TRANSFORMER SERIES : Omega 30

Operating Manual

Indication

Functional description

Safety instructions

Technical parameters

Before initial operation we ask you to pay full attention to these assembling instructions in order to guarantee the
reliability and to ensure the performance of the device.

Current transformers of the model range Omega are inductive single conductor-current transformers operating
according to the transformer principle. Due to the applicated measuring principle, current transformers of this type
may only be installed in alternating current (AC) networks.

In order to avoid personal and material damage the following assembling steps
must by performed only by authorised, qualified and trained personnel.

If the secondary circuit is operated without a burden/load (open) high voltages
may appear. These voltage values are dangerous for persons as well as for the
functional reliability of the current transformer.

Primary current:

30A to 4000A

Secondary current:

5A

Accuracy class:

(Standard) 0.3, 0.6, 1.2
(Non Standard) 1, 2, 3, 2.4, 4.8

Continuos thermal rating factor:

0.6, 0.8, 1, 1.2, 1.33, 1.5, 2

Rated frequency:

60Hz

Rated continuos thermal
current (standard):

1,0 x In

Rated short time thermal
current Ith:

60 x In, 1 s (Max 40kA)

Basic insulation level:

10kV

Place of installation:

Indoor

Altitude:

up to 2000 m

Ambient temperature:

-30°C to 55

It is forbidden to operate the current transformer without a secondary
circuit (open)!

+ °C

Applied standards:

IEEE C57.13

Low Voltage-Current Transformer -

Omega 30 Series