background image

Liebert® EXM™ TXC™

User Manual—10-100kVA, 60Hz

Summary of Contents for Liebert EXM TXC

Page 1: ...Liebert EXM TXC User Manual 10 100kVA 60Hz...

Page 2: ...r damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in...

Page 3: ...TXC with optional dual transformer cabinet Typical configuration 6 Figure 2 Schematic Liebert EXM TXC to Maintenance Bypass Cabinet 8 Figure 3 Bolting Liebert EXM UPS to a Liebert EXM TXC 9 Figure 4 C...

Page 4: ...0VAC input 208VAC output rectifier input with 480V 208V transformer 20 Table 10 Electrical data Liebert EXM TXC 480VAC input 208VAC output bypass input with 480V 208V transformer 20 Table 11 Electrica...

Page 5: ...lance the cabinet before transporting it Never tilt equipment more than 15 degrees from vertical In case of fire involving electrical equipment use only carbon dioxide fire extinguishers or those appr...

Page 6: ...de composants sous tension sont abrit es derri re un panneau m tallique D autres crans de s curit internes prot gent l quipement en conformit avec les normes IP20 Ne retirez jamais les panneaux ou le...

Page 7: ...ions are required for procedures involving handling installation and maintenance of the UPS system and the internal batteries internal batteries accommodated by the 10 40kVA frame only Observe all saf...

Page 8: ...rte plusieurs circuits haute tension Seuls des quipements d essai con us pour le d pannage doivent tre utilis s Cette mise en garde couvre notamment les oscilloscopes Utilisez toujours des voltm tres...

Page 9: ...These limits provide reasonable protection against harmful interference in a commercial environment This unit generates uses and radiates radio frequency energy and if not installed and used in accord...

Page 10: ...f electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recyc...

Page 11: ...switches and cable connections as required by national and local codes STATIC BYPASS UPS CABINET DUAL TRANSFORMER CABINET MAINTENANCE BYPASS CABINET RIB Rectifier Input Breaker BIB Bypass Isolation Br...

Page 12: ...ground cable from sources 1 and 2 to the TXC ground busbar and tighten them to 192 lb in 22Nm for M10 bolt 5 Connect the neutral cable from sources 1 and 2 to the TXC neutral busbar and tighten them...

Page 13: ...C Ground Busbar Ground D Utility Source 2 TXC Bypass Input TB2 Phase A B C E Utility Neutral 2 TXC Neutral Busbar Neutral C Utility Ground 2 TXC Ground Busbar Ground H TXC GEC Customer GEC GEC Utility...

Page 14: ...t EXM TXC Vertiv Liebert EXM TXC User Manual 10 1 3 BOLTING CABINETS TOGETHER 1 Line up cabinets so that mounting holes are aligned NOTE UPS wiring must be completed before the cabinets are bolted tog...

Page 15: ...ets to fall causing equipment damage personal injury and death Vertiv recommends lifting the units with one of the following methods Installing four eyebolts in the factory fabricated holes one at eac...

Page 16: ...net are moved into their final position Connect input wiring to the Liebert EXM TXC ONLY after the units are internally cabled and positioned Battery cabinets may be bolted only to the left side of th...

Page 17: ...iebert EXM TXC and Maintenance Bypass Cabinet The Liebert EXM TXC must be on right side of the Liebert EXM UPS Liebert EXM UPS connected to Liebert EXM TXC and Battery Cabinets an Maintenance Bypass C...

Page 18: ...iv Liebert EXM TXC User Manual 14 2 0 INSTALLATION DRAWINGS Figure 6 Liebert EXM TXC Main components EXM15010 Rev 1 Transformers FRONT With Cover FRONT Door Removed RIGHT SIDE Panel Removed TB2 TB1 Ne...

Page 19: ...75 44mm Typcial 1 75 44mm Typcial 1 25 32mm 1 5 38mm 1 6 41mm 0 437 11mm 6 Typical 0 38 9 6mm 6 Typical DETAIL C 125A XFMR Lugs 375A XFMR Lugs Notes 1 All dimensions are in inches mm 2 Control wiring...

Page 20: ...wiring and power wiring must be run in separate conduits 7 All wiring is to be in accordance with national and local electrical codes 8 All battery cabinets must be positioned on the left side of the...

Page 21: ...SIDE EXM12009 Rev 1 Notes 1 24 610 minimum clearance above unit for air exhaust 36 914 front access required for service 2 Keep cabinet within 15 degrees of vertical 3 Top and bottom cable entry avail...

Page 22: ...Installation Drawings Vertiv Liebert EXM TXC User Manual 18 Figure 11 Liebert EXM TXC transformer location RIGHT SIDE REAR OF CABINET Transformer T1 Transformer T2...

Page 23: ...ections 10 100kVA system NOTE Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Vertiv when the Liebert EXM TXC and Liebert EXM UPS are ordered as a system Table 2...

Page 24: ...EE Environmental Storage Temperature Range F C 13 F to 158 F 25 C to 70 C Operating Temperature Range F C 32 F to 104 F 0 to 40 C 32 F to 86 F 0 30 C when seismic brackets are used Relative Humidity U...

Page 25: ...6 18 002 5 276 17 784 5 212 100 19 456 5 702 17 762 5 206 19 906 5 834 20 084 5 886 NOTE The breakers and cables used must be in accordance with NEC ANSI NFPA 70 A disconnect breaker must be provided...

Page 26: ...Manual 22 Table 8 Terminal block torque with compression lugs for control wiring AWG Wire Size or Range Torque Lb in Nm 22 14 3 5 to 5 3 0 4 to 0 6 NOTE Refer to the manufacturer s data for proper to...

Page 27: ...tem Input Current A Phase Recommended Upstream Protection A 75 C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 10 13 3W G 20 40 1 8 1 8 M10 15 19 3W G 25 40 1 8 1 8 M10 20 25 3W G 35 40 1 8...

Page 28: ...G 100 200 1 1 1 1 0 M10 100 99 3W G 125 205 1 1 0 1 3 0 M10 See Notes on Tables on page 25 Table 13 Electrical data Liebert EXM TXC 208VAC or 220VAC input rectifier input with 208V 208V or 220V 220V t...

Page 29: ...ull rated output current 5 Input power factor of 0 99 is used for the calculations Table 14 Electrical data Liebert EXM TXC 208VAC or 220VAC input bypass input with 208V 208V or 220V 220V transformer...

Page 30: ...Specifications Vertiv Liebert EXM TXC User Manual 26...

Page 31: ......

Page 32: ...mes and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Co assu...

Reviews: