background image

www.actionair.co.uk

January 2017

Health and Safety

This process must be undertaken by competent 

persons. More than one person may be required to 

ensure the safe handling of large dampers and other 

materials. Use must be made of access equipment 

to ensure unsafe practices are not used to approach 

walls or difficult access areas.
Standard site PPE should be used (minimum steel 

toe cap boots, hard hat); together with any protective 

eyewear, gloves and masks, when drilling or cutting 

is being undertaken. The latter should also be used 

when handing the wall construction materials, as 

defined by the material suppliers. If loud equipment  

is being used, hearing protection should be used.
All waste materials should be collected and  

disposed of as defined by the relevant supplier.

Vertical in Block Work/Masonry Wall -  

HEVAC/HVCA Installation Frame (IF)

Damper installation method
1. Measure the positions of the building ties on  

the HEVAC frame

2. Mark up the lintel at the top of the hole in the wall 

to give positions that match to the building ties. Drill 

into the lintel and fit stud anchors (not supplied) or 

similar steel fixings e.g. Loden anchors - loop head 

min Ø6.5mm x 63mm.
3. Turn out the building ties on the damper and place 

damper into position, supporting from underneath 

with a block of wood or board, which will need to  

be removed when the mortar is in position.
4. If 4 hour Integrity is required pockets in the wall  

will be required and wall ties turned out into them.
5. Using a Ø1.5mm steel wire (not supplied) wrap this 

round the building ties and the stud anchors in the 

lintel at the top to hold the damper in position. (Note: 

This will also maintain the quality of the link between 

the damper, infill mortar and the wall if a fire occurs)
6. Add mortar from both sides of the damper and infill 

to the HEVAC frame. Take care not to infill past the 

line on the interface shroud.

SmokeShield PTC & FireShield Dampers

HEVAC Frame (I/F) Installation Method

SmokeShield PTC - ES Rated Fire Damper (Fire & Smoke Barrier) 

FireShield - E Rated Fire Damper (Fire Barrier)

Содержание actionair FireShield

Страница 1: ...HEVAC frame 2 Mark up the lintel at the top of the hole in the wall to give positions that match to the building ties Drill into the lintel and fit stud anchors not supplied or similar steel fixings e g Loden anchors loop head min Ø6 5mm x 63mm 3 Turn out the building ties on the damper and place damper into position supporting from underneath with a block of wood or board which will need to be re...

Страница 2: ...ound the building ties and the stud anchors to hold the damper in position Note This will also maintain the quality of the link between the damper infill mortar and the floor slab should a fire occur 5 Shutter beneath the damper if required add mortar from the top of the slab infill to the HEVAC frame Do not to infill past the line on the interface shroud if the motor is to be fitted above the sla...

Страница 3: ...blems are foreseen 8 Using the access opening provided are the damper blades in the open position Check position of damper blades 9 Has the damper been checked for internal cleanliness free from damage and that vertical casings in particular are free from debris With the damper in the closed position inspect for damage 10 Has the damper been released to simulate operation of the thermal release Da...

Страница 4: ...required to be checked as part of the system as often as once per week or month to ensure ongoing confidence in the life safety system This may be seen as analogous to fire alarm systems Procedure 1 The units should be carefully inspected and cleaned of dust and debris 2 The units should then be lubricated with a light oil by wiping this over all the surfaces 3 The mode should be operated to ensur...

Отзывы: