Phoenix Inverter 

(with firmware xxxx1xx)

 

12 | 3000 | 120V 
24 | 3000 | 120V 
 
 

 

 

Summary of Contents for 12 120V

Page 1: ...Manual EN Appendix Phoenix Inverter with firmware xxxx1xx 12 3000 120V 24 3000 120V ...

Page 2: ......

Page 3: ...Y PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN AS IS BASIS IN NO EVENT SHALL VICTRON ENERGY B V BE LIABLE TO ANYONE FOR SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS THE SOLE AND EXCLUSIVE LIABILITY TO VICTRON ENERGY B V REGARDLESS OF THE FORM OF ACTION SHALL NOT EXCEED THE PURC...

Page 4: ......

Page 5: ...tery is suitable for use with this product The battery manufacturer s safety instructions should always be observed WARNING do not lift heavy objects unassisted Installation Read the installation instructions before commencing installation activities This product is a safety class I device supplied with a ground terminal for safety purposes The chassis must be grounded A grounding point is located...

Page 6: ...ge or transport of the product ensure that the battery leads are disconnected No liability can be accepted for damage in transit if the equipment is not transported in its original packaging Store the product in a dry environment the storage temperature should range from 20 C to 60 C Refer to the battery manufacturer s manual for information on transport storage charging recharging and disposal of...

Page 7: ...r the load to another AC source the automatic transfer switch If an automatic transfer switch is required we recommend to using the MultiPlus or Quattro instead The switch is included in these products and the charger function of the MultiPlus Quattro can be disabled Computers and other electronic equipment will continue to operate without disruption because the MultiPlus Quattro features a very s...

Page 8: ...l is possible with a simple on off switch or with a Phoenix Inverter Control panel 3 3 LED Indications LED off LED flashes LED illuminated Inverter Inverter The inverter is on and supplies power to the load on inverter on Overload low battery off Temperature Inverter The nominal output of the inverter is exceeded The overload LED flashes on inverter on Overload low battery off Temperature ...

Page 9: ...re Inverter The battery is almost fully exhausted on inverter on Overload low battery off Temperature Inverter The inverter has switched off due to low battery voltage on inverter on Overload low battery off temperature Inverter The internal temperature is reaching a critical level on inverter on overload low battery off temperature ...

Page 10: ...alternately the battery is nearly exhausted and the nominal output is exceeded If overload and low battery flash simultaneously the ripple voltage on the battery terminals is too high on inverter on overload low battery off temperature Inverter The inverter switched off due to excess ripple voltage on the battery terminals on inverter on overload low battery off temperature ...

Page 11: ...ve the batteries The Phoenix Inverter is suitable for wall mounting For mounting purposes a hook and two holes are provided at the back of the casing see appendix G The device can be fitted either horizontally or vertically For optimal cooling vertical fitting is preferred The interior of the product must remain accessible after installation Try to keep the distance between the product and the bat...

Page 12: ...m2 2x means two positive and two negative cables Remark Internal resistance is the important factor when working with low capacity batteries Please consult your supplier or the relevant sections of our book electricity on board downloadable from our website Procedure Proceed as follows to connect the battery cables Use an insulated box spanner in order to avoid shorting the battery Avoid shorting ...

Page 13: ...edure The AC output cable can be connected directly to the terminal block AC out 4 4 Optional Connections A number of optional connections are possible 4 4 1 Remote Control The product can be remotely controlled in two ways With an external switch connection terminal H see appendix A Operates only if the switch on the Inverter is set to on With a Phoenix Inverter Control panel connected to one of ...

Page 14: ...d the cross section of the connection between the batteries and the DC distribution point must at least equal the sum of the required cross sections of the connections between the distribution point and the Inverter units Place the units close to each other but allow at least 10cm for ventilation purposes under above and beside the units UTP cables must be connected directly from one unit to the o...

Page 15: ... in the software configuration programs see Section 5 3 Inverter frequency Output frequency Adjustability 50Hz 60Hz Inverter voltage Output voltage of the Inverter Adjustability 95 128V Stand alone parallel operation 2 3 phase setting Using several devices it is possible to increase total inverter power several devices in parallel create a 3 phase system To this end the devices must be mutually co...

