SUNSYS FJB 

Installations- und bedienungsanleitung 

DE

Manuel d’installation et d’utilisation 

FR

 

Installation and operating manual 

GB

 

Manuale di installazione e uso 

IT

 

Summary of Contents for SUNSYS FJB

Page 1: ...SUNSYS FJB Installations und bedienungsanleitung DE Manuel d installation et d utilisation FR Installation and operating manual GB Manuale di installazione e uso IT ...

Page 2: ......

Page 3: ...NG 7 3 3 ASSEMBLING AND DISASSEMBLING OF THE COVER 8 3 4 FIXING OF THE FIELD JUNCTION BOX 8 4 ELECTRICAL REQUIREMENTS 9 4 1 ELECTRICAL INSTALLATION OPERATION MAINTENANCE 9 4 2 DC SWITCH DISCONNECTOR CABLES CONNECTIONS 9 4 3 REMOTE CONTROLLED DC SWITCH 9 4 4 DC STRINGS CONNECTION 10 4 5 INSTALLING THE FUSES 10 4 6 REFERENCES OF SPARE FUSES 11 4 7 SURGYS SURGE PROTECTION DEVICE SPD 11 4 8 PERIODIC M...

Page 4: ...ts Original spare parts are available through SOCOMEC customer assistance service Check protective devices regularly following the indications in the chapter Electrical installation operation and maintenance Use only fuses of the correct dimensions The rated current of the fuses must be calculated according to each plant specifications The Socomec Field Junction Box must be used in accordance with...

Page 5: ...1008 540 x 540 x 201 Box code Box dimensions H x W x D mm REMOTE DISCONNECTION 12 STRINGS 37PV0012 540 x 720 x 201 37PV1012 540 x 720 x 201 Box code Box dimensions H x W x D mm 16 STRINGS 37PV0016 540 x 810 x 201 37PV1016 540 x 810 x 201 Box code Box dimensions H x W x D mm 24 STRINGS 37PV0024 540 x 1080 x 201 37PV1024 540 x 1080 x 201 Box code Box dimensions H x W x D mm ...

Page 6: ... corrente continua sob tensão Atención Cables de corriente continua bajo tensión Attention Ne pas manœuvrer en charge Attenzione Non operare sotto tensione Achtung Nicht unter last betätigen Attention Do not operate under voltage Atenção Não manipular sob tensão Atención No manipular en carga Label on the cover Label inside the box on the polycarbonate protection screen Product code Product code D...

Page 7: ... the direct exposure to sun radiation Special accessories may be proposed by Socomec 3 2 TRANSPORT INSTRUCTIONS FOR HANDLING CAUTION Do not overturn the Field Junction Box The Field Junction Box can be transported only in horizontal position and in an appropriate manner During transport and storage the Field Junction Box must remain in its original packaging WARNING If visible signs of damages due...

Page 8: ...ews 540 540 270 24 strings 6 fixing screws 540 540 540 Tightening torque of the screws for the reassembling of the cover min max 3 Nm 3 5 Nm 3 3 1 Fixing screws of the cover 3 4 1 Field Junction box fixing screws 3 3 ASSEMBLING AND DISASSEMBLING OF THE COVER Unscrew the fixing screws of the cover using a slotted head screw driver 10 mm 2 x 8 screws for the Field Junction Box 24 strings 1 x 8 and 1 x...

Page 9: ...ip coil on the main switch so that the switch can be remote controlled The trip coil is supplied as an option equipped by the customer 4 ELECTRICAL REQUIREMENTS 4 2 1 Cable gland plate of the DC switch disconnector PE I S O PE I S O PE I S O PE I S O PE I S O PE I S O 4 1 ELECTRICAL INSTALLATION OPERATION MAINTENANCE CAUTION RISK OF ELECTRIC SHOCK Before starting any installation work use personal...

Page 10: ... 1000V compliance with IEC 60269 6 ISC STC max string 10 A PV module peak power current IMPP string 9 A The rated current of the fuses must be calculated for each plant separately See maximum rated current ISC STC and Impp STC values per string in the Technical Characteristics chapter The fuse holder terminals where the strings cables are connected are always live even if the fuse holder is open B...

Page 11: ...22521 Reference of spare plug in module m G51 1000PV 49822529 4 8 PERIODIC MAINTENANCE CHECKS Checklist Cable status Box status Connections status Check tightening torques Fuses status DC switch disconnector status DC switch disconnector remote trip operation Surgys surge protection device Status end of life indicators Periodicity once a year minimum 4 9 STORAGE The Field Junction Box must be stor...

Page 12: ...SUNIFXX01 GB 00 12 5 SCHEME 5 1 SOCOMEC Field Junction Box without monitoring Fuse disconnect RM 32 DV 1000V DC switch disconnector PE cable 62 mini mum must not be green yellow Number of strings Load break Q1 Cross section ...

Page 13: ...7 40 8 10 Connection for rating 16 A 9 10 10 00 9 10 10 00 9 10 10 00 9 10 10 00 Maximum rated current per string at 60 C Impp STC Isc STC A Connection for rating 2 A 1 30 1 40 1 30 1 40 1 30 1 40 1 30 1 40 Connection for rating 4 A 2 40 2 66 2 40 2 66 2 40 2 66 2 40 2 66 Connection for rating 6 A 3 50 3 85 3 60 4 00 3 50 3 85 3 80 4 20 Connection for rating 8 A 4 50 5 00 4 60 5 10 4 50 5 00 4 90 ...

Page 14: ......

Page 15: ......

Page 16: ... SOCOMEC capital 10 816 800 R C S Strasbourg B 548 500 149 B P 60010 1 rue de Westhouse F 67235 Benfeld Cedex FRANCE Tel 33 3 88 57 41 41 Fax 33 3 88 74 08 00 info scp isd socomec com YOUR DISTRIBUTOR IOMSUNIFXX01 GB 00 IOMSUNIFXX01 GB 00 01 2014 ...