Installation and operating manual 

EN

 

Manual de instalación y uso 

ES

 

Manuel d’installation et d’utilisation 

FR

 

Manuale di installazione e uso

IT

Summary of Contents for ITYS 10 kVA

Page 1: ...S 1 0 2 0 k V A CN Installations und bedienungsanleitung DE Installation and operating manual EN Manual de instalaci n y uso ES Manuel d installation et d utilisation FR Manuale di installazione e uso...

Page 2: ...re poor ventilation etc tampering or any unauthorised repair work During the warranty period SOCOMEC reserves the right to decide whether the product should be repaired or whether to replace defective...

Page 3: ...ALLATION 7 3 ELECTRICAL REQUIREMENTS 8 4 REAR VIEW 9 5 CONNECTIONS 11 5 1 OPERATION IN HIGH EFFICIENCY MODE 12 5 2 OPERATION IN CONVERTER MODE 12 6 MIMIC PANEL 13 7 OPERATING MODES 14 7 1 SWITCHING TH...

Page 4: ...equipment connection to an IT power system a four pole device which disconnects all phase conductors and the neutral conductor should be provided in the building wiring installation High electrical v...

Page 5: ...east two people 1 2 BACKFEED PROTECTION If the UPS does not have an automatic protection device against current backfeed the operator installer must attach warning labels to all the mains power discon...

Page 6: ...ment and braking devices to ensure that the unit does not fall over WARNING RISK OF ELECTRIC SHOCK When the equipment is transferred from a cold to a warm place wait approx two hours after unpacking b...

Page 7: ...w at least 0 5 m of space on each side Once the installation is completed the side mounting brackets used in shipping shall be fixed back to ensure the stability of the UPS enclosure If this is not po...

Page 8: ...Model rating Magneto thermal Input Magneto thermal Aux Mains Differential input Input mains cable core size Input mains fuse Aux mains cable core size Output cable core size Battery cable core size P...

Page 9: ...GB 00 4 REAR VIEW AUX slot Neutral switch cover Manual bypass Input and output terminal board ITYS 10 kVA RS232 serial connector USB serial port Slot for optional communication boards Fans Input break...

Page 10: ...4 REAR VIEW Fans Fans ITYS 20 kVA Slot for optional communication boards Neutral switch cover Manual bypass Input and output terminal board RS232 serial connector USB serial port AUX slot Input breake...

Page 11: ...AUTION Use selective differentials Any current dispersed by the loads will be summed to that of the UPS The differential protection must be regulated in cases of loads with high current dispersion NA...

Page 12: ...N LINE mode Thus the use of this mode should be carefully evaluated according to the level of protection required by the application 5 2 OPERATION IN CONVERTER MODE In converter mode the UPS can suppl...

Page 13: ...kVA Ref IOMITYTWXX0C GB 00 6 MIMIC PANEL Normal mode green Fault red Battery yellow Bypass mode yellow ON OFF Up Exit1 Enter Down Bypass Inverter Input Battery status Output Load Output load Alert ico...

Page 14: ...10 20 kVA Ref IOMITYTWXX0C GB 00 7 OPERATING MODES 7 1 SWITCHING THE ITYS ON 7 2 SWITCHING THE ITYS OFF 7 1 3 5 sec 7 1 4 7 1 5 7 2 2 7 2 1 5 sec 7 2 6 7 2 5 Wait for complete shutdown 7 1 1 7 1 2 7 2...

Page 15: ...LEVEL UPS STATUS EVENT LOG OUTPUT OVERLOAD UTILITY ABNORMAL OVER CHARGER MEASUREMENTS OUTPUT TEMPERATURE DC BUS BATTERY BYPASS INPUT LINE INPUT CONTROL BUZZER MUTE Buzzer Mute no SINGLE UPS BATTERY T...

Page 16: ...MATIC BATTERY TEST PERIOD 0 to 31days AUTO RESTART enabled disabled AUTOMATIC OVERLOAD RESTART enabled disabled AUTO BYPASS enabled disabled SHORT CIRCUIT CLEARANCE enabled disabled BYPASS VOLTAGE LOW...

Page 17: ...ng of UPS start up and shutdown procedures For a complete description of software features refer to the UniVision and UniVision Pro documentation 8 2 USB INTERFACE The UPS can communicate with the ser...

Page 18: ...nder Voltage UPS internal fault Consult dealer Fault 23 Bus Unbalance UPS internal fault Consult dealer Fault 24 Bus short UPS internal fault Consult dealer Fault 25 Bus Softstart Fail UPS internal fa...

Page 19: ...l loads Bypass supplies the load first ensure there is no overload then turn on UPS Other No indication no warning tone even though system is connected to mains power supply No input voltage Check the...

Page 20: ...83 3 Frequrency Hz 50 60 10 in normal mode 50 60 0 1 in battery mode Overload Normal Mode 25 C 10 m 1 m 10 s 100 ms kW 105 to 110 110 to 130 130 to 150 150 Voltage distortion 5 Non Linear Load 2 Line...