background image

Skylla-IP65

Rev 03 03/2021

ENGLISH

Summary of Contents for Skylla-IP65

Page 1: ...Skylla IP65 Rev 03 03 2021 ENGLISH ...

Page 2: ...5 2 6 Connecting the mains 5 3 Control and Adjustment 6 3 1 Monitor menu 6 3 2 Setup menu 7 3 3 Battery selection 9 3 4 Power supply mode 9 3 5 Temperature compensation dV dT 9 3 6 Power Control maximum use of limited shore current 10 4 Operation 11 4 1 Battery charging 11 4 2 Seven stage charge curve for lead acid batteries 11 4 2 1 Bulk 11 4 2 2 Battery Safe 11 4 2 3 Absorption 12 4 2 4 Automati...

Page 3: ...ls must be provided with uninterruptible grounding for safety purposes An additional grounding point is located on the outside of the product If it can be assumed that the grounding protection is damaged the product should be taken out of operation and prevented from accidentally being put into operation again contact qualified maintenance personnel Ensure that the connection cables are provided w...

Page 4: ...e all openings in the grey terminal block should be closed either with a suitable cable or when no connection is used a dummy piece of cable Connecting earth Connect the earth point to the installation earth Connections to earth have to be according to applicable safety standards On a ship connect to the earth plate or to the hull of the ship On land connect to the earth of the mains The connectio...

Page 5: ... connected to Follow the installation procedure The warranty expires when the Skylla IP65 becomes defective due to reverse polarity Disconnect the mains supply before making or breaking connections to the main battery The starter battery has to be connected using wire of at least 1 5 mm2 max 6 mm2 Connect the positive battery pole to the Starter battery plus connector see Figure 1 The negative pol...

Page 6: ...y external sense and remote shut down The wiring of these signals must be done with the mains disconnected from the charger Figure 1 Connectors for external voltage temperature sensing Rem Shut down VE Can bus and Starter battery 2 5 1 External voltage sense External voltage sensing may be used when accurate battery voltage sensing is important such as high charging currents in combination with lo...

Page 7: ...up Menu 0 Skylla i behaviour on when charging no error condition and battery voltage between low and high voltage settings 12 13 14 and 15 1 Always off 2 Temperature high 85 C 12 and 13 3 Battery voltage too low 4 Equalization active 5 Error condition present 6 Temperature low 20 C 7 Battery voltage too high 14 and 15 8 Charger in float or storage ON CM connected to NO OFF CM connected to NC 2 6 C...

Page 8: ...stments 3 1 Monitor menu The monitor menu is visible when power is applied to the charger The following table shows the consecutive lines when scrolling through the menu with the up down keys Displayed info Icons Segments Units Battery voltage current 14 0 A Battery voltage 14 40 V Battery charge current 60 00 A Battery temperature 1 25 0 Err C F Mains current 1C 3 6 A Battery voltage out 1 2 1 14...

Page 9: ...s Segments Units Function or parameter 01 POWER ON OFF On OFF On off switch 02 MAXIMUM CHARGE CURRENT 1 0 60 0 A Maximum charge current 03 SYSTEM VOLTAGE 12 V System voltage read only 04 CHARGE ALGORITHM 1 2 9 Type Charge algorithm 05 ABSORPTION VOLTAGE 8 0 14 4 15 9 V Absorption voltage 06 FLOAT VOLTAGE 8 0 14 4 15 9 V Float voltage 08 EQUALIZATION VOLTAGE 8 0 15 915 9 V Equalization voltage 09 A...

Page 10: ... POWER SUPPLY VOLTAGE 8 0 12 0 15 9 V Power supply voltage 34 INPUT CURRENT LIMIT 1c 0 0 12 0 A Input current limit 49 BACKLIGHT INTENSITY 0 5 9 The intensity of the backlight 50 BACKLIGHT RELAYS ON OFF ON AUTO Backlight automatic turn off after 60s 51 SCROLL SPEED 1 3 5 Text scroll speed 52 Buzzer y n Buzzer 60 CAN DEVICE INSTANCE dl 0 255 VE Can device instance 61 SOFTWARE VERSION 1 00 Software ...

Page 11: ...OPzS batteries in cyclic mode 2 12 V 14 4 13 8 26 4 15 9 6 max 4hrs 16 24 V 18 8 27 6 13 2 31 8 6 max 4hrs 32 6 PzS tubular plate traction batteries or OPzS batteries in cyclic mode 3 12 V 15 13 8 13 2 15 9 6 max 4hrs 16 24 V 30 27 6 26 4 31 8 6 max 4hrs 32 7 Lithium Iron Phosphate LiFePo4 batteries 12 V 14 2 n a 13 50 n a 0 24 V 28 4 n a 26 7 n a 0 8 Adjustable maximum charge current and absorpti...

Page 12: ...arly exceed 30 C charge current exceeds 15 A per 100 Ah battery capacity Temperature compensation is not required for Li Ion batteries 3 6 Power Control maximum use of limited shore current A maximum mains current can be set in order to avoid interruption of an external fuse in the mains supply Skylla IP65 Page 10 Control and Adjustment ...

Page 13: ...the mains voltage is below normal and the charger is reducing the maximum charge current By using Voltage sensing the actual battery voltage is shown 4 2 Seven stage charge curve for lead acid batteries Figure 3 Voltage and current during different states in battery charging 4 2 1 Bulk Entered when the charger is started or when the battery voltage falls below 13 2 V 26 4 V due to a heavy load dur...

Page 14: ...o compensate for slow self discharge of the battery but will limit water loss and corrosion of the positive plates to a minimum when the battery is not used 4 2 7 Weekly battery refresh Once a week the charger will enter Repeated Absorption mode during one hour to refresh i e to fully charge the battery 4 3 Four stage charge curve for Lithium Iron Phosphate LiFePo4 batteries 4 3 1 Bulk Entered whe...

Page 15: ...ance This charger does not require any specific maintenance However an annual check of the battery and mains connections is recommended Keep the charger dry clean and free of dust Skylla IP65 Page 13 Maintenance ...

Page 16: ...u Select correct battery type in the menu Cable losses too high Use cables with larger cross section Use external voltage sensing The battery is being overcharged The wrong battery type has been selected in the menu Select correct battery type in the menu A battery cell is defective Replace battery Battery temperature too high Overcharging or too fast charging Connect external temperature sensor E...

Page 17: ...7 Temperature Compensation Figure 4 Temperature compensation graph for float and absorption voltages Skylla IP65 Page 15 Temperature Compensation ...

Page 18: ...ting 240 VAC 4A DC rating 4A up to 35 VDC 1 A up to 60 VDC Forced cooling Yes Protection Battery reverse polarity fuse Output short circuit Over temperature Operating temp range 20 to 60 C full output current up to 40 C Humidity non condensing max 95 ENCLOSURE Material Colour steel blue RAL 5012 Battery connection M6 bolts Mains connection screw clamp 6 mm AWG 10 Protection category IP65 Weight kg...

Page 19: ...lure or higher charge current needed 24 Fan failure This error indicates that the fan is powered on but the circuit does not measure any current draw by the fan Most likely the fan is either broken or obstructed Contact your dealer 34 Internal error Contact your dealer 37 No input voltage only for the three output version Mains removed or ac input fuse blown Check mains availability and fuse 65 ch...

Page 20: ...10 Dimensions Skylla IP65 Page 18 Dimensions ...

Reviews: