm 5 Hyste...

Page 58: ...ilter 49 278 vi d 2 Visualization Display 2 49 279 tMo d Timeout Display 49 280 tMo S Timeout Selection 49 281 u M P c User Menu Pre Programmed Cycle 49 282 v out Voltage Output 49 283 ScL t Scrolling Time 49 284 d SP F Display Special Functions 50 285 nFc L NFC Lock 50 286 s k s f Set Key Special Functions 50 GROUP S ct Current Transformer 287 ct F Current Transformer Function 50 288 ct v Current...

Page 59: ...se de Serial Delay 52 322 off L Off Line 52 323 327 Reserved Parameters Group V 52 GROUP W timr Timer 328 tmr 1 Timer 1 52 329 t b t 1 Time Base Timer 1 52 330 a tm 1 Action Timer 1 52 331 tmr 2 Timer 2 52 332 t b t 2 Time Base Timer 2 52 333 a tm 2 Action Timer 2 53 334 tMr s Timers Sequence 53 335 339 Reserved Parameters Group W 53 ...

Page 60: ...ie hier enthaltenen Informationen bezüglich Sicherheit und Einstellung aufmerksam zu lesen Avant d utiliser le dispositif lire avec attention les renseignements de sûreté et installation contenus dans ce manuel 2300 10 304 RevE 120723 Proc Cont Eq E469441 Wachendorff Prozesstechnik GmbH Co KG Industriestrasse 7 65366 Geisenheim Tel 49 0 67 22 99 65 20 Fax 49 0 67 22 99 65 78 E Mail wp wachendorff ...

Reviews: