background image

1. PRODUCT NAME

Viking Micromatic

®

Special Response

Sprinklers

Available Styles: Upright, Pendent,
and Conventional

2. MANUFACTURER

THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058, U.S.A.
Telephone:

(269) 945-9501

(877) 384-5464

Fax:

(269) 945-9599

e-mail: [email protected]

VIKING S.A.
Zone Industrielle Haneboesch
L-4562 Differdange, Luxembourg
Telephone:

(352) 58.37.37

Fax:

(352) 58.37.36

e-mail: [email protected]

3. PRODUCT DESCRIPTION

Viking Micromatic

®

Special Response

Sprinklers are small thermosensitive
glass bulb sprinklers available in various
finishes, temperature ratings, and orifice
sizes to meet design requirements.

During fire conditions, the heat-sensitive
liquid in the glass bulb expands, causing
the bulb to shatter, releasing the pip cap
and sealing spring assembly. Water
flowing through the sprinkler orifice
strikes the sprinkler deflector forming a
uniform spray pattern to extinguish or
control the fire.

4. TECHNICAL DATA

LISTINGS AND APPROVALS

Refer to the Approval Chart on pg 125 c.
Glass-bulb fluid temperature rated to

-65 °F (-55 °C).

Factory tested hydrostatically to 500 PSI

(3 448 kPa).

Min. Operating Pressure: 7 PSI (48,3

kPa)

Rated to 175 PSI (1 207 kPa) water

working pressure.

Testing: USA Patent No. 4,831,870
Response Time Index (RTI): 50-80 (ms)

½

SPRINKLER MATERIALS

Frame: Brass Castings UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 4 mm or 5 mm di-

ameter

Belleville Spring Sealing Assembly:

Nickel Alloy, coated on both sides
with Teflon Tape

Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31600, or:
Pip Cap and Insert Assembly: Copper

UNS-C11000 and Stainless Steel
UNS-S30400

Polyester Coated Sprinklers:

Belleville Spring Sealing Assembly:

Exposed

Screw: Nickel Plated

AVAILABLE FINISHES

Brass, Chrome-Enloy

®

(patents pend-

ing), and White Polyester

ACCESSORIES

(order separately)

Sprinkler Wrenches:

A . S t a n d a r d W r e n c h : P a r t N o .

10896W/B (available since 2000) or
05000CW/B (no longer available)

B. Wrench for Coated and Recessed

Sprinklers: Part No. 07398W* (avail-
a b l e s i n c e 1 9 9 0 ) o r P a r t N o .
12144W/B** (available since 2003).

NOTE: Recessed pendent sprin-
klers with protective caps must
use wrench 12144W/B.

*A ½" ratchet is required (not available from Viking).

See the “Sprinkler Accessories” section
of the Viking data book.

5. INSTALLATION

WARNING:

Viking sprinklers are manu-

factured and tested to meet the rigid re-
quirements of approving agencies. The
sprinklers are designed to be installed in
accordance with recognized installation
standards. Deviation from the standards
or any alteration to the sprinkler after it
leaves the factory including, but not lim-
ited to: painting, plating, coating, or
modification, may render the sprinkler
inoperative and would automatically nul-
lify the approval and any guarantee
made by The Viking Corporation.

A. Viking sprinklers are to be installed

in accordance w ith the latest
edition of Viking technical data,
the latest standards of NFPA, FM
G l o b a l ,

L P C B ,

As s e m b l e e

Pleniere, VdS, or other similar or-
ganizations, and also with the pro-
visions of governmental codes,
ordinances, and standards when-
ever applicable.

The use of Special

Response sprinklers may be limited
due to occupancy and hazard. Refer
to the Authority Having Jurisdiction
prior to installation.

B. Sprinklers must be handled with care.

They must be stored in a cool, dry
place in their original shipping con-
tainer. Never install sprinklers that
have been dropped, damaged, or ex-
posed to temperatures exceeding

Form No. F_021396

Sprinkler 125 a

TECHNICAL DATA

November 18, 2005

MICROMATIC

®

SPECIAL RESPONSE

SPRINKLERS

Sprinkler Temperature

Classification

Nominal Sprinkler Temperature

Rating (Fusing Point)

Maximum Ambient

Ceiling Temperature

1

Bulb

Color

2

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

High

286 °F (141 °C)

225 °F (107 °C)

Blue

Sprinkler Finishes:

Brass, Chrome-Enloy

®

, and White Polyester

1

Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and

other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.

2

The temperature rating is stamped on the deflector.

Table 1

Pendent

Upright

Conventional

Replaces page 125 a-c, dated January 28, 2005
(5 mm glass bulb is an alternate).

OBSOLETE

Summary of Contents for MICROMATIC VK134

Page 1: ... No 12144W B available since 2003 NOTE Recessed pendent sprin klers with protective caps must use wrench 12144W B A ratchet is required not available from Viking See the Sprinkler Accessories section of the Viking data book 5 INSTALLATION WARNING Viking sprinklers are manu factured and tested to meet the rigid re quirements of approving agencies The sprinklers are designed to be installed in accor...

Page 2: ...mber 18 2005 MICROMATIC SPECIAL RESPONSE SPRINKLERS TECHNICAL DATA Approval Chart Micromatic Special Response Sprinklers Standard Orifice Thread Size Maximum Pressure Sprinkler Description Nominal K Factor Overall Length Listings and Approvals2 NPT BSP Style Base Part No 1 SIN U S metric4 Inches mm UL C UL FM NYC VdS LPCB 175 psi Pendent3 09224 VK134 5 6 8 1 2 3 16 56 A2X B2Y 15 mm 175 psi Pendent...

Page 3: ...ons 7 MAINTENANCE NOTICE The owner is responsible for maintaining the fire protection system and devices in proper operating condi tion For minimum maintenance and in spection requirements refer to the NFPA standard that describes care and maintenance of sprinkler systems In addition the Authority Having Jurisdic tion may have additional maintenance testing and inspection requirements that must be...

Page 4: ...er cabinet should be provided for this pur pose Follow instructions in sec tion 6 INSTALLATION 3 Place the system back in service and secure all valves Check for and repair all leaks Sprinkler sys tems that have been subjected to a fire must be returned to service as soon as possible The entire system must be inspected for damage and repaired or replaced as necessary Sprinklers that have been expo...