Page 16: ...nel except for the multi functional relay and the VirtualSwitch when using VE Net The most common settings including parallel and 3 phase operation can be changed by means of DIP switches see Section 5 5 For changing settings with the computer the following is required VEConfigure3 software You can download the VEConfigure3 software free of charge at www victronenergy com A RJ45 UTP cable and the ...

Page 17: ...of the multi functional relay and the VirtualSwitch 5 5 Configuration with DIP switches A number of settings can be changed using DIP switches see appendix A position I Procedure Turn the Inverter on preferably unloaded Set the DIP switches for o AES Automatic Economy Switch o Inverter voltage o Inverter frequency o selection of stand alone parallel or 3 phase operation To store the settings after...

Page 18: ... or the leader L1 in a 3 phase system In a parallel system the setting of DIP switches ds5 to ds3 need to be done on the master only The slaves will follow the master with regard to these settings hence the master slave relationship In a 3 phase system the Inverter voltage setting is required for the other devices i e the followers for phases L2 and L3 The followers therefore do not follow the lea...

Page 19: ...tand alone mode off DS 8 off DS 7 off DS 6 off DS 5 off DS 4 off DS 3 off DS 2 off DS 1 off DS 8 off DS 7 off DS 6 off DS 5 off DS 4 on DS 3 off DS 2 off DS 1 off DS 8 off DS 7 off DS 6 off DS 5 on DS 4 off DS 3 on DS 2 off DS 1 off stand alone Example 1 factory setting 5 AES off 4 Inverter voltage 120V 3 Inverter frequency 50Hz 2 1 Stand alone mode stand alone Example 2 5 AES off 4 115V 3 60Hz 2 ...

Page 20: ...d ds1 for 3 phase operation Leader L1 Follower L2 Follower L3 DS 8 not used off DS 7 not used off DS 6 not used off DS 5 AES na x DS 4 Inv voltage Set DS 3 Inv freq Set DS 2 Leader on DS 1 Leader off DS 8 not used off DS 7 not used off DS 6 not used off DS 5 na x DS 4 Set DS 3 na x DS 2 L2 off DS 1 L2 off DS 8 not used off DS 7 not used off DS 6 not used off DS 5 na x DS 4 Set DS 3 na x DS 2 L3 of...

Page 21: ...y high load Reduce the load Temperature LED flashes or lights The environmental temperature is high or the load is too high Install the converter in cool and well ventilated environment or reduce the load Low battery and overload LEDs flash intermittently Low battery voltage and excessively high load Charge the batteries disconnect or reduce the load or install higher capacity batteries Fit shorte...

Page 22: ...nverter on LED must flash A flashing overload LED indicates that the device can perform inverter operation A flashing temperature LED indicates that the device is not blocking charge operation This is just a formal indication which originates from the relationship with the Phoenix Multi This indication has no special meaning on a Phoenix Inverter NOTE The low battery LED can function together with...

Page 23: ...teristics Material Colour aluminium blue RAL 5012 Protection IP 21 Battery connection M8 bolts 2 plus and 2 minus connections 230 V AC connection Screw terminals 13mm 6 AWG Weight kg 19kg 42 lbs Dimensions hxwxd in mm 362 x 258 x 218mm 14 3 x 10 2 x 8 6inch STANDARDS Safety EN 60335 1 EN 60335 2 29 Emission Immunity EN 55014 1 EN 61000 3 2 EN 55014 2 EN 61000 3 3 Automotive Directive 2004 104 EC 1...

Page 24: ...t L phase N neutral PE ground E Battery minus Double M8 battery minus connection F Battery plus Double M8 battery positive connection H Connections for remote switch Short left and middle terminal to switch the Phoenix on I Dipswitches DS1 tm DS8 for set up mode J Pushbuttons for set up mode K Alarm contact left to right NC NO COM L Primary ground connection PE ...

Page 25: ...EN Appendix APPENDIX B Block diagram See table in chapter 4 2 Recommended DC fuse ...

Page 26: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...

Page 27: ...EN Appendix APPENDIX G Dimensions ...

Page 28: ...Dimensions 3k cabinet ...

Page 29: ......

Page 30: ...ial number Version 03a Date October 13 th 2016 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 Fax 31 0 36 535 97 40 E mail sales victronenergy com www victronenergy com ...