manualshive.com logo in svg
background image

INSTALLATION

MANUAL

Applicable Models

SOMERA VSMD.72.AAA.05

 [AAA= 340 - 350] 

ELDORA VSPG.72.AAA.05

 [AAA= 320 - 330] 

SOMERA

 

VSMG.72.AAA.05

 [AAA= 355 - 365] 

SOMERA VSMD.60.AAA.05

 [AAA= 280 -290] 

ELDORA VSPG.60.AAA.05

 [AAA= 265 - 275] 

SOMERA VSMG.60.AAA.05

[AAA= 295 - 305] 

Содержание ELDORA VSPG.60 Series

Страница 1: ...Applicable Models SOMERA VSMD 72 AAA 05 AAA 340 350 ELDORA VSPG 72 AAA 05 AAA 320 330 SOMERA VSMG 72 AAA 05 AAA 355 365 SOMERA VSMD 60 AAA 05 AAA 280 290 ELDORA VSPG 60 AAA 05 AAA 265 275 SOMERA VSMG 60 AAA 05 AAA 295 305 ...

Страница 2: ...ON 4 04 INSTALLATION ENVIRONMENT 4 04 1 CLIMATE CONDITIONS 4 05 SITE SELECTION 4 06 MOUNTING INSTRUCTIONS 5 06 1 MOUNTING METHODS 5 MOUNTING WITH CLAMPS 6 GROUNDING 7 Module Wiring 7 07 ELECTRICAL CONFIGURATION 8 07 1 FUSING 9 07 2 ELECTRICAL PARAMETERS 9 07 3 INVERTER SELECTION AND COMPATIBILITY 10 08 MAINTENANCE AND CARE 10 09 END OF LIFE PRODUCT RECYCLING 11 10 WARNING 11 11 CONTACT DETAILS 11 ...

Страница 3: ...he module The front back surface of the module constructed with tempered heat strength Float glass and hence it should be handled with utmost care If the glass breaks then human contact with the surface can lead to electric shock particularly when the ambient condition is wet Broken modules cannot be repaired and it should be disposed of properly All electrical connectors should be well protected ...

Страница 4: ...cessary steps have been taken to mitigate the risk At receipt of PV modules verify the product details as it had been ordered Packing list pasted outside the box contains all details including the serial no of modules Do NOT stack packing boxes pallets more than 2 boxes high If pallets are stored temporarily outside then the external protective cover to be placed and stack height should not be mor...

Страница 5: ...e mounting methods and failure to follow the instructions of this manual may result in different capabilities to withstand snow and wind loads The system installer should ensure that installation methods used meet these requirements and any local codes and regulations PV modules should be installed in a place where there is no shading across the location throughout the year Shading can be minimize...

Страница 6: ...nd dust penetrating into the connector According to UL 1703 any other specific clearance required for maintaining a system fire rating should prevail Detailed clearance requirements pertaining to system fire ratings must be provided by your racking supplier Ground reflectance Albedo and Mounting structure height has an impact on energy yield of Bifacial modules Higher power output can be realised ...

Страница 7: ...ads additional clamps may be required to ensure that modules can bear the load Fig 2 Mounting with clamps Vikram Solar Limited warranty may be void in cases where improper clamps or unsuitable installation methods are found When installing clamps take measures so as Not to bend the glass excessively Not to cast shadow on the cells Not to damage or scratch the surface of the glass To ensure the cla...

Страница 8: ...V modules Mounting rails run perpendicular to the long side frame Clamp length 200 mm A 330 20 mm B 650 20 mm Maximum Load Uplift load 1600 Pa Downforce load 1600 Pa SERIES CONNECTION PARALLEL CONNECTION All wiring should be performed by qualified installers in accordance with the local codes and regulations 06 3 MODULE WIRING 07 ...

Страница 9: ...gs can be connected in parallel without using over current protection device fuses etc incorporated in series within each string Three of more strings can be connected in parallel if an appropriate and certified over current protection device is installed in series with each string The maximum voltage of the system should be lesser than the certified system voltage typically 1500V or the maximum i...

Страница 10: ...odel Maximum System Voltage 1500V Maximum Series Fuse 20A 20 Bifacial gain Fire Rating Class Fire Rating Class C Fire Rating Type 1 Dimensions 1975mm 992mm 6mm Weight 27 kg Bypass Diodes 3 Bypass Diodes Typically modules consists of bypass diodes like PST4530 T Peak Inverse voltage 45 V Forward Current 30 A diodes in the junction box Rated electrical characteristics are within 10 of measured value...

Страница 11: ...re no part of the light falling area of the module is shaded any leaves trees or any object which causes shading has to be removed accordingly Ensure all the cable assembly is tight and no part of cable assembly will be exposed to water logging Check that the string fuses in each non earthed pole are in operation Do not open the junction box to change the diodes even if they are defective Please c...

Страница 12: ...erature to the modules being cleaned Use dry or wet soft clean cloth to clean the PV modules non corrosive solvents or hard objects are strictly prohibited do not scrape or rub dry dirt away as this may cause micro scratches Snow should be removed using a soft brush If there are greasy dirt and other substances on the surface of the PV module which are difficult to clean conventional household gla...

Страница 13: ... 9 12 ...

Страница 14: ... 13 ...

Страница 15: ... 10 11 12 14 ...

Отзывы: