Model TN-25 

25.2 (K360) K-factor 

Horizontal Spray Nozzle, Open

Page 1 of 6 

DECEMBER 2020 

TFP850

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

NOTICE

The 

TYCO Model TN-25 Horizontal 

Spray Nozzle

 described herein must 

be installed and maintained in compli-

ance with this document and with the 

applicable standards recognized by any 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The design of individual fixed water 

spray systems for fire protection 

can vary considerably, depending 

on the characteristics and nature of 

the hazard, the basic purpose of the 

spraying system, the configuration of 

the hazard, and wind/draft/ventilation 

conditions. Because of these varia-

tions, the design of fixed water spray 

systems must only be performed by 

experienced designers who thoroughly 

understand the limitations as well as 

capabilities of such systems.
The Tunnel Operator is responsible for 

maintaining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

General 

Description

The TYCO Model TN-25 Horizontal 

Spray Nozzle having a 25.2 (K360) 

K-factor is a specialized open nozzle 

for use in tunnel fire protection deluge 

systems, providing an improved alter-

native to traditional designs. With its 

ability to provide extended coverage, 

the Model TN-25 Nozzle allows for a 

single pipe to run the length of a tunnel, 

compared to traditional designs that 

use multiple pipes in order to provide 

sufficient coverage. The Model TN-25 

Nozzle is an open nozzle designed to 

be integrated into a deluge fire protec-

tion system.
The Model TN-25 Nozzle provides 

protection of coverage areas up to 

16 ft 4 in. x 24 ft 7 in. (5,0 m x 7,5 m) 

as compared to standard coverage 

sprinklers often used in tunnel fire 

protection system designs having a 

maximum coverage area of 10 ft x 10 ft 

(3,0 m x 3,0 m).

Technical 

Data

Approvals

UL and C-UL Listed

Minimum Working Pressure

7 psi (0,5 bar)

Maximum Working Pressure

30 psi (2,1 bar)

Pipe Thread Connections

1 in. NPT or ISO 7-R 1

Discharge Coefficient

K=25.2 gpm/psi

½

 (362,9 Lpm/bar

½

)

Finish

Natural Brass

Physical Characteristics 

Natural Brass

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Deflector Screw  . . . . . . . . . . . . .  Stainless Steel 

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Deflector Nut . . . . . . . . . . . . . . . . . . . . . . .Bronze

Summary of Contents for TN-25

Page 1: ...ers who thoroughly understand the limitations as well as capabilities of such systems The Tunnel Operator is responsible for maintaining their fire protection system and devices in proper operating con dition Contact the installing contrac tor or product manufacturer with any questions General Description The TYCO Model TN 25 Horizontal Spray Nozzle having a 25 2 K360 K factor is a specialized ope...

Page 2: ... 125 mm ARM OVER NIPPLES 2 x 5 LONG DN50 x 125 mm DROP NIPPLE 2 x 8 LONG DN50 x 200 mm DROP NIPPLE 2 x 8 LONG DN50 x 200 mm TEE 2 x 2 x 2 DN50 x DN50 x DN50 FITTING OUTLET 2 DN50 FITTING OUTLET 2 DN50 FITTING OUTLET 2 DN50 FITTING OUTLETS 1 DN25 MAIN MAIN MAIN MAIN USE 1 DN25 MINIMUM PIPE AND FITTINGS USE 1 DN25 MINIMUM PIPE AND FITTINGS USE 1 DN25 MINIMUM PIPE AND FITTINGS ELBOW 90 2 x 2 DN50 x D...

Page 3: ...in the application environment Obstructions The maximum allowable vertical and horizontal distance that the bottom of an obstruction can be away from the Model TN 25 Nozzle is provided in Graph A Non continuous suspended obstruc tions such as air handlers lights and the like are to meet the 4x rule of Figure 6 within 5 ft 152 4 cm of the nozzle deflector in the area below the nozzle the obstructio...

Page 4: ...LE DISTANCE FROM NOZZLE ft SPRAY PROFILES 18 ft BELOW NOZZLE UL testing measured at 18 ft below nozzle Spray Profile Pressure PSI Distance from Nozzle ft 19 7 A 24 10 B 27 15 C 30 20 D 34 25 E 36 5 30 F B F A C D E 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 DISTANCE BELOW NOZZLE m NOZZLE DISTANCE FROM NOZZLE m SPRAY PROFILES 5 5 m BELOW NOZZLE UL testing measured at 5 5 m below nozzle Spray...

Page 5: ...OWED IN AREA ABOVE AND BELOW NOZZLE DEFLECTOR AS DEFINED ON ELEVATION VIEW 3 0 CENTERLINE OF NOZZLE 1 NOTES PLACE LARGE OBSTRUCTIONS SIGNS ETC PARALLEL TO NOZZLE DISCHARGE IN AREAS BETWEEN NOZZLES 4 MAXIMUM LATERAL DISTANCE FROM CENTERLINE OF NOZZLE TO OBSTRUCTION FEET METERS DISTANCE FROM END OF DEFLECTOR TO OBSTRUCTION FEET METERS DISTANCE FROM END OF DEFLECTOR TO OBSTRUCTION FEET METERS 0 OBSTR...

Page 6: ...5 Nozzle into the Reducer Step 3 The Model TN 25 Nozzle must be tightened using only the W Type 1 Sprinkler Wrench as shown in Figure 2 Fully engage the nozzle wrench flats as shown in Figure 1 and wrench tighten A leak tight 1 in NPT or ISO 7 R 1 sprin kler joint should be obtained by apply ing a minimum to maximum torque of 20 to 30 ft lb 26 8 to 40 2 N m Higher levels of torque can distort the ...