TLR-D5 Engineering Manual

 

TLR-D5  
Intelligent Fan Coil controller, Base & Terminal 

 
Features 

 

Temperature control for 2 and 4-pipe fan coil systems.  

 

Relays switching for each up to 10(6)A 

 

Large temperature range from  
–20°C to 70°C (-4°F to 158°F). 

 

Automatic fan control for three stage fans.  

 

Control for heating, cooling and fan only operation 

 

Cost saving option with Economy functionality and set point limitation 

 

Password protected programmable user and control parameters 

 

External sensor or open contact for remote control, external heat – cool change or auto-changeover on supply 
or outdoor temperature with selectable activation limits One terminal may control up to 8 base units in 
parallel mode 

 

Password protected programmable user and control parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode change 

o

 

Access control for heat/cool change and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in degree Celsius or Fahrenheit 

Deluxe Version: 

o

 

Clock and time schedule functions with special options for schools and universities 

o

 

Clock keeps running for 48h in case of power failure 

o

 

Display with blue backlight 

o

 

Infrared remote controller option:  
With special features for Boost and delayed switching on or off 

Applications 

 

Air Only Systems: Three stage fans for single duct systems. 

 

Air/Water Systems: Induction units, fan coil units for 4-pipe systems 

General Description 

The TLR-D5 is a stand-alone electronic single loop controller with a fan control option and a binary sequence. The 
controller includes 1 NTC room temperature sensor and 3+2 relays outputs. A detailed adaptation to local conditions is 
possible with the use of a simple configuration routine. The TLR-D5 can be configured using the standard operation 
terminal. No special tools or software is required.  
The TLR-D5 has been specifically developed to switch larger fans with switching power of up to 10 (6) A.  

Doc: 70-00-0095 20081223 

©2008 Vector Controls 

Page 1 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Summary of Contents for TLR-D5

Page 1: ...ree Celsius or Fahrenheit Deluxe Version o Clock and time schedule functions with special options for schools and universities o Clock keeps running for 48h in case of power failure o Display with blu...

Page 2: ...W1 40 11 00xx 1 Cooling only Accessories AER D5 24 40 11 0017 Base unit only 24V AER D5 230 40 11 0018 Base unit only 230V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20...

Page 3: ...ransport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conf...

Page 4: ...r if unclear Do not connect directly motors larger than 1kW Connection diagram Connection diagram Power supply L Power supply L Connection terminals Connection terminals RTEXT 0V AC N 2 1 FAN 1 3 Heat...

Page 5: ...not stand out more than 5 mm of the surface of the mounting plate 2 Connect the wires of the terminals to the communication wires according wiring diagram 3 Slide the two latches located on the top of...

Page 6: ...after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will...

Page 7: ...nit is manually switched on while in scheduled off mode The unit will switch automatically off when the reset time defined in UP13 expires Setting UP13 to 0 disables the override reset A blinking cloc...

Page 8: ...e Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The...

Page 9: ...ivated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand Clock settings The remote controlle...

Page 10: ...he menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Range Default UP 00 Enable access to operation modes ON OFF ON En...

Page 11: ...r the fan and heating or cooling stages by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for fan and heating or coolin...

Page 12: ...cannot be overridden by using the terminal or time schedules Connecting the external temperature input to GND returns control of the operation mode to the terminal and time schedule This function may...

Page 13: ...s can be changed on the unit without the need of additional equipment Identifying the firmware version The parameters and functionality of controller depend on its firmware version and revision It is...

Page 14: ...r 3 point OFF Binary DO4 Heating DO5 Cooling ON 3 point output DO4 OPEN DO5 CLOSE ON OFF OFF FC 15 Reversing valve in binary mode 0 no reversing valve DO4 Heating DO5 Cooling 1 reversing valve while h...

Reviews: