Nozzle Model: FN-1024 

Swivels Model: FJ-1006; FJ-1045

 

Instruction and Maintenance Manual

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

II 1 G

 

 

 

 

TATSUNO ULTRA automatic nozzle with single swivel (FJ-1006) 

TATSUNO ULTRA automatic nozzle with double swivel (FJ-1045) 

Summary of Contents for ULTRA

Page 1: ...x TATSUNO ULTRAAutomatic Nozzle Swivels for Fuel Dispenser Nozzle Model FN 1024 Swivels Model FJ 1006 FJ 1045 Instruction and Maintenance Manual II 1 G TATSUNO ULTRA automatic nozzle with single swive...

Page 2: ...to electric shown in this example A general caution is indicated by The circle mark shows banning What is banned is shown inside the circle no fire in this example A general ban is indicated by The b...

Page 3: ...gasoline vapours 2 Turn off cell phones and other electronic devices Electronic devices may ignite gasoline vapours 3 Never pull nozzle lever except when refuelling Never pull nozzle lever unless the...

Page 4: ...c container it may cause fire due to static electricity 7 Return nozzle lever securely After fuelling completely return the nozzle lever fully to the initial position Otherwise fuel may pour out when...

Page 5: ...ustomers to safe place Sprinkle dry sand or the like over the leaking fuel to prevent diffusion Keep fire extinguisher at hand to be ready for fire Prevent entry of vehicles and people to prevent seco...

Page 6: ...x 1 Specification 1 2 Instruction 2 2 1 How to use nozzle 2 2 2 Installation 3 2 3 Testing 4 3 Maintenance 5 3 1 Daily inspection 5 3 2 Periodic inspections 5 4 Trouble Shooting 6 5 Guarantee and Repl...

Page 7: ...andard EN 13012 and EN 13617 4 and each nozzle swivel has been subjected to stringent tests before leaving the factory Specification Model Nozzle FN 1024 Swivels FJ 1006 FJ 1045 Fuel type used Petrol...

Page 8: ...G 1 Do not drop the nozzle onto the ground The nozzle may be damaged and automatic shut off function of the nozzle may not work 2 Insert the nozzle deeply into the fuelling port Otherwise the nozzle m...

Page 9: ...ase of replacing nozzles 4 In case of nozzle swivel replacement use new TATSUNO Gasket to connect with the hose The tightening torque of the screw 70N m 5 Flow test nozzles swivels before putting nozz...

Page 10: ...ow rate is below the maximum flow rate of the dispenser 3 Automatic shut off test Start flow into approved metal test container place nozzle in first latch position Immerse the sensor on nozzle spout...

Page 11: ...according to Testing of 2 3 3 Confirm the pressure controlled safety shut off function of the nozzle according to Testing of 2 3 4 Confirm that the electrical resistance between the nozzle tip and dis...

Page 12: ...and fill again 3 Some filler necks are difficult to refuel Slow down fuel delivery Put on low latch position Nozzle fails to open 1 Pump pressure is not added to the nozzle Check the pump and solenoi...

Page 13: ...e quantity of refuelling 2 500 000L If you have any suggestions as to how we can improve the quality and or readability of this manual then we would be happy to hear from you We can be contacted at th...