background image

Z202815-0Q 

Page 1 of 4 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0621 

 

12345 SW Leveton Drive, Tualatin OR  97062 USA

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Metering CTs

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH / 
RISQUE D’ÉLECTROCUTION, D’EXPLOSION OU D’ARC ÉLECTRIQUE

•  Apply appropriate personal protective equipment (PPE) and follow safe electrical

  work practices. See NFPA 70E in the USA or applicable local standards. / Portez

  un équipement de protection individuelle (EPI) approprié et observez les règles

  de sécurité en matière de travaux électriques. Consultez la norme NFPA 70E aux

  États-Unis ou les normes locales applicables.

•   This equipment must only be installed and serviced by qualified electrical

  personnel. / Cet équipement ne doit être installé et entretenu que par du personnel

 qualifié.

•   Turn off all power supplying equipment before working on or inside the equipment. /

  Coupez toutes les équipements d’alimentation électrique avant de travailler sur ou

  dans l’équipement.

•   Product may use multiple voltage/power sources. Disconnect ALL sources before

  servicing. / Le produit est susceptible d’utiliser plusieurs sources de tension,

  d’alimentation. Déconnectez TOUTES les sources avant toute intervention

 d’entretien.

•   Use a properly rated voltage sensing device to confirm that power is off. DO NOT

  depend on this product for voltage indication. / Utilisez un dispositif de détection de

  tension adéquat afin de vérifier que l’alimentation est bien coupée. NE considérez

  PAS ce produit comme un indicateur de tension.

•   Current transformer secondaries must be shorted or connected to a burden at all

  times. / Les secondaires de transformateur de courant doivent être en permanence

  mis en court-circuit ou raccordés à une charge.

•   Products rated only for basic insulation must be installed on insulated conductors. /

  Les produits n’étant conçus que pour une isolation nominale, doivent être installés

  sur des conducteurs isolés.

•   Replace all doors, covers and protective devices before powering the equipment.

  / Replacez toutes les portes, tous les capots et dispositifs de protection avant de

  mettre l’équipement sous tension.

•   This product must be installed inside a suitable fire and electrical enclosure. / Cet

  appareil doit être installé à l’intérieur d’une armoire offrant une protection contre les

  risques électriques et d’incendie.

•   This product is not intended for life or safety applications. / Ce produit n’est pas

  conçu pour les applications de sécurité.

Failure to follow these instructions will result in death or serious 
injury./ Le nonrespect de ces instructions est susceptible d’entraîner l
a mort ou des blessures graves.

DANGER

RISK OF INJURY OR EQUIPMENT DAMAGE/ RISQUE DE BLESSURE 
OU DE DÉTÉRIORATION DE L’ÉQUIPEMENT

•   Do not apply current transducers to circuits having a phase-to-phase voltage

  greater than their voltage rating unless adequate additional insulation is applied

  between the primary conductor and the current transducers. / N’utilisez pas ces

  TC sur des circuits dont la tension entre phases est supérieure à la tension

  nominale indiquée, sauf si une isolation supplémentaire adéquate a été ajoutée

  entre le conducteur primaire et les transducteurs de courant.

•   To reduce the risk of electric shock, always open or disconnect circuit from

  power-distribution system (or service) of building before installing of servicing

  current transformers. / Pour réduire le risque d’électrocution, toujours ouvrir

  ou déconnecter le circuit du système de distribution électrique (ou du service)

  du bâtiment avant toute installation ou intervention sur des transformateurs de

 courant.

•   The current transformers may not be installed in equipment where they exceed

  75 percent of the wiring space of any cross-sectional area within the equipment. /

  Les transformateurs de courant ne doivent pas être installés dans un équipement

  où ils dépasseraient 75 % de l’espace de câblage d’une section de l’équipement.

•   Restrict installation of current transformer in an area where it would block

  ventilation openings. / Éviter l’installation du transformateur de courant dans un

  emplacement où il bloquerait les ouvertures d’aération.

•   Restrict installation of current transformer in area of breaker arc venting. / Éviter

  l’installation du transformateur de courant dans une zone d’échappement d’arc

  électrique d’organe de coupure.

•   Not suitable for Class 2 wiring methods and Not intended for connection to Class

  2 equipment. / Ne convient pas aux méthodes de câblage de Classe 2 et n’est

  pas destiné au raccordement d’équipements de Classe 2.

•   Secure current transformer and route conductors so that they do not directly

  contact live terminals or bus (optional). / Fixer le transformateur de courant en

  position et faire passer les conducteurs de sorte qu’ils ne soient pas en contact

  direct avec les bornes sous tension ni avec le bus (facultatif).

Failure to follow these instructions may result in injury, fire or 
equipment damage. / Le non-respect de ces instructions peut entraîner 
un risque de blessure, d’incendie ou de détérioration de l’équipement.

WARNING/AVERTISSEMENT

Note: Do not use the product if it is damaged. Contact a Veris customer service 

representative for support.

Product Identification

Product Overview

The H681x-V series of 1 volt and 0.333 volt split-core current transformers (CTs) provide secondary AC voltage 
proportional to the primary (sensed) current. For use with power meters, data loggers, chart recorders, and other 
instruments, the H681x-V series CTs provide a cost-effective means to transform electrical service amperages to a 
voltage compatible with monitoring equipment.

H681x-V Series

Split-Core Current Transformers, Voltage Output

0.333 V Models

Description

H6810-100A-.3V (R20)

Split-Core CT, Small, 100A:0.333V

H6810-200A-.3V (R20)

Split-Core CT, Small, 200A:0.333V

H6810-300A-.3V (R20)

Split-Core CT, Small, 300A:0.333V

H6811-400A-.3V (R20)

Split-Core CT, Medium, 400A:0.333V

H6811-600A-.3V (R20)

Split-Core CT, Medium, 600A:0.333V

H6811-800A-.3V (R20)

Split-Core CT, Medium, 800A:0.333V

H6812-800A-.3V (R20)

Split-Core CT, Large, 800A:0.333V

H6812-1000A-.3V (R20) Split-Core CT, Large, 1000A:0.333V
H6812-1200A-.3V (R20) Split-Core CT, Large, 1200A:0.333V
H6812-1600A-.3V (R20) Split-Core CT, Large, 1600A:0.333V
H6812-2000A-.3V (R20) Split-Core CT, Large, 2000A:0.333V
H6812-2400A-.3V (R20) Split-Core CT, Large, 2400A:0.333V
H6810-100A-.3VU  

Split core CT, Small, .3V, 100A UL2808   

H6810-200A-.3VU

Split core CT, Small, .3V, 200A UL2808  

H6810-300A-.3VU

Split core CT, Small, .3V, 300A UL2808  

H6810-400A-.3VU

Split core CT, Small, .3V, 400A UL2808  

H6811-600A-.3VU

Split core CT, Medium, .3V, 600A UL2808  

H6811-800A-.3VU

Split core CT, Medium, .3V, 800A UL2808  

H6812-1000A-.3VU

Split core CT, Large, .3V, 1000A UL2808  

H6812-1200A-.3VU

Split core CT, Large, .3V, 1200A UL2808  

H6812-1600A-.3VU

Split core CT, Large, .3V, 1600A UL2808  

H6812-2000A-.3VU

Split core CT, Large, .3V, 2000A UL2808  

H6812-2400A-.3VU

Split core CT, Large, .3V, 2400A UL2808  

H6812-800A-.3VU

Split core CT, Large, .3V, 800A UL2808

1 V Models

Description

H6810-100A-1V

Split-Core CT, Small, 100A:1V

H6810-200A-1V

Split-Core CT, Small, 200A:1V

H6810-300A-1V

Split-Core CT, Small, 300A:1V

H6811-400A-1V

Split-Core CT, Medium, 400A:1V

H6811-600A-1V

Split-Core CT, Medium, 600A:1V

H6811-800A-1V

Split-Core CT, Medium, 800A:1V

H6812-800A-1V

Split-Core CT, Large, 800A:1V

H6812-1000A-1V

Split-Core CT, Large, 1000A:1V

H6812-1200A-1V

Split-Core CT, Large, 1200A:1V

H6812-1600A-1V

Split-Core CT, Large, 1600A:1V

H6812-2000A-1V

Split-Core CT, Large, 2000A:1V

H6812-2400A-1V

Split-Core CT, Large, 2400A:1V

H6810-100A-1VU

Split core CT, Small, 1V, 100A UL2808   

H6810-200A-1VU

Split core CT, Small, 1V, 200A UL2808  

H6810-300A-1VU

Split core CT, Small, 1V, 300A UL2808  

H6810-400A-1VU

Split core CT, Small, 1V, 400A UL2808  

H6811-600A-1VU

Split core CT, Medium, 1V, 600A UL2808  

H6811-800A-1VU

Split core CT, Medium, 1V, 800A UL2808  

H6812-1000A-1VU Split core CT, Large, 1V, 1000A UL2808  
H6812-1200A-1VU Split core CT, Large, 1V, 1200A UL2808  
H6812-1600A-1VU Split core CT, Large, 1V, 1600A UL2808  
H6812-2000A-1VU Split core CT, Large, 1V, 2000A UL2808  
H6812-2400A-1VU Split core CT, Large, 1V, 2400A UL2808  
H6812-800A-1VU

Split core CT, Large, 1V, 800A UL2808

Subset of models shown.

E150462

E520136

E207042

Summary of Contents for H681-V Series

Page 1: ...où ils dépasseraient 75 de l espace de câblage d une section de l équipement Restrict installation of current transformer in an area where it would block ventilation openings Éviter l installation du transformateur de courant dans un emplacement où il bloquerait les ouvertures d aération Restrict installation of current transformer in area of breaker arc venting Éviter l installation du transforma...

Page 2: ...o 60 C 5 to 140 F Storage Temp Range 40 to 70 C 40 to 158 F Humidity Range 0 to 95 non condensing Altitude of Operation 3 km max Mounting Location Not suitable for wet locations For indoor use only WARRANTY Limited Warranty 5 years COMPLIANCE INFORMATION Agency Approvals UL61010 1 IEC 61010 1 EN 61010 1 Installation Category Category III Pollution Degree 2 INPUTS Frequency Range 50 60 Hz Leads 16 ...

Page 3: ...uct indicating source side H6810 Small UL2808 100 400Amp A 3 23 82 mm B 1 4 36 mm C 1 4 36 mm D 1 12 28 mm E 3 25 83 mm F 4 12 105 mm H6811 Medium UL2808 600 800Amp A 4 95 126 mm B 2 9 74 mm C 2 46 63 mm D 1 2 31 mm E 5 36 136 mm F 5 83 148 mm H6812 Large UL2808 1000 2400Amp A 4 91 125 mm B 5 73 146 mm C 2 47 63 mm D 1 16 30 mm E 8 12 206 mm F 4 91 125 mm B E F C D A A B E C F D A B E C F D Dimens...

Page 4: ...ose the CT with a suitable cable tie Fixer la barre en I à la barre en U de sorte qu elle reste fermement en place Fermer leTC à l aide d un serre câble adapté Failure to follow these instructions may result in injury fire or equipment damage Le non respect de ces instructions peut entraîner un risque de blessure d incendie ou de détérioration de l équipement WARNING AVERTISSEMENT Note These split...

Reviews: